KNX 4 channels binary input interface

   7 .  parameter Setting DeSCription in the etS (continued)

7 .5 parameter window“preset Channel a~D” (continued)
7 .5 .2  Separately adjustable working mode for binary input 

(continued)

7 .5 .2 .2 Switch/Dimming operation mode

Parameter window “Switch/Dimming” can be shown in Fig.5.10. It is 

visible when Function of the channel “Switch/Dimming” is selected. It is 

possible that switch and dimming the lighting via a button operation.

Fig.7.10 Parameter window “Switch / Dimming. X”

parameter “Connect contact type”
This parameter defines whether the input contact is a normally closed 

or normally open contact.

Options:  Normally open 

Normally closed

The parameters that are described in this chapter are based on normally 

open connect type as example, the normally close connect type is just 

opposite.
parameter “Dimming functionality”
This parameter is used to define whether the lighting can only be 

dimmed or whether it also should be permitted switching. In this case 

a long operation actuated dimming and a short operation actuates 

switching.

Options:  Dimming and switching 

Only dimming

If “Only dimming” is selected, there is no distinction between a short 

and long operation. Therefore the dimming is carried out immediately 

after an operation action; there is not required to determine whether 

the operation is long or short. If “Dimming and switching” is selected, it 

will distinguish the operation is a short or long operation. In this case, 

the lighting is dimmed via a long operation and switched via a short 

operation.
parameter “reaction on short operation”
The parameter is visible if the option dimming and switching has been 

selected with the parameter dimming functionality. It is used to set if 

the value of object “Switch, X” is ON, OFF, TOGGLE, or if no action should 

be occur with short operation.

Options:  No action 

Off 

On 

Toggle

   7 .  parameter Setting DeSCription in the etS (continued)

7 .5 parameter window“preset Channel a~D” (continued)
7 .5 .2  Separately adjustable working mode for binary input 

(continued)

7 .5 .2 .2 Switch/Dimming operation mode (continued)

parameter “reaction on long operation”
The parameter is visible if the option dimming and switching has been 

selected with the parameter dimming functionality. It is used to set 

if the object “dimming, X” sends a brighter or darker telegram with 

long operation. When the operation is over, the object will send a stop 

dimming telegram.

Options:  Dimming BRIGHTER 

Dimming DARKER 

Dim BRIGHTER / DARKER with start BRIGHTER 

Dim BRIGHTER / DARKER with start DARKER

If the option “Dim BRIGHTER / DARKER with start DARKER” is selected, 

the dim command which is the opposite to the last dim command is 

set, and the first action is dimming darker with long operation. Other 

options are similar with the option.
parameter “long operation after”
The parameter is visible if the option dimming and switching has been 

selected with the parameter dimming functionality. Here defines the 

period TL after which an operation is interpreted as “long”.

Options: 0.3s/0.5s/……/10s

parameter “reaction on operation”
The parameter is visible if the option only dimming has been selected 

with the parameter dimming functionality. There is no distinction 

between short and long operation. Therefore the object “dimming, X” 

will send a brighter or darker telegram after an operation trigger. When 

the operation is over, the object will send a stop dimming telegram.

Options:  Dimming BRIGHTER 

Dimming DARKER 

Dim BRIGHTER / DARKER with start BRIGHTER 

Dim BRIGHTER / DARKER with start DARKER

parameter “Debounce time”
This parameter is used to set the debounce time. Debouncing prevents 

unwanted multiple operation of the input, e.g. due to bouncing of the 

contact.

Options: 10ms/20ms/……/150ms/Min. operation

The “Min. operation” can be set in fig.5.8 if the option only dimming has 

been selected with the parameter dimming functionality.
parameter “Dimming mode”

The parameter sets whether the dimming mode is start-stop dimming 

or steps dimming.

Options:  Start-stop dimming

 

Steps dimming

If the option start-stop dimming is selected, it will start the dimming 

mode with a bright or darker telegram and end the dimming mode 

with a stop dimming telegram at the end of operation. The dimming 

telegram need not be cyclically sent in start-stop dimming mode.

