Operating Instructions 

 

PipeCheck

plus

 

Hand-held measuring device for 
district heating pipe sensors with 
fault location at NiCr measurement

BA 075431.220/09.20

Содержание PipeCheck

Страница 1: ...Operating Instructions PipeCheckplus Hand held measuring device for district heating pipe sensors with fault location at NiCr measurement BA 075431 220 09 20...

Страница 2: ...Cu measurements 11 HDW measurements 12 Single measurement 13 Fault detection for NiCr measurements only 14 How to save measurement values 17 Read stored data 19 Device settings 20 GPS info 20 Clock i...

Страница 3: ...al Data Hand held measuring device PipeCheckplus Included are a measuring cable with banana plugs and alligator clips pipe connection magnet mains charger USB cable Li Ion rechargeable battery accesso...

Страница 4: ...ating pipe monitoring activities The PipeCheckplus is destined for the use in residential and small business areas Any non compliant use excludes the manufacturer from liability for any dam ages The o...

Страница 5: ...arging socket 12V DC 8 Charging status indicator 9 Reset button 1 Top of device Bottom of device 2 3 4 5 6 7 8 9 Scope of supply 10 Measuring device PipeCheckplus 11 Carrying bag with accessory com pa...

Страница 6: ...und half way The red and green measurement lines con nect to the sensor wires of the pipe to be 3 12 measured The two black measurement lines are connected to the medium pipe separately from each othe...

Страница 7: ...netic fields such as cardiac pacemakers etc hearing aids televisions and monitors bank and credit cards data carriers and computers How to connect the pipe connection monitor Using the banana plugs pl...

Страница 8: ...utomatically Key Explanation of symbols GPS satellite indicator flashes if there is no satellite connection e g inside buildings Is visible when there is a satellite connection Rechargeable battery ch...

Страница 9: ...ipe I_ab Measurement value for insulation resistance measuring wire a against b Ux aP Measurement value for voltage measuring wire a against the pipe Ux ab Measurement value for voltage measuring wire...

Страница 10: ...oltage Ux can be displayed by pressing and hold ing the Ux soft key The presence of an element voltage can be an indication of moisture in the insulation layer Press the Stop soft key to end the measu...

Страница 11: ...the element voltage Ux can be displayed by pressing and hold ing the Ux soft key The presence of an element voltage can be an indication of moisture in the insulation layer Press the Stop soft key to...

Страница 12: ...n of moisture in the insulation layer Press the Stop soft key to end the measurement and freeze the display Shown are the loop resistance the insulation resistance for measuring wire a against b the i...

Страница 13: ...pipe Pressing the Ux Rx soft key alternates between Ux voltage measurement und Rx resistance measurement Pressing the aR ab soft key alternates between aR measuring wire a against the pipe and ab meas...

Страница 14: ...r and then displays the measurement result For experienced measurement technicians the PipeCheckplus has an option to perform fault detection measurements in individual steps This allows for a detaile...

Страница 15: ...tinuous to perform the currently selected measure ment and then displays the measurement result Press the right soft key to switch to the next measurement for manual fault location For all measurement...

Страница 16: ...he bar chart below the measured value shows the deviation of the measured value from 0 V centre F b Distance fault end of the measuring wire in and m The bar chart below the measured value shows the f...

Страница 17: ...xt text should be modified Press the OK soft key to select the measured value underlaid with the dark background that is marked with a Edit measurement point Press the or soft key to increase or decre...

Страница 18: ...alues under the specified measuring point stops the measurement storage procedure and calls up the mea surement screen Find out more about how to evaluate data stored in the log file on page 21 If no...

Страница 19: ...that is marked with a The values stored in the measurement file are displayed Press the soft key to scroll down wards through the value list line by line Once the bottom line is reached the arrow chan...

Страница 20: ...longitude coordinates longitude with an indica tion of the position respective to the prime meridian Greenwich West or East GPS Q 1 Digit 0 No satellite reception 1 Satellite reception available 2 Di...

Страница 21: ...be changed by pressing the or soft keys The same applies for setting the other val ues in the order of Day Minute and Hour The changes are not stored on the device until the Save soft key is pressed...

Страница 22: ...So it is ready for use more quickly Sensor wire information Shows the resistance value for the sensor wire set on the device in m Pressing the or soft keys increases or decreases the resistance value...

Страница 23: ...op soft key makes the dis play return to the measurement screen No measurement values will be shown Broken measurement loops If a measurement loop is interrupted the display will show the Loop interru...

Страница 24: ...terface 5 The charging process is indicated by the lit 15 7 8 up red and green diodes on the charge indicator 8 next to the charging socket 7 If the device is switched on during charging the charge in...

Страница 25: ...rface 5 on the PipeCheck s underside 5 14 Connect the plug at the cable s other end to one of the PC s free USB ports The PipeCheckplus starts up automatically The data connection will be shown on the...

Страница 26: ...eckplus will automatically create a new file and begin naming data points from 1 onwards CU CSV Contains stored CU measurement data GPS CSV Contains stored GPS data HDWCSV Contains stored HDW measurem...

Страница 27: ...ion SD memory card data can be completely deleted or formatted How to edit info texts Info texts that relate to measurement points e g routes or location information can be stored in the INFOTEXT TXT...

Страница 28: ...Page 28 Evaluation of measurement results Measurement results are evaluated primarily on the basis of the determined MH level D D D D W D W D E W D E t W E D D D t D...

Страница 29: ...rom MH level 11 and an insulation resistance of 3 5 M onwards automatic localisation must commence to obtain initial insights about the fault location Significant amounts of moisture in the insulation...

Страница 30: ...ckplus to LANCIER Monitoring GmbH Gustav Stresemann Weg 11 48155 M nster Germany Helpline Tel 49 0 251 674 999 0 Disposal The PipeCheckplus is equipped with a Li Ion rechargeable battery When neccessa...

Страница 31: ...Page 31 EC Declarations of Conformity for power adaptor...

Страница 32: ...II For proper implementation of the health and safety requirements named in the EC directives the following standard s and or technical specification s have been consulted EN 61326 1 Electrical equipm...

Отзывы: