Field legend
SI
Service alarm interval command.
<interval>
Service alarm interval in months.
Accepted values: 0, 1, 3, 6 and 12.
0 means that the function is off.
Example
To set the device to provide service interval alarm every six months, follow the steps below.
Send the following text message to the idOil unit:
SI 6
The unit's reply message format is as follows:
SI <device name> 6
4.4.
Settings for battery-operated devices
4.4.1. Measurement interval (MI)
An interval can be set for the device, according to which it will wake up from power saving
mode, perform sensor measurements and, if necessary, activate the 3G modem to forward
the alarm data. After this, the device returns to power saving mode.
The factory default for the measurement intervals is 10 (minutes).
This setting can also be entered via the idOil unit’s browser user interface.
The format of the measurement interval setting command is as follows:
MI <nnn>
Field legend
MI
Command
<nnnn>
Measurement interval in minutes. Permitted
values:
10, 30, 60, 120, 180, 240, 360, 480, 600,
720, 1440
Example:
If Pirkkala Myllyhaantie has been set as the device name and the command
MI 60
is sent, the response is:
MI Pirkkala Myllyhaantie 60
With this setting, the device wakes up to perform sensor measurements every 60 minutes
and sends alarm data to the set telephone numbers, if necessary.
Installation and Operating Instructions | idOil-30 3G, idOil-30 Battery 3G
11/19
DOC001696-EN-1