LEGRAND 0 026 93 Скачать руководство пользователя страница 17

17/20

ContentS

Technical data sheet: S000092664EN-1 

Updated:  

Created: 03/05/2016

Catalogue number(s): 0 026 93

KNX 4 channels binary input interface

  7 .  parameter Setting DeSCription in the etS (continued)

7 .5 parameter window“preset Channel a~D” (continued)
7 .5 .2  Separately adjustable working mode for binary input 

(continued)

7 .5 .2 .6 Counter (continued)

parameter “Cyclically send counter value: base × factor”
The parameter is used to set the interval time between two telegrams 

that are sent cyclically. Transmission cycle time=Base × Factor.
Base options: 100ms/1s/1min/1h 

Factor options: 1…255

note: 

Counting rules (the mode of counter): 

If a decrementing counter is defined with the parameter “factor: one 

counter step changes counter value by [-10000…10000]”, namely 

negative counting, the initial value is for the high limit value. The 

device counts from the high limit to low limit. When the count value 

is less than low limit value, it will overflow. Then the new count 

value=the count value – the low limit value + the high limit value 

+1, and the device will start continually counting from the new 

count value.
If an incrementing counter is defined with the parameter “factor: 

one counter step changes counter value by [-10000…10000]”, 

namely positive counting, the initial value is for the low limit value. 

The device counts from the low limit to high limit. When the count 

value is greater than the high limit, it will overflow. Then the new 

count value=the count value - the high limit value + the low limit 

value -1, and the device will start continually counting from the new 

count value.
The application program automatically compares the counter 

limit value1 and limit value 2, looks for the high limit value from 

both set limits, and commences to count up or down to suit the 

counting direction. (About the high / low limit value parameters are 

described below). The mode of counter is the same for the main and 

differential counter.
It is important to ensure that both limit values are set to different 

values. If identical end limit values are entered the behaviour of the 

counter cannot be defined.

When disable the counter function, both input scanning and object 

in/out are disabled.Any input status change will be ignored. 

Fig.7.14 (2) Parameter window “Main Counter X”

parameter “Data width of counter”
The data width of the main counter is selected with this parameter. The 

counting range and the data type of the object “Mcounter: Counter 

value, X” depend on this parameter setting.

Options:  8bit [0…255]

 

16bit [-32768…32767] 

 

16bit [0…65535]

 

32bit [-2147470000…2147470000]

parameter “Counter limit value ½”
The parameter is used to set the counter limit value. The limit value 1 is 

preset for every data type to 0. The limit value 2 is preset which depend 

on the data width of main counter selected, and the input field of limit 

value 2 can be freely edited.

  7 .  parameter Setting DeSCription in the etS (continued)

7 .5 parameter window“preset Channel a~D” (continued)
7 .5 .2  Separately adjustable working mode for binary input 

(continued)

7 .5 .2 .6 Counter (continued)

parameter “Send counter value on change”
This parameter is used to select if a change of the counter state is to be 

sent for the main counter.

Options:   Yes 

No

parameter “Send counter value cyclically”
This parameter is used to determine if the counter values are to be sent 

cyclically on the bus for the main counter. The interval time between 

two telegrams that are sent cyclically to be set with the parameter 

“Cyclically send counter value: Base × Factor”.

Options:   Yes 

No

Fig.7.14(3) Parameter window “Differential Counter X”

parameter “Data width of counter”
The data width of the differential counter is selected with this 

parameter. The counting range and the data type of the object 

“DCounter: Counter value, X” depend on this parameter setting.

Options:  8bit [0…255]

 

16bit [-32768…32767]

 

16bit [0…65535]

 

32bit [-2147470000…2147470000]

parameter “Counter limit value ½”
The parameter is used to set the counter limit value1/2. The limit value 

1/2 are preset which depend on the data width of differential counter 

selected, and the input field of limit value 1/2 can be freely edited.
parameter “mode of counter”
The parameter indicates the counting mode of differential counter is the 

same with the main counter.
parameter “When counter crossing limit value”
This parameter sets the reaction when a limit value is reached. Options: 

Continue circular counting Stop until reset
If “Continue circular counting” is selected, the counter continues 

circular counting. If the actual value falls below the low limit value (only 

possible with a decrementing counter) or exceeds the high limit value 

(only possible with an incrementing counter), the new count value is 

set to the start count value and the pulse count is continued. The new 

count value is described in the above chapters.
If “Stop until reset” is selected, the counter stops counting and waits for 

a reset. If the actual value falls below the low limit value (only possible 

with a decrementing counter) or exceeds the high limit value (only 

possible with an incrementing counter), the object “Dcounter: stop, X” 

will send telegram “0" on the bus, and the counter stops counting, until 

the counter value is reset or the object “Dcounter: stop, X” receiving 

telegram “1”. If the object “Dcounter: stop, X” receiving telegram “1”, 

the counter continues circular counting from the new count value. 

If the counter value is reset, it will count from the initial value of the 

parameter. The new count value is described in the above chapters.

Содержание 0 026 93

Страница 1: ...ointly adjustable Shutter 4 6 2 4 Communication object Switch 4 6 2 5 Communication object Switch Dimming 4 6 2 6 Communication object Value force output 5 6 2 7 Communication object Scene control 5 6 2 8 Communication object Switch sequence 6 6 2 9 Communication object Counter 6 6 2 10 Communication object Multiple operation 7 6 2 11 Communication object Shutter control 7 7 Parameter setting desc...

Страница 2: ...tion via KNX bus 360mW Input Number 4 Permitted voltage range Un 0 265V AC DC Input current In Max 2mA Signal level for 0 signal 0 3V AC DC Signal level for 1 signal 9 265V AC DC KNX bus via bus connecting terminal Connections EIB KNX Via bus connection terminal Inputs Using screw terminals Cable cross section Multi core 0 2 2 5mm Single core 0 2 4 0mm Tightening torque Max 0 6 Nm Permitted cable ...

Страница 3: ...nient to count the daily consumption Push button with multiple operation For triggering various functions depending on the frequency of the operation A long operation can also be detected and trigger a function Shutter control For movement lamella adjustment of a blind or a shutter via a one push button or two push buttons function Eight preset operating responses are possible in total Channel dis...

Страница 4: ... UpDown This communication object is used to send a shutter moving command up or down to the bus Telegram value 0 move up 1 move down 2 Shutter stop X Y Shutter stop X Y 1bit C T 1 007 DPT_ Step This communication object is used to send a stop shutter moving command Telegram value 0 stop moving 1 stop moving Table 6 3 Communication object table Jointly adjustable Shutter 6 PARAMETERSANDCOMMUNICATI...

Страница 5: ...128 127 1byte 0 255 1byte recall scene 1byte store scene 2byte 32768 32767 2byte 0 65535 2byte Float 3byte time of day 4byte 2147483648 2147483647 4byte 0 4294967 295 1 001 DPT_Switch 6 010 DPT_Value_1_Count 5 010 DPT_Value_1_Ucount 17 001 DPT_SceneControl 18 001 DPT_SceneControl 8 001 DPT_Value_2_Count 7 001 DPT_Value_2_Ucount 9 001 DPT_Value_Temp 10 001 DPT_TimeOfDay 13 001 DPT_Value_4_Count 12 ...

Страница 6: ... in Fig 6 9 Including main counter and differential counter communication object both these communication objects will start count when the input pulse is generated with an operation The data width which has been selected for both counters can be set to same or different But the counting is independent of each other Fig 6 9 Communication object Counter No Function Object name Data type Flags DPT 1...

Страница 7: ...on selected yes Once detected a long operation the object will send telegram value on the bus the telegram is set with the parameter value send object Tele Long operation Table 10 Communication object table Multiple operation 6 2 11 Communication object Shutter control The communication object Shutter Control will be shown in Fig 6 11 Fig 6 11 Communication object Shutter Control 6 PARAMETERSANDCO...

Страница 8: ...rameter Manual Automatic button The parameter defines if the switchover between the manual operation and automatic operation operating states is disabled or enabled using the manual automatic button on the binary input Options Enable Disable by object Enable If the enable disable by object is selected the En Dis Man Auto communication object appears The object receiving telegram value 0 disable th...

Страница 9: ...one button operation Fig 7 5 1 Parameter window Preset Channel A D separately adjustable working mode 7 ParametersettingdescriptionintheETS continued 7 5 Parameter window Preset Channel A D continued Fig 7 5 2 Parameter window Preset Channel A D Jointly adjustable working mode 7 5 1 Jointly adjustable working mode for binary input In the jointly adjustable working mode for binary input each jointl...

Страница 10: ...5 2 1 Switch operating mode continued This parameter defines whether the input distinguishes between a short and long operation If yes is selected there is a delay after opening closing the contact to determine whether there is a short or long operation Only then is a possible reaction triggered The following diagram illustrates the function Input signal TL Possible reaction to the input signal Po...

Страница 11: ...unce period As shown below Input signal TL Detected pulse edge TL TL Once a pulse edge has been detected at the input further edges are ignored for the duration of the debounce time TD The process of preventing debounce in the below chapters are the same with here TD is the effective time of a pulse edge input namely the period after a input signal is recognised as a operation 7 Parametersettingde...

Страница 12: ...he parameter dimming functionality It is used to set if the object dimming X sends a brighter or darker telegram with long operation When the operation is over the object will send a stop dimming telegram Options Dimming BRIGHTER Dimming DARKER Dim BRIGHTER DARKER with start BRIGHTER Dim BRIGHTER DARKER with start DARKER If the option Dim BRIGHTER DARKER with start DARKER is selected the dim comma...

Страница 13: ...ions Normally open Normally closed The parameters that are described in this chapter are based on normally open connect type as example the normally close connect type is just opposite Parameter Long operation after Base Factor 2 255 The parameter is visible if the option yes has been selected with the parameter distinction between long and short operation Here defines the period TL after which an...

Страница 14: ...en the object value 1 will not send out again when long operation The objects Output group A F can be modified via the bus for the duration of the long operation Once the long operation has finished the object Store scene X sends the value 0 on the bus and the current object value can not be modified On the long operation If the object Store scene X receives the value 0 on the bus even the long op...

Страница 15: ...ter No of objects The parameter set the number of communication objects has the same meaning the number of levels max 5 The communication objects level 1 to level 5 are enabled accordingly Options 2level 3level 4level 5level For example parameter 3level means there are 3 communication objects level 1 level 2 and level 3 The first operation modified the value of level 1 the second operation modifie...

Страница 16: ...bouncing prevents unwanted multiple operation of the input e g due to bouncing of the contact Options 10ms 20ms 150ms Min operation The Min operation can be set in fig 5 8 Parameter Enable differential counter The parameter set whether enable the differential counter Options Yes No If this parameter is set to yes the parameter window fig 5 14 3 is displayed 7 ParametersettingdescriptionintheETS co...

Страница 17: ...imit value 1 is preset for every data type to 0 The limit value 2 is preset which depend on the data width of main counter selected and the input field of limit value 2 can be freely edited 7 ParametersettingdescriptionintheETS continued 7 5 Parameter window Preset Channel A D continued 7 5 2 Separately adjustable working mode for binary input continued 7 5 2 6 Counter continued Parameter Send cou...

Страница 18: ...es in detail 3 fold operation as an example the value send for toggle If the option 3 fold operation is selected there are three objects value appear and they are not independent meanwhile they send value according to a certain sequence 1 fold 2 fold 3 fold In order to state clear the following parameter Value on every operation set YES if operation count reach Max number of operations in a certai...

Страница 19: ...apter are based on normally open connect type as example the normally closed connect type is just opposite 7 ParametersettingdescriptionintheETS continued 7 5 Parameter window Preset Channel A D continued 7 5 1 Jointly adjustable working mode for binary input continued 7 5 2 8 Shutter Control continued Parameter Operation functionality type This parameter sets the shutter operating functionality t...

Страница 20: ... operation Options Move up Move down Parameter Reaction on operation It is visible if the shutter operation functionally type is 2 push button moving shutter 2 switch operation moving shutter and 2 pushbutton stepping It is defines the action when operation Different operation functionally type makes different operate action The former two operations functionally type is move up and down the last ...

Отзывы: