PIR presence detector for high bay applications - ON/OFF

Technical data sheet: S000105276EN-2 

Updated: 03/02/2021 

Created: 27/11/2018

Cat. No(s): 0 489 59

CONTENTS

 TECHNICAL CHARACTERISTICS (CONTINUED) 

230 V

A

10 A

10 A

10 A

10 A

10 A

230 V

A

10 A

10 A

10 A

10 A

10 A

1 - Halogen lamps
2 -  ELV halogen lamps with 

separate ferromagnetic ballast

3 -  Fluorescent tubes with separate 

ferromagnetic ballast

4 -  Compact fluorescent lamps with 

separate ferromagnetic ballast

5 -  ELV halogen lamps with 

separate electronic ballast

6 -  Fluorescent tubes with separate 

electronic ballast

7 -  Compact fluorescent lamps with 

built-in electronic ballast

8 -  Compact fluorescent lamps with 

separate electronic ballast

9 -  LED lamps with separate 

electronic ballast

10 -  LED lamps with built-in 

electronic ballast

2

7

3

8

5

4

9

1

6

  3. DIMENSIONS

 Detector

Surface mounting accessory

  4. CONNECTION

Wire the products as shown in the diagram.

The auxiliary switch is optional. It can be used to switch the lighting on 

and off.

N

L

L/Out

Absence detection mode

To use absence detection, a push-button must be connected between 

the 2 terminals on the diagram (mains voltage switching).

The unit ships with presence detection as default. To change to absence 

detection, press and release the push-button 5 times within a minute 

of power-up. The LED lights up for 30 seconds to indicate that absence 

detection mode has been selected.

To change back to presence detection, repeat the above procedure: 

the LED flashes for 30 seconds to indicate that presence mode has been 

selected.

Note: The above adjustments can also be made using the infrared 

configurator.

Содержание 0 489 59

Страница 1: ... OFF control of lighting The unit can turn lights on when a room is occupied and off when the room is empty Optional settings allow lights to be turned off in response to ambient daylight These units come complete with accessories that allow changes to the detection area and surface mounting All functionality is fully programmable using an infrared configurator 2 TECHNICAL CHARACTERISTICS PIR sens...

Страница 2: ...th separate electronic ballast 10 LED lamps with built in electronic ballast 2 7 3 8 5 4 9 1 6 3 DIMENSIONS Detector Surface mounting accessory 4 CONNECTION Wire the products as shown in the diagram The auxiliary switch is optional It can be used to switch the lighting on and off N L L Out Absence detection mode To use absence detection a push button must be connected between the 2 terminals on th...

Страница 3: ...ire pivoter comme indiqué ø 64 mm Trou ø 30 mm max 50 mm où 60 mm entraxes de faire pivoter comme indiqué 30 mm max m entraxes de INSTALLATION CONTINUED Surface mounting ø30mmholemax Takecarenottobendthe springswhenfittingthe unit Pull out spring tab and rotate spring arm as shown 50 mm or 60 mm fixing centres ø 64 mm ø30mmholemax Takecarenottobendthe springswhenfittingthe unit Pull out spring tab...

Страница 4: ...ming is completed before affixing the masking shields to the detector The masking shields may impair the light sensor and IR sensors by covering them Ensure correct operation before completing commissioning Ensure correct operation before completing commissioning INSTALLATION CONTINUED Masking shields trimmed for aisle shaped detection Item No Masking shield coverage 1 45 2 32 3 22 4 11 Item No 1 ...

Страница 5: ...t light level using the Lux On Level and Lux Off Level parameters Allumage Extinction Occupation détectée Plus lumineux Plus Sombre Seuil de luminosité Off Seuil de luminosité On Niveau d éclairement Temporisation de luminosité ON Temporisation de luminosité OFF 7 SETTINGS The detector functions are controlled by a number of parameters which can be changed or programmed by an infrared configurator...

Страница 6: ...ready on Off sensitivity 8 9 1 min to 9 max Sensitivity level for detecting movement when the detector is off On delay 0 minutes 0 to 99 minutes The On delay allows the first channel to switch on after the second channel A typical application for this would be when a detector is controlling lighting and air conditioning in an area When the occupant is detected the lighting will be turned on immedi...

Страница 7: ...L Out If the detection range is smaller than expected see the Performance section Rotating the sensor slightly may improve the detection range 2 If the load does not switch off Ensure that the area is left unoccupied for longer than the timeout period Ensure that the detector is not affected by circulating air heaters or lamps 3 In the event of false tripping reduce the sensitivity settings 4 If t...

Страница 8: ...1 STANDARDS Directive CE Installation standards NFC 15 100 Product standards NF EN 60730 1 Environmental standards WEEE Waste Electrical and Electronic Equipment European Directive 2002 95 EC RoHS Restriction of Hazardous Substances Decrees and or regulations Public buildings workplace buildings high rise buildings Conformity EMC 2014 30 EU LVD 2014 35 EU WARNING Always test before using other spe...

Отзывы: