background image

F.  Check  the  smoke  pipe  and  make  certain  each 

joint is tight and the connections to the Vapor-

Fire Furnace and chimney are air tight.

G.  Check the ashes. Ash pan and fire compartment 

may be overloaded with ashes.

H.  Check type of wood being burned. If too green or 

wet wood is being used, it may cause excessive 

smoking.

I.  Check  your  chimney  for  down  drafts.  This  is 

caused  by  air  currents  being  deflected  down 

the chimney from higher objects, such as trees , 

buildings, and hills. This problem can usually be 

corrected with an open vented chimney cap.

J.  Make sure the chimney clean-out door is tightly 

closed.

K.  If other fuel-burning devises are connected to the 

chimney,  they  may  be  causing  draft  problems. 

This must be corrected by your heating contrac-

tor.

L.  Remove any mesh from your chimney cap.

YOU ARE NOT RECEIVING ENOUGH HEAT  
FROM YOUR FURNACE

A.   Make sure the pipe or duct from the Vapor-Fire 

Furnace, as well as the pipe connections, are air 

tight.

B.  The  cold  air  return  of  your  forced  air  upflow 

furnace is blocked. NEVER PLACE SOLID OB-

JECTS IN FRONT OF OR OVER THE COLD AIR 

RETURNS IN YOUR HOME.

C.  The cold air return of your forced air upflow fur-

nace is inadequate. It may be necessary to in-

crease its capacity.

D.  If you don’t seem to get enough air circulation – 

POSSIBLE CAUSES:

  1.  Air filter is dirty. Clean or replace air filter, as 

necessary.

  2.  Registers  and  grills  are  obstructed.  Check 

supply  pipe  or  damper  positions.  Check  regis-

ters and grills to make sure they are not closed 

or  obstructed  by  carpet,  draperies  or  furniture. 

Remove any obstructions.

E.  Contact your dealer or installer for further techni-

cal assistance.

SERVICE HINTS

A.  Thermostat  is  not  set  correctly.  Check  adjust-

ment.

B.  No electric power to furnace. Check fuse or cir-

cuit breaker. If fuse is blown, replace. If breaker is 

tripped, reset. Check to be sure shut off switch is 

“ON”.

C.  Clean  the  inside  of  heat  exchanger  through 

opening on the front face of main housing unit. 

Remove plate covering the opening and scrape 

the inside of exchanger clean. Remove any loose 

soot through the flue collar in rear of stove.

BOX 422 • TOWER, MN 55790 • USA • Tel (218) 753-2330 • www.lamppakuuma.com

21

IMPORTANT

NEVER OPERATE YOUR VAPOR-FIRE 
FURNACE WITH THE FIRE OR ASH DOOR 
OPEN.

Figure 32

SMOKE BAFFLE

MOUNTING CLIP

FIRE DOOR FRAME 

INSIDE

FIRE DOOR 

SMOKE BAFFLE

Содержание KUUMA 100

Страница 1: ...UTION Lamppa Manufacturing Inc READ ALL INSTRUCTIONS AND RULES FOR SAFE OPERATION CAREFULLY BEFORE STARTING THE INSTALLATION FOLLOW ALL STATE AND LOCAL CODES AND ORDINANCES BOX 422 TOWER MN 55790 USA...

Страница 2: ...Chamber Rear View 12 Mounting Controls 13 Wiring Schematic 14 Draft Measurement and Stove Pipe Connections 15 Normal Automatic Operations 16 Dos and Don ts of Operation 17 Basic Firing Instructions 18...

Страница 3: ...f of purchase Any repairs or replace ment of components shall have a prior agreement between the customer and the manufacturer before any such action is undertaken Dimensions 51 5 H x 27 W x 52 25 D F...

Страница 4: ...t control field con trol 6 RC BT as described and illustrated on page 7 and 9 also see figures 9 10 11 7 WE SUGGEST THAT A LICENSED ELEC TRICIAN BE HIRED TO DO ALL YOUR ELECTRICAL CONNECTIONS See wiri...

Страница 5: ...Association 60 Batterymarch Street Boston Massachusetts 02110 For equipment of this type National Fire Protection Agency NFPA Standard No 90B specifies the minimum standard clearances to combustible s...

Страница 6: ...RIC POWER FAILURE BOX 422 TOWER MN 55790 USA Tel 218 753 2330 www lamppakuuma com 6 HOT C O L D R E T U R N H O T H O T C O L D CHECK FLAP STOP STOP TWO SPEED SWITCHES 500 1500 CFM ON DEMAND CHECK FLA...

