3/8
PIR presence detector for high bay applications - ON/OFF
Technical data sheet: S000105276EN-2
Updated: 03/02/2021
Created: 27/11/2018
Cat. No(s): 0 489 59
CONTENTS
5. INSTALLATION
The product is designed to be mounted on the ceiling (surface or flush
mounting), using the accessory provided.
Use the supplied gasket to ensure IP65 rating (not compatible with
surface mounting).
For optimum operation of the lux sensor, the lens must be shielded as
much as possible from the light source.
Avoid direct sunlight being aimed at the sensor.
Do not site within 1 m of forced air heating or ventilation.
Do not fix to a vibrating surface.
Flush mounting
Faire attention à la
compression des
ressorts lors du
montage de l’unité
faire pivoter comme indiqué
ø 64 mm
Trou ø 30 mm max
50 mm où 60 mm entraxes de
Faire attention à la
compression des
ressorts lors du
montage de l’unité
faire pivoter comme indiqué
ø 64 mm
Trou ø 30 mm max
50 mm où 60 mm entraxes de
INSTALLATION (CONTINUED)
Surface mounting
ø 64 mm
ø 30 mm hole max
Take care not to bend the
springs when fitting the
unit
Pull out spring tab and rotate
spring arm as shown
50 mm or 60 mm fixing
centres
ø 64 mm
ø 30 mm hole max
Take care not to bend the
springs when fitting the
unit
Pull out spring tab and rotate
spring arm as shown
50 mm or 60 mm fixing
centres
Faire attention à la
compression des
ressorts lors du
montage de l’unité
faire pivoter comme indiqué
ø 64 mm
Trou ø 30 mm max
50 mm où 60 mm entraxes de
Power-up test procedure
When power is applied to the unit, the load will switch on immediately.
Set the timeout to 10 seconds, vacate the room or remain very still and
wait for the load to switch off.
Check that the load switches on when movement is detected.
The unit is now ready for programming.