DISPLAY TOTAL CYCLE COUNT
The Main Control Board counts the number of cycles the
appliance has operated. In the Main Control Board, a cycle is
counted every time the gas valve is energized. To access this
number, perform the following procedure:
1. Press the SELECT push-button on the display board until the
LED display reads OPt (Options).
2. To enter into the options mode, press the ENTER push-button.
3. The display will show Circ. Press the SELECT push-button
until the display shows Count. Enter this mode by pressing
the ENTER push-button.
4. The display will now show the current number of cycles the
appliance has cycled through.
5. The display will automatically resort to show the outlet
temperature
TANK PROBE TEMPERATURE SET-POINT
ADJUSTMENT PROCEDURE
The user can easily change the water temperature set-point at
any time by using the following procedure:
1. Press the SELECT push-button on the display board until both
the Set-Pt LED (LED D, see figure 21) and Inlet Water
Temperature LED (LED A, see figure 21) are illuminated.
NOTE : When a third probe is installed on the board at location
CN10, the Inlet Water Temperature LED defaults to Tank Water
Temperature.
2. The LED display will show the current set-point temperature.
3. Press and hold the ADJUST push-button. The displayed
temperature will either increase or decrease. To alternate
between increasing or decreasing the temperature, release
then press and hold the ADJUST push-button.
4. When the desired set-point temperature is reached, release
the ADJUST push-button.
5. Press the ENTER push-button once, this enters the selected
tank set-point temperature into controller memory.
6. The appliance will now control the water temperature to the
desired set-point value.
value (or 50°F [28°C], the maximum value) and stop. At this point,
if the desired switching differential is not obtained, release the
ADJUST push-button and depress it again. The switching
differential value will now start at 5°F (3°C) to (50°F [28°C]) and
once again increase (decrease) in value for as long as the ADJUST
push-button is pressed.
CIRCULATING PUMP
ADJUSTMENT PROCEDURE
The Controller is factory set with a 45 second post circulate
function. With the Display Board, the user has the capability to
choose between a 45, 90, or 180 second post circulate time
period, or turn the pump on continuously. This provides flexibility
in selecting the post circulate time to meet specific installation
requirements, and improves the efficiency of the circulating pump
operation.
NOTE: It is recommended that intermittent post circulate pump
modes be used for maximum efficiency.
To change or view the current programmed post-circulating time:
1. Press the SELECT push-button on the display board until the
LED display reads OPt (Options).
2. To enter into the options mode, press the ENTER push-button.
3. The display will illustrate Circ. Enter this mode by pressing
the ENTER push-button.
4. The display will now illustrate the current post circulate time.
Press the ADJUST push-button to select the desired post
circulate time (45, 90, 180, On).
5. When you have selected the desired post circulate time mode,
press the ENTER push-button once, this enters the selected
post circulate time into controller memory.
6. The display will automatically return to showing the outlet
temperature.
DISPLAY CURRENT MODE
In this mode, the Display Board will show the current functional
step in the appliance operational sequence. For example, if the
appliance is performing Ignitor Warm-up, the display will show
IGnt. To enter into this mode, perform the following steps:
1. Press the SELECT push-button on the display board until the
LED display reads OPt (Options).
2. To enter into the options mode, press the ENTER push-button.
3. The display will show Circ. Press the SELECT push-button
until the display shows StEP. Enter this mode by pressing the
ENTER push-button.
4. The display will show the current appliance operating step.
5. The display will automatically resort to illustrating the outlet
temperature, after five (5) seconds. To keep the display in the
Display Step Mode, press ENTER twice in step 3.
Table 10.
Display Message
Appliance Mode
IdLe
Idle state
NoSn
Wait for No Sensor Inputs
CrSn
Wait for Circulate Sense
Circ
Circulate Pump is ON
PrSn
Wait for Blower Pressure Sense
PreP
Pre-Purge state
IGnt
Ignitor Warm-up
rEdn
Turn ON redundant Gas Valve relay
IAct
Turn ON Gas Valves
StAb
Turn OFF Ignitor and wait for Flame
Sense Stabilization
HEAt
Heat Mode
PoPC
Post Purge and Post Circulate
Po C
Post Circulate