7: Network, Serial Line, Tunnel, and Modbus Settings
IntelliBox-I/O 2100 User Guide
57
Line –
Configuration
Page Settings
Description
Stop Bits
Select the number of stop bits used by the currently selected
serial line. Choices are:
1
(default)
2
For
the Modbus protocols, the default is 1; this setting
automatically changes to 2 if parity is None.
Flow Control
Select the flow control method used by the currently selected
serial line. Choices are:
None
(default for Tunnel protocol)
Hardware
(commonly called CTS/RTS)
Software
(commonly called Xon/Xoff)
On Line 1, for the Modbus protocols,
Flow Control
defaults to
None; this setting cannot be changed.
On Line 2,
Flow Control
is unavailable for all protocols.
Xon char
Character to use to initiate a flow of data.
When
Flow Control
is set to
Software
, specify
Xon char
. Prefix
a decimal character with
\
or a hexadecimal character with
0x, or
provide a single printable character. The default Xon char is
0x11.
Xoff char
When
Flow Control
is set to
Software
, specify
Xoff char
. Prefix
a decimal character with
\
or a hexadecimal character with
0x, or
provide a single printable character. The default Xoff char is
0x13.
Содержание I/O 2100
Страница 1: ...Part Number 900 474 Revision B March 2012 IntelliBox I O 2100 User Guide ...
Страница 36: ...5 Getting Started IntelliBox I O 2100 User Guide 36 Figure 5 1 Lantronix DeviceInstaller ...
Страница 86: ...9 Services Settings IntelliBox I O 2100 User Guide 86 Figure 9 7 HTTP Configuration Page ...
Страница 95: ...10 Security Settings IntelliBox I O 2100 User Guide 95 Figure 10 1 SSH Server Host Keys Page ...
Страница 123: ...12 Advanced Settings IntelliBox I O 2100 User Guide 123 Figure 12 3 Email Configuration Page ...
Страница 182: ...E Isolated I O Specifications IntelliBox I O 2100 User Guide 182 Figure C6 Relay Contact position when energized ...