LEGRAND 0 489 59 Скачать руководство пользователя страница 6

6/8

PIR presence detector for high bay applications - ON/OFF

Technical data sheet: S000105276EN-2 

Updated: 03/02/2021 

Created: 27/11/2018

Cat. No(s): 0 489 59

CONTENTS

CONTENTS

  7. SETTINGS (CONTINUED)

Parameter

Default 

value

Value after 

initialisation

Range/

option

Description

General parameters

LED operation 

test

Off

-

ON or Off

When this option is activated, a red LED on the sensor flashes when it detects 

movement. Use this function to check that the sensitivity levels are suitable.

Inhibit 

detection

No

-

Yes/No

Disables presence/absence detection so that the detector does not control 

switching, only dimming. Use this mode for light regulation without automatic 

control according to occupancy.

Timeout

20 minutes

-

0 to 99 

minutes

Once the detector is turned on, this value sets how long the lights will stay on once 

movement has ceased. Select 0 for a 10-second period (for commissioning only).

Manual timeout 

period

10 minutes

-

0 to 99 

minutes

When a manual operation occurs, either via the switch input or the infrared, it 

invokes the timeout period.
Example 1: a detector in presence mode has a detector timeout of 15 minutes and 

a manual timeout of 3 minutes. When the user leaves the room, they press the Off 

button. The sensor will revert to automatic mode after 3 minutes. Walking back into 

the room will turn the lights on.
Example 2: using the settings above, the user turns the lights off (say for a 

presentation) but stays in the room. Every time a movement is detected, the manual 

timeout period is re-triggered, but if it doesn’t pick up anything over a short period, 

the detector will revert to automatic mode. This means that the lights may come on 

inadvertently during the presentation, even if the occupants are still present during 

the manual timeout period, so adjust the timing carefully.

On sensitivity

8

9

1 (min) to 9 

(max) 

Sensitivity level for detecting movement when the detector is already on.

Off sensitivity

8

9

1 (min) to 9 

(max) 

Sensitivity level for detecting movement when the detector is off.

On delay

0 minutes

-

0 to 99 

minutes

The On delay allows the first channel to switch on after the second channel. 

A typical application for this would be when a detector is controlling lighting and air 

conditioning in an area. When the occupant is detected, the lighting will be turned 

on immediately, whereas the air conditioning may be turned on after 15 minutes. If 

the area is vacated before the detector times out, then the air conditioning will not 

have come on. The delay can be set for channel 1 only using this parameter.

Detection mode

Presence

-

Presence or 

absence 

Presence mode allows the output to turn on when movement is detected and 

off when movement ceases. Absence mode allows the output to turn off when 

movement ceases, but must be manually turned on first.

Lux On level

999

200

1-950, 

999: 

OFF 

dimming 

regulation

Sets a minimum light level below which the PIR sensor is enabled, allowing the lights 

to be turned on by movement.

Note: The “Lux Off level” value must always be greater than the “Lux On level” value.

Lux Off level

999

400

1-950, 

999: 

disabled

Sets a maximum light level above which the PIR sensor is disabled, preventing the 

lights from being turned on by movement.

Lux On time

0

-

0 to 99 

minutes

When the ambient light drops below the Lux On Level, this is the delay before 

the lights come on. If at any time during the timed delay the Lux level position is 

reversed, the process is cancelled. A minimum time of 15 seconds is defined for a 

value of 0. If you try to turn on the lights using a manual control, the lights will come 

on regardless of the ambient light level. However, if there is sufficient ambient light, 

they will turn off again after the Lux Off time.

Lux Off time

0

1

0 to 99 

minutes

When the ambient light exceeds the Lux Off Level, this is the delay before the lights 

go out. If at any time during the timed delay the LUX level position is reversed, the 

process is cancelled. A minimum time of approximately 15 seconds is defined for a 

value of 0.

Содержание 0 489 59

Страница 1: ... OFF control of lighting The unit can turn lights on when a room is occupied and off when the room is empty Optional settings allow lights to be turned off in response to ambient daylight These units come complete with accessories that allow changes to the detection area and surface mounting All functionality is fully programmable using an infrared configurator 2 TECHNICAL CHARACTERISTICS PIR sens...

Страница 2: ...th separate electronic ballast 10 LED lamps with built in electronic ballast 2 7 3 8 5 4 9 1 6 3 DIMENSIONS Detector Surface mounting accessory 4 CONNECTION Wire the products as shown in the diagram The auxiliary switch is optional It can be used to switch the lighting on and off N L L Out Absence detection mode To use absence detection a push button must be connected between the 2 terminals on th...

Страница 3: ...ire pivoter comme indiqué ø 64 mm Trou ø 30 mm max 50 mm où 60 mm entraxes de faire pivoter comme indiqué 30 mm max m entraxes de INSTALLATION CONTINUED Surface mounting ø30mmholemax Takecarenottobendthe springswhenfittingthe unit Pull out spring tab and rotate spring arm as shown 50 mm or 60 mm fixing centres ø 64 mm ø30mmholemax Takecarenottobendthe springswhenfittingthe unit Pull out spring tab...

Страница 4: ...ming is completed before affixing the masking shields to the detector The masking shields may impair the light sensor and IR sensors by covering them Ensure correct operation before completing commissioning Ensure correct operation before completing commissioning INSTALLATION CONTINUED Masking shields trimmed for aisle shaped detection Item No Masking shield coverage 1 45 2 32 3 22 4 11 Item No 1 ...

Страница 5: ...t light level using the Lux On Level and Lux Off Level parameters Allumage Extinction Occupation détectée Plus lumineux Plus Sombre Seuil de luminosité Off Seuil de luminosité On Niveau d éclairement Temporisation de luminosité ON Temporisation de luminosité OFF 7 SETTINGS The detector functions are controlled by a number of parameters which can be changed or programmed by an infrared configurator...

Страница 6: ...ready on Off sensitivity 8 9 1 min to 9 max Sensitivity level for detecting movement when the detector is off On delay 0 minutes 0 to 99 minutes The On delay allows the first channel to switch on after the second channel A typical application for this would be when a detector is controlling lighting and air conditioning in an area When the occupant is detected the lighting will be turned on immedi...

Страница 7: ...L Out If the detection range is smaller than expected see the Performance section Rotating the sensor slightly may improve the detection range 2 If the load does not switch off Ensure that the area is left unoccupied for longer than the timeout period Ensure that the detector is not affected by circulating air heaters or lamps 3 In the event of false tripping reduce the sensitivity settings 4 If t...

Страница 8: ...1 STANDARDS Directive CE Installation standards NFC 15 100 Product standards NF EN 60730 1 Environmental standards WEEE Waste Electrical and Electronic Equipment European Directive 2002 95 EC RoHS Restriction of Hazardous Substances Decrees and or regulations Public buildings workplace buildings high rise buildings Conformity EMC 2014 30 EU LVD 2014 35 EU WARNING Always test before using other spe...