– E350 series 2, 1-phase ZCF100Ax/Cx – User Manual
Insufficiently tightened screws
Insufficiently tightened screws of the connections can lead to increased
power losses at the terminals and therefore to undesirable heating. A
contact resistance of 1 m
causes a power loss of 6.4 W at 80 A!
Insulate to correct length
Touching live parts is dangerous to life. Shorten the stripped part of the
connecting wire, if bare wire is visible above the terminal edge.
Do not withdraw connecting wires with closed terminals
Never withdraw connecting wires with the terminal closed, since this could
damage the terminal.
4.3
Checking the Connections
Before putting the meter into operation check (and correct, if necessary) the
following points to ensure a correct connection:
1.
Has the correct meter (identification number) been installed at the
measuring point of the relevant consumer?
2.
Is the calibration connection closed (sealable sliding piece inserted
and sealed)?
3.
Are the screws for the phase and neutral connection tightened well?
4.
Are all inputs and outputs connected correctly? The house connection
or consumer fuse wires must be present at the input (terminals 1, 4),
those of the meter to the consumer at the output (terminals 3, 6).
Mount the terminal cover after a successful check of the connections,
tighten its screws and seal it.
4.4
Commissioning and Functional Check
Do not touch live parts
The main fuses must be inserted to put the meter into operation and for the
functional check. Without terminal cover there is a danger of contact with
the terminals. Touching live parts is a danger to life.
The installed meter should be put into service and checked as follows:
1.
Insert the corresponding main fuse. The meter is on.
2.
Check whether the display appears correctly (no error message) and
with no load connected that the anti-creep indicators are constantly on.
3.
Connect a load and check whether the anti-creep indicator for active
energy disappears.
4.
Check whether the disconnector (if present) works according to the
functionality specified for your application.