38
F14
1
Function enabled
if F12 = ON
OFF
Tests on opening safety sensor E.O. disabled; for sensors which are not pre-arranged for
monitoring
S
ON
Test on opening safety sensors E.O. enabled; for sensors pre-arranged for monitoring by the
automation (cat.2/pl.c).
For details, refer to the paragraph "Safety sensors".
F15
1
Function active if
F13 or
F14 = ON
OFF
Safety sensors test with LOW logic level.
For details, refer to the paragraph "Safety sensors".
S
ON
Safety sensors test with HIGH logic level.
For details, refer to the paragraph "Safety sensors".
F16
OFF*
If the work program “Night Lock” is selected, the door remains closed and can only be
opened by actuating the OPEN-START inputs, or the Spyco radio control with the radio EN-
RF1 radio receiver.
ON
Selecting the work program “Night Lock”, the door opens and remains open 10” before
reclosing to allow leaving the building.
F17
OFF*
Disabled function OFF
ON
Disabled function ON Refer to the paragraph “Courtesy operation for disabled” for details on
the operating mode.
F18
OFF*
Operation with automatic closing
ON
Step-by-step function: an OPEN command opens the door; a second command is required
to close back the door.
F19
Function enabled
if F18 = ON
OFF*
In the step-by-step function, the door, when open, can be closed only with a closing
command given by the OPEN-START input or by the Spyco radio control with the EN-RF1
radio receiver.
ON
In the step-by-step function, the door, when open, automatically closes if the closing
command is not given within 30 seconds.
F20
OFF*
Standard operation on the internal and external radar inputs.
ON
Operation with separate opening and closing commands. The external radar input controls
the opening, the internal radar input controls the closing, without automatic closing. The
OPEN and START inputs operate in standard mode.
F21
1
OFF
OPEN input configuration: normally closed contact.
When a device with N.C. contact is installed.
ON
OPEN input configuration: normally open contact.
When not in use or if a device with N.O. contact is installed.
F22
OFF*
The OPEN input is disabled in the work program “Manual free door”.
ON
The OPEN input is enabled also in the work program “Manual free door”, to allow the
automatic opening of the door.
F23
OFF*
Pause time with open door before constant automatic closing.
ON
Automatic increase of the pause time with door open if the door cannot close due to the high
flow of people.
F24
OFF*
The pause time set by the potentiometer P4 is never reset.
ON
The pause time set by the potentiometer P4 is reset to the initial value if, with the door open,
an opening command is given.
F25
For NB-
SMT/SMTB
automations only
OFF*
In case of power failure, when mains supply is restored, the door remains in the current
position.
ON
In case of power failure, when mains supply is restored, the door slowly goes to closed
position.
F26
OFF*
Interlock function disabled.
ON
Function of interlock between two doors enabled. A door may be opened only if the other one
is closed. Please refer to the paragraph "Interlock system".
F27
Function enabled
if F26 = ON
OFF*
In interlock function, door opening is delayed by 0.5” after the opening command. Please
refer to the paragraph "Interlock system".
ON
In interlock function, door opening is immediate after the opening command. Please refer to
the paragraph "Interlock system".