Page 71
N
EO
T
HERM
Boilers and Water Heaters
203
Invalid MFEP
(Main Flame
Establishing
Period) fl ame
failure response
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
204
Invalid NTC
sensor type
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
205
Invalid Outlet
high limit
response setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
207
Invalid PII
(Pre-Ignition
Interlock) enable
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
210
Invalid
Postpurge time
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
211
Invalid Power
up with lockout
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
212
Invalid
Preignition time
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
213
Invalid Prepurge
rate setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
214
Invalid Prepurge
time setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
215
Invalid Purge
rate proving
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
216
Invalid Run
fl ame failure
response setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
Содержание NTV
Страница 4: ...LAARS Heating Systems...
Страница 11: ...Page 7 NEOTHERM Boilers and Water Heaters...
Страница 24: ...Page 20 LAARS Heating Systems Figure 16 Hydronic Piping Single Boiler Zoning with Circulators...
Страница 26: ...Page 22 LAARS Heating Systems Figure 18 Hydronic Piping Multiple Boilers Zoning with Circulators...
Страница 84: ...Page 80 LAARS Heating Systems Parts Illustration 1 Jacket Components...
Страница 86: ...Page 82 LAARS Heating Systems Parts Illustration 4 Internal Components Sizes 750 850...
Страница 88: ...Page 84 LAARS Heating Systems Parts Illustration 6 Gas Train Components Sizes 600 850...
Страница 89: ...Page 85 NEOTHERM Boilers and Water Heaters Parts Illustration 7 Heat Exchanger Components 68A Sizes 285...
Страница 90: ...Page 86 LAARS Heating Systems Parts Illustration 8 Electrical Components Front Battery CR2032 Touchscreen Back...
Страница 91: ...Page 87 NEOTHERM Boilers and Water Heaters Notes...