Operation
31/52
D000030875 en q
– E350 series 2, 1-phase ZCF100Ax/Cx – User Manual
© Gyr
Exiting the service mode depends on how you entered:
Long button press
– exit at the end of list.
Terminal cover removal
– exit when the cover replaced.
Power up
– exit after a time period.
The number of displays (max. 31), their sequence, whether they are con-
tained in the auto scrolling list or only in the recall list (all displays of the
auto scrolling list appear also in the first part of the recall list) and the dis-
play duration for the items (between 1 and 15 seconds) can be
parameterised. Up to 12 displays, under the control of the AMR module,
can be included in the main display.
The
auto scrolling list
of the main display is displayed
if the end of the service display or the recall list of the main display is
reached,
if the display button is not pressed for a period, configurable at
manufacturing, of between 5 and 60 minutes (default 30 minutes), or
after a long press of the display button (more than 5 seconds) in the
service display.
It shows the end-user the main consumption data, e.g. the status of rated
registers and total registers, current instantaneous demand etc. After the
last display in the auto scrolling list it starts again. If the number of displays
in the auto scrolling list is set to 1, auto scrolling is switched off and the first
display of the recall list is displayed continuously.
The
recall list
of the main display is accessed by a
short press
(less than
5 seconds) of the display button while the auto scrolling list is running.
A
short press
moves the display to the next item in the recall list.
Repeated short presses will scroll through to the end of the recall list, then
"End" is displayed after which auto scrolling is resumed.
A
long press
(more than 5 seconds) in the main display will access the
service display (if parameterised to do so). Exception: If the display button
is pressed for a long time while the consumption since last reset is
displayed, the register is reset instead.
The following table shows a simple meter main display. The value of the
total active energy import register is assumed to be 000123456 Wh and
that of the total reactive energy import register 000009876 Varh. The
registers are set to show 6 digits with 1 decimal place. The leading zeros
are not suppressed.
Displayed value
Total active energy import
-
Total reactive energy import
-
Display check (all segments on)
-
Empty display (all segments off)
Main display
Example