31
5
Operating Control and Displays
NOTICE
The following firing rate points are available:
Ignition point
, 200, 250, 300, 400, 500, 600, 700, 800, 900, 999
Use BACK key
to switch to menu settings after having completed curve settings.
NOTICE
Pressing
while setting firing rate points discards the modifications.
Set Multi Stage Operation
NOTICE
Set the following stages according to this procedure!
NOTICE
Pressing die key
while modifying the firing-rate points discards the changes.
NOTICE
The following points are available for multi stage operation:
Ignition point
,
1 (first stage),
1
2 (valve switch-on threshold for stage 2),
2
1 (valve switch-off threshold for stage 2),
2 (second stage),
2
3 (valve switch-on threshold for stage 3)
3
2 (valve switch-off threshold for stage 3) ,
3 (third stage)
AIR
Air channel
Switching from 1. stage to 2. stage
S
Setpoint position of air
damper
The internal setpoint curve always has
200 digit in stage 1, 300 digit in stage 2 and 400
digit in stage 3.
I
Actual position of air damper