2
CALIBRATION OF MINIMUM GAS PRESSURE SWITCH
The minimum gas pressure switch serves to prevent the burner from being started up, or to shut it down if it
is operating, when the gas pressure falls below the minimum required level. This setting should be 0% lower
than the gas pressure obtained with the burner operating at max. flow rate.
CALIBRATION OF MAXIMUM GAS PRESSURE SWITCH (ON REQUEST)
The maximum gas pressure switch serves to put the burner in blocking mode if the gas pressure exceeds the
pre-set value. Set the combustion head pressure to 15% (for Natural Gas) and 10% (for B/P) more than the
nominal capacity required at the time of installation.
PRESSURE SWITCH Model: GW 50 - LGW 10 A2P
Pressure tap
Take off the cover and turn dial (A).
Model
Air pressure
switch - model
Setting range
millibar
Gas pressure
switch - model
Setting range
millibar
310 PM/2-E
30 PM/2-E
1 - 10
1 - 10
2,5 - 50
2,5 - 50
DUNGS
LGW 10 A2P
DUNGS
LGW 10 A2P
DUNGS
GW 50
DUNGS
GW 50
Содержание 310 PM/2-E
Страница 2: ......
Страница 16: ...16 CICLO DI FUNZIONAMENTO 310 430 PM 2 E ...
Страница 38: ...38 OPERATING CYCLE 310 430 PM 2 E ...
Страница 60: ...60 CYCLE DE FONCTIONNEMENT 310 430 PM 2 E ...
Страница 82: ...82 PROGRAMMABLAUF 310 430 PM 2 E ...
Страница 104: ...104 CICLO DE FUNCIONAMIENTO 310 430 PM 2 E ...
Страница 113: ...113 ...
Страница 114: ...114 ...
Страница 115: ......