Index value
(OBIS code)
Item
Meter software
version
-
6.8.0
-
Reactive Energy Q2
-
7.8.0
-
Reactive Energy Q3
-
8.8.0
-
Reactive Energy Q4
-
9.8.0
-
Apparent Energy {+kVAh} (Q1+Q4)
-
10.8.0
-
Apparent Energy {-kVAh} (Q2+Q3)
-
15.8.0
-
Active Energy - Absolute Value [|+A|+|-A|]
{+kWh}
-
16.8.0
-
Active Energy - Absolute Value [|+A|-|-A|]
{+/-kWh}
-
130.8.0
-
Reactive Energy - Absolute Value [|+R|+|-
R|] {+kVArh}
-
131.8.0
-
Reactive Energy - Absolute Value [|+R|-|-
R|] {+/-kVArh}
-
132.8.0
-
Reactive Energy - Import [+R(Q1+Q4)]
{kVArh(+)}
-
133.8.0
-
Reactive Energy - Export [-R(Q2+Q3)]
{kVArh(-)}
-
36.7
-
Phase L1 kW
-
151.7
-
Phase L1 kVar
4 Energy efficiency items (see section
5.2.11)
-
[M52]
-
Module data 1 - 12 (value and OBIS code
will be sent by module)
-
End of list
5.2.10 Display Status Messages
Depending from configuration the following messages can appear on the
end of a display list:
Message
Meaning
-
FF 00000000
-
Error detected (if error value FF > 0)
-
rEd
-
Reverse energy detected
-
td
-
Terminal cover removal detected
-
mFd
-
Strong magnet field tamper detected
-
btd
-
Disconnector (breaker) tamper detected
-
VoltAGE Low
-
Voltage is lower than the configured threshold (standard value:
170 V)
Fig. 5.5 Sample: Message for magnet tamper detected