18
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE
TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE
CONTROL WARNING ON PAGE 28. IF HIGHER PREHEAT
TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE
BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT
WATER SUPPLIED TO FIXTURES.
ONE LEGEND (MODEL LW) HOT WATER SUPPLY BOILER WITH VERTICAL TANK
FIGURE 13.
INSTALL THERMAL EXPANSION
TANK ON COLD WATER SUPPLY
LINE, IF CHECK VALVE OR
PRESSURE REDUCING VALVE IS
USED IN SUPPLY.
ONE LEGEND (MODEL LW) HOT WATER SUPPLY BOILER WITH HORIZONTAL TANK
DANGER
TEMPERATURE SETTING SHOULD NOT
EXCEED SAFE USE TEMPERATURE AT
FIXTURES. SEE WATER TEMPERATURE
CONTROL WARNING ON PAGE 28. IF
HIGHER PREHEAT TEMP-ERATURES ARE
NECESSARY TO OBTAIN ADEQUATE
BOOSTER OUTPUT, ADD AN ANTI-
SCALD VALVE FOR HOT WATER
SUPPLIED TO FIXTURES.
INSTALL THERMAL
EXPANSION TANK ON
COLD WATER SUPPLY
LINE, IF CHECK VALVE
OR PRESSURE
REDUCING VALVE IS
USED IN SUPPLY.
INSTALL IN ACCORDANCE WITH ALL LOCAL CODES.
PRESSURE RELIEF VALVE RATING SHOULD NOT EXCEED PRESSURE
CAPACITY OF ANY COMPONENT IN THE SYSTEM.
INSTALL TEMPERATURE, PRESSURE GAUGE AND PRESSURE RELIEF AS
CLOSE TO BOILER OUTLET AS POSSIBLE.
SHUTOFF VALVES SHOULD BE INSTALLED FOR SERVICING BOILER,
LOCAL CODES SHALL GOVERN THEIR USAGE.
SAFETY RELIEF VALVE SETTING SHOULD NOT EXCEED PRESSURE
RATING OF ANY COMPONENT IN THE SYSTEM.
STOP VALVES ARE SHOWN FOR SERVICING BOILER. HOWEVER, LOCAL
CODES SHALL GOVERN THEIR USAGE.
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW
PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE,
PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER
SYSTEM MUST BE PROVIDED.
FIGURE 14.