Voltech BC-2415P Скачать руководство пользователя страница 1

BC-2415P/ 2420P/ 2430P 

Multi-Stage Battery Chargers 

User Manual 

 

 

Keep this manual in a safe place for quick reference at all times. 

 

This manual contains important safety and operation instructions for correct use of the battery charger. Read through the manual 

And pay special attention to the markings and labels of the charger, battery and any equipment connected into the system. 

 

Pay special attention to these two types of notices used in this manual; 

 

WARNING: 

Failure to heed this warning may cause injury to persons and damage to Equipment. 

 

CAUTION: 

Failure to observe this warning may result in damage to equipment and improper functioning of the Charger. 

 

WARNING: 

 

 

The charger is designed for in-door use. Protect the charger from ingress of water. 

 

This charger is made to charge only properly sized lead acid batteries. 

 

Don't recharging non-rechargeable batteries. 

 

Charging other types of battery or under-sized lead acid batteries may cause fire or explosion. 

 

Install the charger in accordance with all local codes 

 

Do not use the charger if it has been dropped or damaged. 

 

Do not remove casing of the charger, there is no user serviceable parts inside.   

 

Never attempt to charge a frozen battery   

 

Never attempt to charge a damaged battery. 

 

Wear protective goggles and turn your face away when connecting or disconnecting the battery. 

 

Never place the charger on top of a battery. 

 

Never smoke, use an open flame, or create sparks near battery or charger during normal charging operation as Batteries may 

 

give out explosive gas. 

 

Do not charge batteries in a sealed enclosure (boxed- in) due to possible explosion of entrapped explosive gas. 

 

Use of accessories not recommended may cause risk of fire, electric shock or equipment damage. 

 

Disconnect the mains supply before connecting or disconnecting the links to the battery. 

 

If the charger does not work properly or if it has been damaged, unplug its AC and DC connection. 

  Do not use this charger in connection with any medical device or life support system. 

  This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or   

 

lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a 

 

person responsible for their safety. 

  Children should be supervised to ensure that they do not play with the appliance. 

  Battery chargers for charging automobile batteries shall not be fitted with natural rubber-sheathed supply cords.

 

 

CAUTIONS: 

 

 

Refer to battery manufacturer’s specific recommended values for battery type settings and float voltage setting. 

 

Ensure all ventilation ports are not obstructed for efficient fan cooling, keep loose soft material such as paper, cloth, etc. away 

 

from the Charger 

 

During charging, the battery must be placed in a well ventilated area. 

 

If longer output charging cable are required, make sure the cable diameter is adequate for the Current & Cable length. 

 

AC source from portable generator:

   

 

The VA rating of a standard generator should be at least 4 times the maximum rating of the charger. 

    How-ever, Inverter type generators need to have only 2 to 3 times the maximum rating of the charger. 

  It is recommended that the ac output is stabilized by running the generator for 2-3 minutes before switching on the charger. 

  This charger is for standalone application only, parallel or series connection with another charger may cause damage to charger             

and connected battery. 

  AC supply cord (leads) should be at least minimum size of 3G 0.75mm

nominal cross-sectional area.

 

Содержание BC-2415P

Страница 1: ...cause risk of fire electric shock or equipment damage Disconnect the mains supply before connecting or disconnecting the links to the battery If the charger does not work properly or if it has been damaged unplug its AC and DC connection Do not use this charger in connection with any medical device or life support system This appliance is not intended for use by persons including children with red...

Страница 2: ...el AGM LiFePO4 Calcium Calcium and now also Lead Crystal batteries There are also two User programmable charging profiles for the professional users via the USB port by personal computer In addition the programmed maintenance charge provides a timely Equalization charge for the Wet lead acid battery Almost all the protections are controlled by the Micro Processor On start up the charger runs a ser...

Страница 3: ...minal s 10 Ventilation Fan 11 Inlet AC socket with Mains fuse holder 12 Temperature Sensor Socket Connection to Battery Temperature sensor accessory Sensor to increase decrease charging voltage at low high battery temperature B Using the charger 1 Check the supplied accessories AC cord Remote Battery temperature sensor CD software USB cable are with the package 2 Remove the magnetic dummy remote c...

Страница 4: ...he operation of connected powered appliance or connections E Battery Charger Installation and Connection Observe the warnings safety precautions before rushing to install and operate the charger Check battery condition fill up cells for wet battery clean battery poles Secure the battery charger in a well ventilated place make sure the mounting surface is flat and without soft covering material or ...

Страница 5: ...orption stage Charging current will now decrease gradually until a pre set value at which the charger then automatically switches to Float Stage The max Absorption time is also controlled by the time in Bulk charge and battery type selected Stage 3 THE UO PHASE FLOAT mode Constant voltage charging Float LED is ON In Float stage the battery is full and only takes in the amount of current necessary ...

Страница 6: ...to equalization by charger itself Once Auto is selected the charger will start Equalization automatically if charger stays in Float mode for over 21 days After entering into this mode the Absorption indicator Amber LED will flash the Equalization will run for 240 minutes The charger will then go back to Float once completed Remark 1 This mode only can be operated at WET Flooded selection Battery S...

Страница 7: ...mote temp sensor at 60 C Flashing Solid ON OFF Manual power on off reset after fault cleared Alarm flash Buzzer on Bat Over Temp Fan not working or stuck Flashing Flashing OFF Manual power on off reset after fault cleared Alarm flash Buzzer on Fan Fault Output Over Voltage Protection when output voltage is 4 higher than it should be for the battery type and charge stage Solid ON OFF OFF Manual pow...

Страница 8: ...oad and charger not balanced Battery does not get full charge All indicator LED work normally and sequentially OTP LED flashing Bad battery connection Battery type select switch in wrong setting Battery capacity too large Ambient temperature too low Battery has damaged cell or battery is too old Wrong set the lower power level Check for loose contact right cable size cable integrity Recheck batter...

Страница 9: ...ad 230V 2 5A 3 5A 5 0A Protection Overload 90 110 Rated Output Current or 50 Rated Output Current Soft Charge Protection Type Constant Current Limiting recovers Automatically after Fault Condition is Removed Short Circuit Recovers Automatically if Fault Condition is Removed within 20 seconds Otherwise the charger will shut down until re start the charger again Reverse Polarity Automotive type Blad...

Страница 10: ...r level set type of fault with alarm etc and can remote control the output terminal On OFF trigger the Equalization charging for wet battery and force charger to float mode It can be mounted on BC charger by replacing the dummy cover on the front panel or remotely mounted with 10m extension cable going through the unplugged hole at the front of the dummy panel II Connection 1 10 Meters Phone Cable...

Страница 11: ...r output ON and OFF Green LED is illuminated when output is ON 2 Alarm Can be silenced or audible by toggling this button default is audible Red LED will illuminate when fault occurred 3 Func To toggle charger setting Menu and select scrolling to make display continue to scroll all setting See optional remote programming section 4 Set To confirm the chosen feature you selected ...

Страница 12: ...e Version Displays the current control software version Remote Short cut 1 Press and hold the SET button for 5 seconds and release the button to enter Equalization mode Equalization selection slide switch on main unit should be selected at manual position 2 Press and hold the Func button for 5 seconds and release the button to force the charger to Float mode V Fault Indication 1 Charger High Temp ...

Отзывы: