Larson Electronics SPLT IVT-12VDC-1000VA-120VAC Series Скачать руководство пользователя страница 4

SPLT-xx-IVT-12VDC-1000VA-120VAC

Larson Electronics, LLC

 

 Phone: (800) 369-6671 

Fax: (903) 498-3364 

www.larsonelectronics.com 

4

 of 

11

5.

Your air compressor is equipped with a permanently lubricated, maintenance-free motor.

 

 

Never try to 

lubricate the compressor.

6.

All repairs should be performed by Manufacturer or Manufacturer’s Authorized Service

 

Agencies only.

CAUTION: 

Never touch the air compressor or fittings connected to the air compressor, with bare hands during 

or immediately after use. The leader hose and fittings connected to leader hose will become very HOT during 

and after use. If necessary, wear heat resistant gloves to handle fittings, air line, and leader hose. 

Pneumatic mast: 

Masts come from the factory pre-lubricated and require no scheduled maintenance under normal operating 

conditions. In extremely harsh environmental conditions, maintenance of the mast might be required. Signs 

that cleaning and lubrication are needed can be: 

• A noticeable gritty film on the exterior surfaces of the mast sections
•  rratic extension or retraction of the mast
• Noisy operation of the mast
•  ticking of one or more mast sections when mast is extending or retracting

 

PROCEDURE:

1.

Remove top load from the mast. This will allow the sections of a non-locking mast to more

 

easily be 

extended from smallest to largest. See Step 3. On locking masts, the sequence of

 

extension can be 

controlled by the locking collars.

2.

When a regulator exists in the pneumatic system, reduce its pressure to between 5 and 10

 

PSIG.

NOTE: 10 PSIG should be sufficient pressure to extend all sections of the mast without a top load. If any 

section will not extend with 10 PSIG the mast may require overhaul. Consult the factory. 
3.

 

One person operating the air control valve should slowly pressurize the mast just enough to

 

extend the top 

mast section.
Another person may need to hold down the larger mast section collars to assure the proper sequence of 

extension. Close the air control valve as soon as the mast section is up. 

Содержание SPLT IVT-12VDC-1000VA-120VAC Series

Страница 1: ...S RATED VOLTAGE TO PREVENT WIRING DAMAGE OR ABRASION DO NOT EXPOSE WIRING TO EDGES OF SHEET METAL OR SHARP OBJECTS SUITABLE FOR DAMP LOCATIONS IMPORTANT READ CAREFULLY BEFORE INSTALLING THIS FIXTURE S...

Страница 2: ...equipped with positive and negative probes which allows the meter to get a DC voltage reading from the battery Multimeters give a DC voltage reading from your batteries Look up the battery s model num...

Страница 3: ...but wet use either a window wiper or a microfiber cloth on a handle to dry the panels Making sure there is not residue on your panels is an important part of solar panel maintenance and cleaning Resid...

Страница 4: ...hat cleaning and lubrication are needed can be A noticeable gritty film on the exterior surfaces of the mast sections rratic extension or retraction of the mast Noisy operation of the mast ticking of...

Страница 5: ...icant 8 Lower the mast completely Allow several minutes for the lubricant to settle and spread around the wear ring and seal at the bottom of each mast section 9 Extend the mast again one section at a...

Страница 6: ...intle having trailer GVW rating if needed Tires Check tire pressure when cold and inflate as needed Also check for damage Wheels lug nuts or bolts and hub Check for tightness and tighten For new or re...

Страница 7: ...ck Drop Leg if equipped Grease gears at the top Structure Frame Members Inspect all frame members bolts and rivets Repair or replace damaged worn or broken parts Structure Welds Inspect and repair all...

Страница 8: ...battery does not hold Voltage replace them with equivalent 200Ah batteries Mast do not extend Turn on the power switch Turn on the disconnect switch Move the pressure valve to up position Switch on th...

Страница 9: ...or runs continuously and air flow lower than normal 1 Excessive air usage 2 Loose connections 3 Worn piston ring or inlet valve 4 Clogged air filter element 1 Decrease air usage 2 Check all connection...

Страница 10: ...itch to reset 4 Replace pressure switch Thermal overload protector cuts out repeatedly 1 Lack of proper ventilation or ambient temperature is too high 2 Compressor valves failed 1 Move compressor to w...

Страница 11: ...place out of the reach of children when not in use Inspect for good working condition prior to storage and before re use REPLACEMENT PARTS The SPLT xx IVT 12VDC 1000VA 120VAC is designed to provide ye...

Отзывы: