Page 68
LAARS Heating Systems
149
Flame detected
H or L
Holds if fl ame detected during Safe Start check up to Flame Establishing
period.
150
Flame not
detected
H
Sequence returns to standby and restarts sequence at the beginning of
Purge after the HF switch opens if fl ame detected during Safe Start check
up to Flame Establishing period.
154
Purge Fan
switch On
H or L 1. Purge fan switch is on when it should be off.
2. Check wiring and correct any errors.
3. Inspect the Purge Fan switch J6 terminal 3 and its connections. Make
sure the switch is working correctly and is not jumpered or welded.
4. Reset and sequence the relay module.
5. If the fault persists, replace the relay module.
155
Purge fan switch
OFF
H or L 1. Purge fan switch is off when it should be on.
2. Check wiring and correct any errors.
3. Inspect the Purge Fan switch J6 terminal 3 and its connections. Make
sure the switch is working correctly and is not jumpered or welded.
4. Reset and sequence the relay module.
5. If the fault persists, replace the relay module.
156
Combustion
pressure and
fl ame ON
H or L
1. Check that fl ame is not present in the combustion chamber. Correct
any errors.
2. Make sure that the fl ame detector is wired to the correct terminal.
3. Make sure the F & G wires are protected from stray noise pickup.
4. Reset and sequence the module, if code reappears, replace the fl ame detector.
5. Reset and sequence the module, if code reappears, replace the module.
157
Combustion
pressure and
fl ame OFF
L
1. Check that fl ame is not present in the combustion chamber. Correct
any errors.
2. Make sure that the fl ame detector is wired to the correct terminal.
3. Make sure the F & G wires are protected from stray noise pickup.
4. Reset and sequence the module, if code reappears, replace the fl ame detector.
5. Reset and sequence the module, if code reappears, replace the module.
158
Main valve ON
L
1. Check Main Valve terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persists, replace the module.
159
Main valve OFF
L
1. Check Main Valve terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persists, replace the module.
160
Ignition ON
L
1. Check Ignition terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persists, replace the module.
161
Ignition OFF
L
1. Check Ignition terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persists, replace the module.
164
Block intake ON
L
1. Check wiring and correct any errors.
2. Inspect the Block Intake Switch to make sure it is working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the voltage across the switch.
Supply voltage should be present. If not, the Block Intake Switch is
defective and needs replacing.
5. If the fault persists, replace the relay module.
Содержание NTV
Страница 4: ...LAARS Heating Systems...
Страница 11: ...Page 7 NEOTHERM Boilers and Water Heaters...
Страница 24: ...Page 20 LAARS Heating Systems Figure 16 Hydronic Piping Single Boiler Zoning with Circulators...
Страница 26: ...Page 22 LAARS Heating Systems Figure 18 Hydronic Piping Multiple Boilers Zoning with Circulators...
Страница 84: ...Page 80 LAARS Heating Systems Parts Illustration 1 Jacket Components...
Страница 86: ...Page 82 LAARS Heating Systems Parts Illustration 4 Internal Components Sizes 750 850...
Страница 88: ...Page 84 LAARS Heating Systems Parts Illustration 6 Gas Train Components Sizes 600 850...
Страница 89: ...Page 85 NEOTHERM Boilers and Water Heaters Parts Illustration 7 Heat Exchanger Components 68A Sizes 285...
Страница 90: ...Page 86 LAARS Heating Systems Parts Illustration 8 Electrical Components Front Battery CR2032 Touchscreen Back...
Страница 91: ...Page 87 NEOTHERM Boilers and Water Heaters Notes...