Page 66
LAARS Heating Systems
94
Header sensor
fault
H
1. Check wiring and correct any possible errors.
2. Replace the header sensor.
3. If previous steps are correct and fault persists, replace the module.
95
Stack sensor
fault
H
1. Check wiring and correct any possible errors.
2. Replace the stack sensor.
3. If previous steps are correct and fault persists, replace the module.
96
Outdoor sensor
fault
H
1. Check wiring and correct any possible errors.
2. Replace the outdoor sensor.
3. If previous steps are correct and fault persists, replace the module.
97
Internal Fault:
A2D mismatch.
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
98
Internal Fault:
Exceeded
VSNSR voltage
tolerance
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
99
Internal Fault:
Exceeded
28V voltage
tolerance
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
100
Pressure Sensor
Fault
H
1. Verify the Pressure Sensor is a 4-20 ma source.
2. Check wiring and correct any possible errors.
3. Test Pressure Sensor for correct operation.
4. Replace the Pressure sensor.
5. If previous steps are correct and fault persists, replace the module.
105
Flame detected
out of sequence
H or L
1. Check that fl ame is not present in the combustion chamber. Correct
any errors.
2. Make sure that the fl ame detector is wired to the correct terminal.
3. Make sure the F & G wires are protected from stray noise pickup.
4. Reset and sequence the module, if code reappears, replace the fl ame detector.
5. Reset and sequence the module, if code reappears, replace the module.
106
Flame lost in
MFEP
L
1. Check main valve wiring and operation - correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, fl ame detector, fl ame detector
siting or fl ame rod position.
5. If steps 1 through 4 are correct and the fault persists, replace the module.
107
Flame lost early
in run
L
1. Check main valve wiring and operation - correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, fl ame detector, fl ame detector
siting or fl ame rod position.
5. If steps 1 through 4 are correct and the fault persists, replace the module.
108
Flame lost in run
L
1. Check main valve wiring and operation - correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, fl ame detector, fl ame detector
siting or fl ame rod position.
5. If steps 1 through 4 are correct and the fault persists, replace the module.
Содержание NTV
Страница 4: ...LAARS Heating Systems...
Страница 11: ...Page 7 NEOTHERM Boilers and Water Heaters...
Страница 24: ...Page 20 LAARS Heating Systems Figure 16 Hydronic Piping Single Boiler Zoning with Circulators...
Страница 26: ...Page 22 LAARS Heating Systems Figure 18 Hydronic Piping Multiple Boilers Zoning with Circulators...
Страница 84: ...Page 80 LAARS Heating Systems Parts Illustration 1 Jacket Components...
Страница 86: ...Page 82 LAARS Heating Systems Parts Illustration 4 Internal Components Sizes 750 850...
Страница 88: ...Page 84 LAARS Heating Systems Parts Illustration 6 Gas Train Components Sizes 600 850...
Страница 89: ...Page 85 NEOTHERM Boilers and Water Heaters Parts Illustration 7 Heat Exchanger Components 68A Sizes 285...
Страница 90: ...Page 86 LAARS Heating Systems Parts Illustration 8 Electrical Components Front Battery CR2032 Touchscreen Back...
Страница 91: ...Page 87 NEOTHERM Boilers and Water Heaters Notes...