background image

                                                 

H2-506 Vector Easy Servo Drive User Manual Version 1.0

 

Leadshine Technology Co., Ltd   

 

 

 

 

 

 

 

 

11/F, Block A3, iPark, No.1001 Xueyuan Blvd. Shenzhen, China 

Tel: 1-949-608-7270      Fax: 1-949-608-7298 

Web

:

 

www.leadshine.com

 

Email:

 

[email protected]

 

           

   

 

Key Parameters   

 

 

 

 

 

 

NO. in Protuner 

NO. on HMI panel 

Position Loop Kp

 

Range 

unit  default 

30053 

0—10000

 

  - 

100 

You can determine the response of the positional control system. Higher the gain of position loop you set, 

faster the positioning time you can obtain. Note that too high setup may cause vibration. Set a value as large 

as possible base on the machine without shout.

 

NO. in Protuner 

NO. on HMI panel 

Speed loop Ki

 

Range 

unit  default 

30055 

0—10000

 

  - 

60

 

You can set up the integration time constant of speed loop, Smaller the set up, faster you can dog-in 

deviation at stall to 0. Set a value as small as possible base on the machine without vibration.

 

NO. in Protuner 

NO. on HMI panel 

Speed loop Kp

 

Range 

unit  default 

30054 

0—10000

 

  - 

100 

You  can  determine  the  response  of  the  velocity  loop.  In  order  to  increase  the  response  of  overall  servo 
system by setting high velocity loop gain. However, too high setup may cause vibration. Set a value as large 
as possible base on the machine without shout. 

NO. in Protuner 

NO. on HMI panel 

Pulse /Rev.

 

Range 

unit  default 

200—65535

 

  - 

1600 

Pulse per Revolution. 

NO. in Protuner 

NO. on HMI panel 

Encoder resolution

 

Range 

unit  default 

29 

200—20000

 

  - 

4000 

The encoder of easy servo motor from Leadshine is 1000, 2500, 5000PPR, so If you use these motors, the 
value must be 4000, 10000, 20000 respectively. The recommend encoder is 5000 lines . 

NO. in Protuner 

NO. on HMI panel 

Position following error

 

Range 

unit 

default 

30

 

9

 

1—65535

 

4000 

The  tolerance  for  position  following  error,  if  the  error  is  over  this  value  of  setting,  drive  will  display 
ERR20 . 

NO. in Protuner 

NO. on HMI panel 

Lock 

Shaft 

Current 

Percentage( power on)

 

Range 

unit 

default 

30007

 

10

 

1—100

 

0.1A 

40 

The current uses for locking the motor shaft when, it is effective only when NO.30015 in ProTnuer is set to 
3or 4. And if the parameter No.24 in ProTuner is set to 0 (Open-loop), this current will be peak current for 
motor. 

Содержание Vector Easy H2-506

Страница 1: ...506 Vector Easy Servo Drive Revision 1 0 2016 Leadshine Technology Co Ltd Address 11 F Block A3 iPark No 1001 Xueyuan Blvd Nanshan District Shenzhen China Tel 86 400 885 5521 Fax 86 755 2640 2718 Web...

Страница 2: ...red in retrieval form or transmitted by any means electronic mechanical photocopying recording or otherwise without approval from Leadshine While every precaution has been taken in the preparation of...

Страница 3: ...Mechanical Specifications 5 2 4 Operating Environment 5 3 Connectors and Pin Assignments 6 3 1 Control Signal Connector CN1 6 3 2 Encoder Signal Input CN2 7 3 3 RS232 Communication Connector for Tunin...

Страница 4: ...ime quick acceleration and very high high speed torque 30 over open loop Load dependent dynamic current output from drive to motor to significantly motor heating deduction Input voltage from 24 to 50V...

Страница 5: ...e Disable Input Differential Alarm Signal Output Isolated OC Output Encoder Signal Output ABZ Output Tuning Interface On board HMI or RS232 communication Regeneration Resistor Built in 50 Ohm 100W Sup...