Страница 7: ...allation and Figure 6 of Masonry Chimney note roof clearance in ac cordance with NFPA 211 COMMON CHIMNEY PROBLEMS In order to have a proper operating Solid Fuel Heat System the chimney must be capable...

Страница 8: ...use an obstruction to draft as well as a place for debris to collect 7 Elbow Restrictions The flue pipe is connected to the chimney with too many elbows reducing the draft the chimney can provide Use...

Страница 9: ...approximate 45 degree adj elbows for angled connections NO HORIZONTAL PIPING INSTALLATION Barometric Draft Control field 6 RC BT provided with your model 100 Vapor Fire Furnace A draft reg ulator is...

Страница 10: ...ary to disassemble unit down to the main frame in order to move into older homes without damage to the Model 100 shell or electronics If this must be done please refer to the following assembly steps...

Страница 11: ...e side panel holes and secure with metal screws the holes are on each end of the channel Do the same with the top channel and secure tightly Now slide the blower assembly housing towards the back of t...

Страница 12: ...eel removable secondary air tubes are located on the right and left sides of the door frame inside the fire chamber They actually pro vide the fourth level of combustion air to complete the burn proce...

Страница 13: ...wiring to fans in fan enclosure as shown in Figure 23 K Run incoming conduit to transformer junction box and connect to a separate circuit breaker panel Use a 15 amp AWG copper wire to the fur nace Gr...

Страница 14: ...IDE COVER JUNCTION BOX 4 X 4 X 2 4 X 4 X 2 BOX INDICATES WIRE NUT DOTTED WIRING BY OTHERS BLUE TO RED FOR LOW SPEED RED TO BLACK FOR HIGH SPEED 2 X 4 X 2 BLACK YELLOW BLUE RED WHITE WT OUTSIDE COVER W...

Страница 15: ...and adjustable elbows 2 Angle your stove pipes upward towards the chimney smoke exit hole 3 Install barometric damper provided Set to 03 to 06 WC 4 Avoid using 90 degree pipe bends unless it s one 90...

Страница 16: ...ucts and registers The display screen is furnished on the electric control to provide the following A The letters O and P will blink on and off and the beeper beeps intermittently when there is an ope...

Страница 17: ...Unit Rake hot coals to the FRONT as shown DO NOT BLOCK PRIMARY AIR OPENINGS Keep coals approximately 1 from front air inlets HOT COALS ASHES HOT COALS ASH PAN RAKE A I R P R I M A R Y Figure 30 Perio...

Страница 18: ...en finished STARTING A COLD FURNACE NO HOT COALS A Open fire door B Scrape entire fire chamber ashes through open grate into ash pan using side paddle on ash scraper provided C Preheat fire chamber wi...

Страница 19: ...g the combustion process It consists of a number of elements which condense and bake layer upon layer in the chimney flue Highly combustible in its solid and semi liquid state creosote is present in t...

Страница 20: ...Yellow Birch 3000 26 000 000 185 Red Oak 3250 27 000 000 195 White Oak 3750 27 700 000 200 Hard Maple 3000 29 000 000 200 Hickory 3500 30 500 000 215 USEFUL FACTS No 2 Fuel Oil 140 000 BTU gallon Nat...

Страница 21: ...R OVER THE COLD AIR RETURNS IN YOUR HOME C The cold air return of your forced air upflow fur nace is inadequate It may be necessary to in crease its capacity D If you don t seem to get enough air circ...

Страница 22: ...control B Soot and creosote buildup in heat exchanger or chimney Clean if necessary C Chimney too low Increase chimney height D Obstruction in chimney Check for obstruction such as loose mortar bird n...

Страница 23: ...t we call the pilot burn and will continue like this until the fire chamber cools down and then the control again takes over and will adjust the shutter opening based on the fire chamber tem perature...

Страница 24: ...ws or a short chimney do not in stall the heat exchanger baffles you could get a draft reversal Smoke backing up or the smell of smoke would indicate a poor draft If questionable have your draft check...

Страница 25: ...prohibit the use of fire starters made from paper cardboard sawdust wax and similar substances for the purpose of starting a fire in an affected wood heater Be absolutely sure to install both UL appr...

Страница 26: ...by Intertek a certified lab each burn level was less than 15 pounds of emissions per million Btu s with an overall average of 0 093 This not only satisfies the EPA requirement from 2015 2020 of 93 po...

Страница 27: ...d operate the furnace according to the owner s manual 3 Use seasoned firewood approximately one year dried under cover 15 30 3 Install both carbon monoxide CO and smoke detector alarms 3 Always rememb...

Отзывы: