28
16) COMMISSIONING OF THE AUTOMATION (INITIAL SETUP)
After completing the mechanical installation and performing the electrical connections, manually move the leaf along its entire stroke,
checking that the movement is frictionless.
SET-UP operation is compulsory to allow the automation electronic control unit getting run limit positions.
When the setup begins, the door must be closed and during the run learning cycle, no obstacle must be in the leaf motion area.
The Neptis Plus automation is equipped with a function allowing it to learn the position of the side wall during the initial set-up.
This function is useful as it allows to store the wall position at the end of the opening run, and as a consequence to precisely set the point
where the tripping of the opening safety sensor causes leaf slowdown in the last few degrees of the opening stage.
It is important that you adjust the safety sensor detection range before starting the automation setup cycle.
If the Neptis Plus automation controls a single leaf automatic door, switches 1 and 2 on the dip-switch SW1 of the LCB logic card must
be set to OFF.
If two Neptis Plus automations must control a dual leaf automatic door, refer to the paragraph "Dual leaf door".
Follow chapter 16.1 only if the digital selector ET-DSEL is new and is powered on for the first time.
Follow chapter 16.2 if the digital selector has already been used before.
16.1) FIRST START OF THE DIGITAL SELECTOR ET-DSEL
Power the automation Neptis Plus with mains voltage, the control unit buzzer emits a few
quick, short beeps.
•
Language selection is shown on the display of the digital selector ET-DSEL;
•
use the buttons
F2
and
to move the arrow in correspondence with the language desired.
•
Press the EXIT
button to exit the “Language” section and enter the “Serial
communication settings” section, as described under para. 15.3.
16.2) SERIAL COMMUNICATION SETTINGS
Provide mains voltage to the automation Neptis Plus;
The control unit buzzer emits a few quick, short beeps.
The selector ET-DSEL automatically detects the presence of the automation electronic control unit (fig. A) and stores the LCB board
serial code (fig. B).
When the acquisition of the serial code is completed, the display must show the closed padlock symbol on letter M and the open padlock
symbol
?
if it is a single Neptis Plus automation (fig. C).
If it is a dual leaf swing door, refer to the paragraph “Dual leaf swing door”.
Press the EXIT button
to exit the “Serial communication setups” section and enter the general programming menu.
Fig.A
Fig.B
Fig.C