If the option step dimming is selected, the dimming telegram is sent 

cyclically during a long operation. The stop telegram ends the dimming 

process at the end of operation.
parameter “brightness change on every sent”
The parameter is visible if the option step dimming has been selected 

with the parameter dimming mode. It is used to set the change 

brightness (in percent) which is cyclically sent with every dim telegram.

Options:   100% 

50% 

... 

1.56%

Содержание 0 026 93

Страница 1: ...ointly adjustable Shutter 4 6 2 4 Communication object Switch 4 6 2 5 Communication object Switch Dimming 4 6 2 6 Communication object Value force output 5 6 2 7 Communication object Scene control 5 6 2 8 Communication object Switch sequence 6 6 2 9 Communication object Counter 6 6 2 10 Communication object Multiple operation 7 6 2 11 Communication object Shutter control 7 7 Parameter setting desc...

Страница 2: ...tion via KNX bus 360mW Input Number 4 Permitted voltage range Un 0 265V AC DC Input current In Max 2mA Signal level for 0 signal 0 3V AC DC Signal level for 1 signal 9 265V AC DC KNX bus via bus connecting terminal Connections EIB KNX Via bus connection terminal Inputs Using screw terminals Cable cross section Multi core 0 2 2 5mm Single core 0 2 4 0mm Tightening torque Max 0 6 Nm Permitted cable ...

Страница 3: ...nient to count the daily consumption Push button with multiple operation For triggering various functions depending on the frequency of the operation A long operation can also be detected and trigger a function Shutter control For movement lamella adjustment of a blind or a shutter via a one push button or two push buttons function Eight preset operating responses are possible in total Channel dis...

Страница 4: ... UpDown This communication object is used to send a shutter moving command up or down to the bus Telegram value 0 move up 1 move down 2 Shutter stop X Y Shutter stop X Y 1bit C T 1 007 DPT_ Step This communication object is used to send a stop shutter moving command Telegram value 0 stop moving 1 stop moving Table 6 3 Communication object table Jointly adjustable Shutter 6 PARAMETERSANDCOMMUNICATI...

Страница 5: ...128 127 1byte 0 255 1byte recall scene 1byte store scene 2byte 32768 32767 2byte 0 65535 2byte Float 3byte time of day 4byte 2147483648 2147483647 4byte 0 4294967 295 1 001 DPT_Switch 6 010 DPT_Value_1_Count 5 010 DPT_Value_1_Ucount 17 001 DPT_SceneControl 18 001 DPT_SceneControl 8 001 DPT_Value_2_Count 7 001 DPT_Value_2_Ucount 9 001 DPT_Value_Temp 10 001 DPT_TimeOfDay 13 001 DPT_Value_4_Count 12 ...

Страница 6: ... in Fig 6 9 Including main counter and differential counter communication object both these communication objects will start count when the input pulse is generated with an operation The data width which has been selected for both counters can be set to same or different But the counting is independent of each other Fig 6 9 Communication object Counter No Function Object name Data type Flags DPT 1...

Страница 7: ...on selected yes Once detected a long operation the object will send telegram value on the bus the telegram is set with the parameter value send object Tele Long operation Table 10 Communication object table Multiple operation 6 2 11 Communication object Shutter control The communication object Shutter Control will be shown in Fig 6 11 Fig 6 11 Communication object Shutter Control 6 PARAMETERSANDCO...

Страница 8: ...rameter Manual Automatic button The parameter defines if the switchover between the manual operation and automatic operation operating states is disabled or enabled using the manual automatic button on the binary input Options Enable Disable by object Enable If the enable disable by object is selected the En Dis Man Auto communication object appears The object receiving telegram value 0 disable th...

