83-507-013 Rev. A
22
Fig.3-7: Load wires connection to the output connector
Load wires
Negative (-)
Output/Return
Positive Output (+)
+V
-V
Fig.3-8: Shield assembly
A
A
+V
-V
Fig.3-9: Protective shield and wires assembly
Load
wires
-V
The 80V to 600V models have a four terminal wire clamp output connector. The two left terminals are the
positive outputs and the two right terminals are the negative outputs. The connector requirements are as
follows:
1. Wires: AWG18 to AWG10.
2. Tightening torque: 6.5-7.0 Lb-inch.
Follow the instructions below for connection of the load wires to the power supply:
1. Strip approx. 10mm (0.39 inches) at the end of each of the wires.
2. Loosen the connector terminal screws.
3. Insert the stripped wires into the terminal and tighten the terminal screw securely (see Fig.3-7)
4. Loosen the two chassis screws marked “A” halfway as shown in Fig.3-8.
5. Assemble the protective shield to the chassis and tighten the two screws to fix the shield to the
chassis (see Fig.3-8). Screws tightening torque: 4.8-5.3 Lb-inch.
6. Tighten the wires to one of the shield sides using typ-wrap or equivalent. Refer to Fig.3-9. Ensure
that the wire length inside the shield is long enough to provide proper strain relief.
3.9.7 Connecting single
loads, local
Содержание Genesys GENH 750W
Страница 2: ...83 000 015 Rev C...
Страница 16: ...83 507 013 Rev A 9 CHAPTER 2 SPECIFICATIONS...
Страница 17: ...83 507 013 Rev A 10...
Страница 19: ...83 507 013 Rev A 12 2 13 GENESYSTM 750W 1500W POWER SUPPLIES OUTLINE DRAWINGS...