41
7
Technical Data
7.2
Actuators 662R550...
Environmental Conditions
Operation:
Climatic conditions
Class 3K5 according to DIN EN 60721-3
Mechanic conditions
Class 3M5 according to DIN EN 60721-3
Temperature range
-20
...
+60
°C/-4 °F ... +140 °F
(condensation is prohibited)
Transport:
Climatic conditions
Class 2K3 according to DIN EN 60721-3
Mechanic conditions
Class 2M2 according to DIN EN 60721-3
Temperature range
-20 ... +70
°C/-4 °F ... +158 °F
(condensation is prohibited)
Storage:
Climatic conditions
Class 1K3 according to DIN EN 60721-3
Mechanic conditions
Class 1M2 according to DIN EN 60721-3
Temperature range
-20 ... +70
°C/-4 °F ... +158 °F
(condensation is prohibited)
Electronic safety:
Degree of protection (DIN EN 60529):
BT300 – IP00 housing
IP20 (terminals covered)
UI300 – IP40 (clamping)
IP54 (glued assembly)
Function
Power supply
24 VDC ±20 %
Floating time
5 s / 90° at 180 Hz
Direction of rotation 0° to 90°
right
Torque
0.8 Nm (both directions)
Holding torque
0.4 Nm (no power)
0.7 Nm
Permissible radial load
30 Nm (centre of output shaft)
Permissible axial load
5 N
Axial play of drive shaft
0.1 ... 0.2 mm
Cable length
securely connected 0.6 m
pluggable max. 3 m
Environmental conditions
Operation
Climatic condition
Class 3K3 according to DIN EN 60721-3
Mechanical condition
Class 3M3 according to DIN EN 60721-3
Temperature range
-20 ... +60 °C (condensation is prohibited)
Transport
Climatic condition
Class 2K3 according to DIN EN 60721-3
Mechanical condition
Class 2M2 according to DIN EN 60721-3
Temperature range
-20 ... +70 °C (condensation is prohibited)
Storage
Climatic condition
Class 1K3 according to DIN EN 60721-3
Mechanical condition
Class 1M2 according to DIN EN 60721-3
Temperature range
-20 ... +70 °C (condensation is prohibited)
Содержание BT300 BurnerTronic
Страница 2: ......
Страница 39: ...38 6 Leakage Test for Main Gas Valves Fig 6 2 Leakage test process diagram...
Страница 46: ...45 7 Technical Data...