Страница 9: ...one button operation Fig 7 5 1 Parameter window Preset Channel A D separately adjustable working mode 7 ParametersettingdescriptionintheETS continued 7 5 Parameter window Preset Channel A D continued Fig 7 5 2 Parameter window Preset Channel A D Jointly adjustable working mode 7 5 1 Jointly adjustable working mode for binary input In the jointly adjustable working mode for binary input each jointl...

Страница 10: ...5 2 1 Switch operating mode continued This parameter defines whether the input distinguishes between a short and long operation If yes is selected there is a delay after opening closing the contact to determine whether there is a short or long operation Only then is a possible reaction triggered The following diagram illustrates the function Input signal TL Possible reaction to the input signal Po...

Страница 11: ...unce period As shown below Input signal TL Detected pulse edge TL TL Once a pulse edge has been detected at the input further edges are ignored for the duration of the debounce time TD The process of preventing debounce in the below chapters are the same with here TD is the effective time of a pulse edge input namely the period after a input signal is recognised as a operation 7 Parametersettingde...

Страница 12: ...he parameter dimming functionality It is used to set if the object dimming X sends a brighter or darker telegram with long operation When the operation is over the object will send a stop dimming telegram Options Dimming BRIGHTER Dimming DARKER Dim BRIGHTER DARKER with start BRIGHTER Dim BRIGHTER DARKER with start DARKER If the option Dim BRIGHTER DARKER with start DARKER is selected the dim comma...

Страница 13: ...ions Normally open Normally closed The parameters that are described in this chapter are based on normally open connect type as example the normally close connect type is just opposite Parameter Long operation after Base Factor 2 255 The parameter is visible if the option yes has been selected with the parameter distinction between long and short operation Here defines the period TL after which an...

Страница 14: ...en the object value 1 will not send out again when long operation The objects Output group A F can be modified via the bus for the duration of the long operation Once the long operation has finished the object Store scene X sends the value 0 on the bus and the current object value can not be modified On the long operation If the object Store scene X receives the value 0 on the bus even the long op...

Страница 15: ...ter No of objects The parameter set the number of communication objects has the same meaning the number of levels max 5 The communication objects level 1 to level 5 are enabled accordingly Options 2level 3level 4level 5level For example parameter 3level means there are 3 communication objects level 1 level 2 and level 3 The first operation modified the value of level 1 the second operation modifie...

Страница 16: ...bouncing prevents unwanted multiple operation of the input e g due to bouncing of the contact Options 10ms 20ms 150ms Min operation The Min operation can be set in fig 5 8 Parameter Enable differential counter The parameter set whether enable the differential counter Options Yes No If this parameter is set to yes the parameter window fig 5 14 3 is displayed 7 ParametersettingdescriptionintheETS co...

Страница 17: ...imit value 1 is preset for every data type to 0 The limit value 2 is preset which depend on the data width of main counter selected and the input field of limit value 2 can be freely edited 7 ParametersettingdescriptionintheETS continued 7 5 Parameter window Preset Channel A D continued 7 5 2 Separately adjustable working mode for binary input continued 7 5 2 6 Counter continued Parameter Send cou...

Страница 18: ...es in detail 3 fold operation as an example the value send for toggle If the option 3 fold operation is selected there are three objects value appear and they are not independent meanwhile they send value according to a certain sequence 1 fold 2 fold 3 fold In order to state clear the following parameter Value on every operation set YES if operation count reach Max number of operations in a certai...

Страница 19: ...apter are based on normally open connect type as example the normally closed connect type is just opposite 7 ParametersettingdescriptionintheETS continued 7 5 Parameter window Preset Channel A D continued 7 5 1 Jointly adjustable working mode for binary input continued 7 5 2 8 Shutter Control continued Parameter Operation functionality type This parameter sets the shutter operating functionality t...

Страница 20: ... operation Options Move up Move down Parameter Reaction on operation It is visible if the shutter operation functionally type is 2 push button moving shutter 2 switch operation moving shutter and 2 pushbutton stepping It is defines the action when operation Different operation functionally type makes different operate action The former two operations functionally type is move up and down the last ...

Отзывы: