Page 73
N
EO
T
HERM
Boilers and Water Heaters
229
Invalid
Modulation
output setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
230
Invalid CH
(Central Heat)
demand source
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
231
Invalid Delta
T limit delay
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
232
Invalid Pressure
sensor type
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
234
Invalid Outlet
high limit enable
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
235
Invalid Outlet
connector type
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
236
Invalid Inlet
connector type
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
237
Invalid DHW
(Domestic
Hot Water)
connector type
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
238
Invalid Stack
connector type
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
239
Invalid Header
connector type
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
240
Invalid Outdoor
connector type
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
Содержание NTV
Страница 4: ...LAARS Heating Systems...
Страница 11: ...Page 7 NEOTHERM Boilers and Water Heaters...
Страница 24: ...Page 20 LAARS Heating Systems Figure 16 Hydronic Piping Single Boiler Zoning with Circulators...
Страница 26: ...Page 22 LAARS Heating Systems Figure 18 Hydronic Piping Multiple Boilers Zoning with Circulators...
Страница 84: ...Page 80 LAARS Heating Systems Parts Illustration 1 Jacket Components...
Страница 86: ...Page 82 LAARS Heating Systems Parts Illustration 4 Internal Components Sizes 750 850...
Страница 88: ...Page 84 LAARS Heating Systems Parts Illustration 6 Gas Train Components Sizes 600 850...
Страница 89: ...Page 85 NEOTHERM Boilers and Water Heaters Parts Illustration 7 Heat Exchanger Components 68A Sizes 285...
Страница 90: ...Page 86 LAARS Heating Systems Parts Illustration 8 Electrical Components Front Battery CR2032 Touchscreen Back...
Страница 91: ...Page 87 NEOTHERM Boilers and Water Heaters Notes...