3
C. For High Volume Applications, connect to optional storage unit.
D. When used with the optional 38.5 Gallon Pure Storage unit, the Delivery Pump must be installed
below the tank level to ensure proper operation..
1.8
CONNECTING UNIT TO WATER SUPPLY
A. The water inlet connection for units without a water boost pump is on the top left hand side of
the unit. Connect to filtered water source using 3/8” OD tubing.
B. The water connection port, for units equipped with a water boost pump, is the inlet port on the
pump (see Figure 1). Connection can be accomplished using 3/8” OD tubing. As an
alternative, the Installation Kit contains an adaptor with a 3/8” barbed fitting. This allows the use
of 3/8” ID beverage tubing as the inlet water tube.
C.
Use cold water supply ONLY.
CAUTION
THE UNIT COVER MUST BE PROPERLY INSTALLED ON UNIT DURING OPERATION WITH ALL
FIVE (5) SCREWS IN PLACE. FAILURE TO PROPERLY SECURE COVER TO UNIT WILL
RESULT IN FAILURE OF THE UNIT TO SHUT OFF AND/OR BOOST PUMP WILL OPERATE
CONTINUOUSLY IN BY-PASS.
1.9
TURNING WATER ON
Turn water on to unit and check for leaks. Membrane will begin to produce water to fill storage bag.
The time required to fill the bag is dependent upon the Pure Link model.Water production can be
verified by observing flow rate to drain. If equipped with internal delivery pump, disconnect 3 pin
pump connector from power supply. Follow Sanitizing Instructions in Section 1.12. Allow unit to fill
with water, then reconnect delivery pump.
1.10 CONNECTING UNIT TO ELECTRIC POWER SUPPLY (IF EQUIPPED WITH POWER SUPPLY)
WARNING
THIS UNIT MUST BE PROPERLY ELECTRICALLY GROUNDED TO AVOID POSSIBLE FATAL
ELECTRICAL SHOCK OR SERIOUS INJURY TO THE OPERATOR. THE POWER CORD IS
PROVIDED WITH A THREE PRONG GROUNDED PLUG. IF A THREE HOLE GROUNDED
ELECTRICAL OUTLET IS NOT AVAILABLE, USE AN APPROVED METHOD TO GROUND THE
UNIT.
DO NOT USE EXTENSION CORDS WITH THIS UNIT. DO NOT “GANG” TOGETHER WITH
OTHER ELECTRICAL DEVICES ON THE SAME OUTLET.
Plug unit power cord into transformer control box and into the proper electrical outlet. The water
boost pump will begin to operate. Product water will begin to fill the product water storage bag. The
boost pump will shut off when the storage bag is full.
1.11 Boost Pump Bypass Pressure Setting (if so equipped)
A. Install pressure gauge (0-160 psi) on outlet side of boost pump (PN 86-0112). Connect feed
water line from Pure Link unit to other side of gauge.
B. Turn on water supply.
C. Connect unit to electrical supply.
D. With boost pump operating, insert 1/16" hex key into bypass adjustment screw on pump head.
Turn clockwise to increase bypass setting, or turn counterclockwise to decrease bypass setting.
Set to 110 psi.
E. Disconnect electrical supply.
F. Turn off water supply.
G. Remove gauge and reconnect feed water line from Pure Link to boost pump outlet.
H. Turn on water supply and connect unit to electrical supply. Check for pump operation and leaks.
NOTE:
Pressure Test Gauge is available through Lancer Customer Service.