![LEGRAND 0 026 93 Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/legrand/0-026-93/0-026-93_technical-data-manual_1871597002.webp)
2/20
Technical data sheet: S000092664EN-1
Updated:
Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
1 . USe
The KNX binary interface ref. 002693 is a DIN modular device with 4
binary input contacts.The binary inputs serve as interfaces for operation
of EIB/KNX systems via
conventional buttons/switches or for coupling of binary signals (signal
contacts, such as input 24V~230V).
Through its application program the main possible functions are:
•
switch and dimming functions
•
control of blinds and shutters
•
sending of values e.g. temperature values, time...
•
saving and storing of scenes
•
operation of various loads by multiple push button actions
•
operation of several loads in a fixed switching sequence
•
standard counting and differential counting
Each input contact is associated with a red LED which indicates the
status of the contact (OFF = open contact, ON= closed contact)
The KNX inary interface ref.002693 is power supplied via the KNX BUS
and does not need an external power supply.
2 . teChniCal featUreS
2 .1 electrical features
power supply
• Bus voltage 21-30V DC, via the KNX bus
• Current consumption, via KNX bus < 12mA
• Power consumption, via KNX bus < 360mW
input
• Number 4
• Permitted voltage range Un: 0…265V AC/DC
• Input current In: Max.2mA
• Signal level for 0-signal: 0…3V AC/DC
• Signal level for 1-signal: 9……265V AC/DC
• KNX bus via bus connecting terminal
Connections
• EIB/KNX Via bus connection terminal
• Inputs Using screw terminals
• Cable cross-section Multi core 0.2……2.5mm
• Single core 0.2……4.0mm
• Tightening torque Max.0.6 Nm
• Permitted cable length ≤100M(cross section for 1.5mm2)
2 .2 operating/display
• Programming LED and button: For assignment of the physical address
• Channel LED: 1LED per channel for display of the input state
• Manual operation button: 1 button per channel for changing the input
• Manual/Automatic LED: State 1LED for display of the manual/
automatic mode states
• Manual/Automatic button: 1 button for switchover of manual and
automatic mode
2 .3 Climatic features
temperature rang
• Operation: –5 °C ... 45 °C
• Storage: – 25 °C ... 55 °C
• Transport: – 25 °C ... 70 °C
Design
Modular installation device Modular installation device, ProM
installation
On 35mm mounting rails
Weight
0.1kg
3 . DimenSionS
4 . ConneCtion
29V
=
•
Connection
terminals
•
Channel LED
•
Manual operation
button
•
Programming button
•
Programming LED
•
Bus connection
terminal
•
Manual/automatic
LED
5 . StanDarDS anD approvalS
marking
KNX, CE
Certification
KNX approved
Ce certified
note:
All technical information is available at
36.0 mm
64.0 mm
90.0 mm