3 OPERATION DESCRIPTION:
3.1 TURNING ON
Select the origin of the power supply of the equipment according to 4.1. Connect the power
cord to the connector "POWER" on the rear part of the equipment or power it directly from the
ACSI bus. An indicator checking sequence will appear in the front part of the equipment. Once the
sequence is conclude, the linking process with the system will start and it will be indicated by the
corresponding indicator (LNK).
When the equipment is turned on for the first time, typical adjustments of the installation
must be done (see section 4.2)
3.2 EMERGENCY
3.2.1 ACTIVATING EMERGENCY CONDITION
To give an evacuation notice, the system must be in an emergency condition. This mode of
operation will be able to issue the following notices types:
•
Recorded alert message
•
Recorded evacuation message
•
Live message from emergency microphone
To activate the emergency mode, proceed as follows:
Remove the protective cover of the "EMG" button and push the button. If the equipment
has priority to activate the emergency condition, the "EMG" indicator will light up.
When the emergency condition is activated, an audible warning signal will be activated.
This signal will be automatically muted when using the emergency microphone or manually by
pushing the "ACK" key.
3.2.2 ISSUING VOICE WARNING
Once the emergency condition is activated, you will be able to select the following options
to make a voice warning:
•
Issuing a recorded warning message: "EVAC"
•
Issuing a recorded evacuation message: "ALERT"
•
Issuing a live message from the microphone: "EMIC"
To issue a voice warning, if you have an expansion keyboard, select the zone memories
where you want to deliver the notice, their selection indicators will light up. In case you do not have
expansion keyboards, or have not made any selection, all the zone memories will be selected
automatically. Then press the "EVAC", "ALERT" or "TALK" button to issue recorded evacuation,
alert, or live messages respectively.
Simultaneously, it can issue a recorded message and a live message in the same or
different selection from the message that is being issued. The priority of the emergency sources
from higher to lower importance: live message from emergency microphone, recorded evacuation
message, recorded alert message. If an evacuation message is issued in a zone memory or
memories the alert message will stop immediately.
If you want to change the zone memories where it is being issued, make a new selection
and then press again on the type of alarm that you want to issue.
NOTE: The previous zone memories selection will disappear when you make a new selection.