5
2.1.1 Wall-Mounting the A75D(E) (4B75 & 475 Only)
The
4B75 & 475
cases of the A75D(E) are shipped from the factory with the necessary brackets installed for
wall-mounting
(The same bracket is used for rear mounting on a 19” relay rack and cannot be removed).
The
975 & 72
cases do not come with wall mounting equipment, it is not recommended to attempt to mount these
cases on any wall.
Wall-Mount Procedure
To wall-mount the A75D(E), install four 0.25 in (6.4 mm) bolts on the wall rated to support the charger weight
plus a safety factor of at least two times (for the
475
case 6 bolts are needed). Place the A75D(E) on the bolts,
add appropriate mounting hardware and tighten. Refer to the figures below for mounting dimensions and
specifications.
NOTE: All above dimensions are in inches. For further A75D(E) cabinet information, see the outline drawings for
the
4B75
(D4B-75)
and
475
(D4-75)
online at
http://www.lamarchemfg.com/info/enclosure-drawings.html
Figure 1 - Keyhole Slot Used
Figure 3 - 475 Case Bolt Pattern