Technical data sheet: S000092664EN-1
Updated:
Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
6 . parameterS anD CommUniCation objeCtS (continued)
6 .2 .7 Communication object “Scene control” (continued)
No.
Function
Object
name
Data type
Flags
DPT
1
CHX/Y Store
scene
Store
scene,X
1Bit
C,W,T
1.002
DPT_Bool
It is visible if parameter “Dimming functionality” selected “Dimming
and switching”. Operate with a short operation to input the object
value to carry out the relevant action, such as ON, OFF, TOGGLE.
Telegram value 0 OFF
1 ON
2
CH X
1bit/1byte/2byte,
Group-A…F
Output
1bit/1byte/2byte,
Group-A…F, X
1bit[ON/OFF]
1byte[0..100%]
1byte[0..255]
2byte[Float]
C,W,T, U
1.001 DPT_
Switch
5.001 DPT_
Scaling
5.010 DPT_
Value_
1_Ucount
9.001 DPT_
Value_
Temp
The communication object is used to control the actuator group,
it can control by a 1 bit, 8 bit data or 16 bit data (set by parameter).
When saving the scene, the object “output 1bit/8bit, group A…E” will
be read, and which can be modified and storage on the bus. After the
bus voltage recovery, the value of the object resume to the default
value and the new storage value will be lost.
6 .2 .8 Communication object “Switch sequence”
The communication object “Switching sequence” will be shown in
Fig.6.8. It can modify the object value with an operation step by step. An
object corresponds to one switch level.
Fig.6.8 Communication object "Switching sequence"
No.
Function
Object name
Data
type
Flags
DPT
1~5
CH X level-1(1~5)
Output
level-1 (1~5),
X
1bit
C,T
1.001
DPT_
Switch
The number of the communication object (maximum 5) which
the levels of switch are set by parameter “No. of object”. The
communication object sent on the bus is the object which one of
binary code is modified, which the bit of the binary code had been
changed. The objects are derailed description in the switching
sequence parameter chapter.
6
CH X Level
increment/
decrement
Level
increment /
decrement,
X
1bit
C,W
1.001
DPT_
Switch
The communication object “level increment/decrement, X” is used
to increase/decrease the level of the switch. It will increase one level
when receiving “1” and decrease a level when receiving “0”. The object
is derailed description in the switching sequence parameter chapter.
Table8 Communication object table “Switching sequence”
6 . parameterS anD CommUniCation objeCtS (continued)
6 .2 .9 Communication object “Counter”
The communication object "Counter" will be shown in Fig.6.9. Including
main counter and differential counter communication object, both
these communication objects will start count when the input pulse is
generated with an operation. The data width which has been selected
for both counters can be set to same or different. But the counting is
independent of each other.
Fig.6.9 Communication object “Counter”
No. Function Object
name
Data type
Flags
DPT
1
CHX/Y
Counter
value
Mcounter:
Counter
value,X
1byte[0..255]
2byte[-32768..32767]
2byte[0..65535]
4byte[ -2147470000…
2147470000]
C,T
5.010 DPT_Value_1_Ucount
8.001 DPT_Value_2_Count
7.001 DPT_Value_2_Ucount
13.001 DPT_Value_4_Count
This communication object is used to transmit the current counting value of the main
counter. The counting range depends on data type, which is defined with the parameter
“Data width of counter”.
2
CH X
DCounter
value
Dcounter:
Counter
value, X
1byte[0..255]
2byte[-32768..32767]
2byte[0..65535]
4byte[ -2147470000…
2147470000]
C,T
5.010 DPT_Value_1_Ucount
8.001 DPT_Value_2_Count
7.001 DPT_Value_2_Ucount
13.001 DPT_Value_4_Count
It is visible if enable the parameter “Enable differential counter”. This communication
object is used to transmit the current counting value of the differential counter. The counting
range depends on data type, which is defined with the parameter “Data width of counter”.
3
CH X
DCounte:
Limit
exceeded
DCounter:
Limit
exceeded,
X
1bit
C,T
1.002 DPT_Bool
When the differential count value exceeded the limit value, the object will send telegram
value “1”, which report counting overflow.
4
CH X
DCounter:
Reset
value
CH X
DCounter:
Reset
value, X
1bit
C,W
1.015 DPT_Reset
The communication object is used to reset the count value of differential counter. When
the object receives telegram value “1”, the current count value will become count initial value
(limit value).
5
CH X
DCounter:
Stop
DCounter:
Stop, X
1bit
C,W,T
1.002 DPT_Bool
When the differential counter overflow, the object sends telegram value “0”, which report
count stopping (set in the parameter). Meanwhile, if the object receives telegram value “0”,
the differential counter can also stop counting. If the object receives telegram value “1”, it will
continue counting.
6
CH X
MCounter:
Limit
exceeded
Mcounter:
Limit
exceeded,
X
1bit
C,T
1.002 DPT_Bool
When the main count value exceeded the limit value, the object will send telegram value
“1”, which report counting overflow.
7
CH X
Request
Counter
value
Request
Counter
value, A
1bit
C,W
1.002 DPT_Bool
When the object receives telegram value “1”, the objects “MCounter: Counter value, X” and
“DCounter: Counter value,X” will send their current value on the bus.
Table 9 Communication object table “Counter”