Страница 6: ...NNECTED ENABLED Please note that the PNP and Differential control signals are on the contrary namely Low level for enabling The active level of ENA signal is software configurable 2 ENA 3 PUL I Pulse...

Страница 7: ...D 10 Pend O In position Signal OC output signal active when the difference between the actual position and the command position is zero This port can sink or source 20mA current at 24V The resistance...

Страница 8: ...Connection 10 NC I No Connection 11 EA I Encoder A input 12 EB I Encoder B input 13 VCC O 5V power output 14 NC I No Connection 15 NC I No Connection 3 3 RS232 Communication Connector for Tuning CN3 C...

Страница 9: ...eb www leadshine com Email tech leadshine com 3 PE I 4 A O Motor phase A 5 A O Motor phase A 6 B O Motor phase B 7 B O Motor phase B 3 4 Connector Pin Out CN1 Control Signal Connector CN2 Feedback Sig...

Страница 10: ...4 E5Z ES2 M22327 E5Z Wiring Diagram Step Angle 1 8 1 8 1 8 Holding Torque N m 1 4 2 4 2 0 Phase Current A 4 0 5 0 5 0 Phase Resistance Ohm 0 42 0 38 0 44 Phase Inductance mH 1 6 1 75 2 0 Shaft Inertia...

Страница 11: ...power is used to energize the motor and the control power is used for logic circuit Typically they can share the same AC power 4 1 2 Control Signal Wiring Drive Controller VCC PUL PUL ENA PUL DIR ENAB...

Страница 12: ...otor wires should not be tied up together It is better to separate them by at least 10 cm otherwise the disturbing signals generated by motor will easily disturb pulse direction signals causing motor...

Страница 13: ...not less than 2 5s d t4 Low level width not less than 2 5s 4 3 Configuring H2 506 4 3 1 Configuring H2 506 by the on board HMI Users can configure the drive via the on board HMI in the front panel Thi...

Страница 14: ...xiliary Function Write to EEPROM Start Writing Writing Completes ENT M M M Operation Procedure of the on board HMI Display Data Mode This mode is active initially at drive s power up In this mode user...

Страница 15: ...value Range Description ProTuner Panel 15 0 Current loop Kp R W 0 0 65535 Invalid 16 1 Current loop Ki R W 0 0 65535 Invalid 124 2 Tuning proportionality for Current loop R W S 100 0 1024 Unit This pa...

Страница 16: ...200 1 2000 These parameters are effective when running the motor with HMI panel 22 Speed R W 60 1 3000 23 Distance R W 100 1 65535 24 Running times R W 1 1 65535 25 Start direction R W 1 0 1 26 Runni...

Страница 17: ...nvalid 30011 47 Time Constant for Over Voltage Detection R W S 2 0 20 Unit 100ms 30014 48 Voltage Limited Value for Enabling Brake Resistor R W S 72 0 500 Unit V 30013 49 Brake Resistor Enable R W S 1...

Страница 18: ...W S 0 0 255 Invalid 133 65 Position loop KpH R W S 100 0 1000 30051 66 Rigidity R W S 0 0 31 Invalid 30052 67 Inertia ratio R W S 100 100 10000 Invalid 30057 68 Speed feed forward R W S 28 0 32 30060...

Страница 19: ...can determine the response of the velocity loop In order to increase the response of overall servo system by setting high velocity loop gain However too high setup may cause vibration Set a value as l...

Страница 20: ...l Range unit default 59 42 0 100 3 1 ES2 M21706 E2 2 ES2 M21708 E2 3 ES2 M22320 E5 4 ES2 M22310 E5 5 ES2 M22430 E5 Set correctly codebase on the motor model you are using Not to be recommended connect...

Страница 21: ...etermining the problem should you need assistance Many of the problems that affect motion control systems can be traced to electrical noise controller software errors or mistake in wiring Problem Symp...

Страница 22: ...ervice at e mail before returning product for service Customer shall prepay shipping charges for products returned to Leadshine for warranty service and Leadshine shall pay for return of products to c...

Отзывы: