Laars NEOTHERM NTH Series Скачать руководство пользователя страница 63

Page 63

N

EO

T

HERM 

 Residential Boilers

®

 

 

SIZE 

 SIZE SIZE SIZE 

ITEM  DESCRIPTION 

 

80 105 150 210 

  

 

 

 
30  PVC Reducer 

— 

— 

RP2053000  RP2053000 

30a  CPVC Reducer  

RD2010501  RD2010501  RP2065600  RP2065600 

 

or Coupling

30b  2” Dia. Pipe, CPVC 

RD2010212  RD2010212  RD2010213  RD2010213 

31 Hose 

Barbed 

Adapter RP2067100 RP2067100 RP2056100 RP2056100 

33  Air Inlet/Exhaust Bracket  R8D3005 

10D3005 

R20D3120 

R20D3120 

 
 
Gas Train Components – 

See Figure 42

 

40 Combustion 

Air 

Blower RA2113700 RA2113700 RA2107500 RA2114200 

41 Gas 

Valve/Venturi 

RV2017900 RV2017901 RV2017902 RV2017903 

42  On/Off Rectifier Module  E2324300 

E2324300 

E2324300 

E2324300 

47 

Gas 

Valve 

O-Ring  R30-227 R30-227 R30-227 R30-227 

51 Duct/Venturi 

Transition R10D5021 R10D5021 R10D5021 R10D5013 

52 Gas 

Supply 

Pipe 

RP2051700 RP2051400 RP2051400 RP2051400 

55  Air Inlet Flex Hose 

D0091403 

RD0091403  RD0091403 

D0091401 

 
 

Heat Exchanger Components – 

See Figure 44

60 Heat 

Exchanger 

RS2106900 RS2105500 RS2105800 RS2105700 

N.S.  Pump Assembly 

A2114900

 

A0076700

 

A0076700

 

14-55802

 

(Not Shown) 

62  Low Water Cutoff Switch 

— 

— 

— 

63 Inlet 

Water 

Temp 

Sensor 

RE2320600 RE2320600 RE2320600 RE2320600 

64  Duplex Outlet Water  

RE2319900  RE2319900  RE2319900  RE2319900 

 

Temperature Sensor

65 Duplex 

Stack 

 

RE2319700 RE2319700 RE2319700 RE2319700 

 

Temperature Sensor

66 

Pressure 

Relief 

Valve, 

R51-182 R51-182 R51-182 R51-182 

 

Boiler 

(30 PSI) 

(30 PSI) 

(30 PSI) 

(30 PSI) 

 

Pressure Relief Valve, 

 

 

A2114802 

A2114802 

 

 

 

 

(125 PSI) 

(125 PSI) 

67 

Air 

Vent 

 

R1-592 R1-592 R1-592 R1-592 

68 Burner 

Door 

w/gasket RS2112801 RS2112801 RS2112801 RS2112801 

68A  Burner Door Gasket

 (rubber)

 

R2069400 R2069400 R2069400 R2069400 

69 Burner 

Gasket 

RS2108500 RS2108500 RS2108500 RS2108500 

69A 

Gasket 

Set 

 

RS2109100 RS2109100 RS2109100 RS2109100 

 

(burner gasket, ignitor gasket, sensor gasket & burner door gasket)

70 Front 

Refractory 

Tile  RT2109001 RT2109001 RT2109001 RT2109001 

71 Rear 

Refractory 

Tile  R50D2021 R50D2021 R50D2021 R50D2021 

72  Main Burner w/gasket 

R2069101 

R2069102 

R2069103 

R2069104 

73 

Flame 

Sensor 

w/gasket 

R2069200 R2069200 R2069200 R2069200 

74 

Ignitor 

w/gasket 

R2069300 R2069300 R2069300 R2069300 

74A Ignitor 

Gasket 

RW2013300 RW2013300 RW2013300 RW2013300 

74B Screw, 

Ignitor/ 

m4-.7X8mm m4-.7X8mm m4-.7X8mm m4-.7X8mm 

 

Flame 

Sensor 

S2112700 S2112700 S2112700 S2112700 

74C Flame/Sensor 

Gasket RW2013400 RW2013400 RW2013400 RW2013400 

Содержание NEOTHERM NTH Series

Страница 1: ...fire department Installation and service must be performed by a qualified installer service agency or gas supplier AVERTISSEMENT Assurez vous de bien suivres les instructions donn es dans cette notic...

Страница 2: ...te Drain 23 6 D Freeze Protection 23 6 E Recognized Chemicals 23 6 F Suggested Piping Schematics 24 30 SECTION 7 ELECTRICAL AND WIRING DIAGRAMS 7 A Installation Warnings 31 7 B Main Power Connections...

Страница 3: ...ponent Description 56 10 C Gas Conversion 58 SECTION 11 OPERATING DETAILS AND TROUBLESHOOTING 11 A Normal Startup and Initialization 60 11 B Sequence of Operation 60 11 C Modulation Control 60 11 D Pu...

Страница 4: ...LAARS Heating Systems...

Страница 5: ...input 2 1 0 210 000 BTU hr input 7 Fuel N Natural Gas P LP Gas 8 Options Code X U S C Canada 9 Pump Options N Pump included X No pump configuration available for all sizes 10 Revision 3 Third version...

Страница 6: ...o hot such as domestic hot water use adjust the outlet control limit or use temperature limiting valves to obtain a maximum water temperature of 125 F 52 C WARNING The inlet gas pressure to the unit m...

Страница 7: ...turbed as a result of servicing or repair these substances become airborne and if inhaled may be hazardous to your health Do not remove or replace RCF parts or attempt any service or repair work invol...

Страница 8: ...AIR GAS BLOWER PRESSURE RELIEF VALVE WATER INLET WATER OUTLET AIR INLET CONNECTION DRAIN VALVE CONDENSATE TRAP AIR TRANSITION EXHAUST VENT CONNECTION GAS CONNECTION AIR PRESSURE SWITCH USER CONTROL I...

Страница 9: ...L AIR INLET VENT IN CM IN CM IN CM 19 49 2 5 1 2 5 1 19 49 2 5 1 2 5 1 19 49 3 7 6 3 7 6 26 68 3 7 6 3 7 6 A B D E F G J Size in cm in cm in cm in cm in cm in cm in cm 80 13 34 9 24 7 19 10 28 11 30 1...

Страница 10: ...Figure 3 1 Temperature pressure gauge kit 2 Air intake terminal 3 Exhaust vent terminal US only 4 Jumper Terminal 5 CPVC exhaust pipe section US only 6 Alternate size vent terminal screens 7 Outdoor...

Страница 11: ...e Wall or Roof Termination The forced draft combustion air blower in the unit has sufficient power to vent properly when the guidelines in Table 3 are followed NOTE When located on the same wall this...

Страница 12: ...12 xPPS VKL 5 xPPS VTML 5 8 83x050 2ZDESx Air Inlet 2ZDESx MFR MODEL NUMBER ABBREVIATED MFR MODEL NUMBER ABBREVIATED Trade Name Model Example Components Example Components Trade Name Model Boilers mus...

Страница 13: ...tal ducts each opening shall have a minimum free area of not less than 1square inch per 2000 Btu hr 1100 square mm kW of total input rating of all equipment in the enclosure Method 2 One permanent ope...

Страница 14: ...t can terminate through the roof or through an outside wall When using PVC CPVC for vent material venting must be connected to the CPVC section included with unit sizes 80 210 The CPVC vent section in...

Страница 15: ...terminal must be installed If an exhaust vent terminal is not available with the certified vent system the Manufacturer suggests the use of a coupler fitting from the certified vent system into which...

Страница 16: ...l so that it cannot be blocked by snow The National Fuel Gas Code requires that it be at least 12 inches 30cm above grade but the installer may determine it should be higher depending upon local condi...

Страница 17: ...ulator vent outlet See note 4 3 feet 91 cm J Clearance to nonmechanical air supply Direct vent only 12 30cm 80 285 inlet to building or the combustion air inlet Other than Direct vent 4 ft 1 2m below...

Страница 18: ...carbon monoxide detectors a In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic the hard wired carbon monoxide with alarm and battery ba...

Страница 19: ...rs and any other gas burning appliance to their previous conditions of use 7 Any improper operation of the common venting system should be corrected so that the installation conforms to the National F...

Страница 20: ...CTION 5 PUMP REQUIREMENTS 5 A Boiler Flow and Head Requirements Table 12 Water Flow Requirements Notes Consult and confirm with Applicable Fuel Gas Code before beginning work Verify gas inlet pressure...

Страница 21: ...measured at the supply pressure port on the gas valve Low gas pressure could be an indication of an undersized gas meter undersized gas supply lines and or an obstructed gas supply line Some Units are...

Страница 22: ...of boiler installation BOILER PIPE SIZE SIZE INCHES 80 1 105 1 150 1 210 1 Table 14 Water Connection Pipe Sizes SECTION 6 WATER CONNECTIONS 6 A Boiler System Piping Hot Supply Connections NOTE This u...

Страница 23: ...ich may result in bursting of pipes or damage to the boiler which could result in leaking or flooding conditions Do not use automotive antifreeze To help prevent freezing Manufacturer recommends the u...

Страница 24: ...Page 24 LAARS Heating Systems Figure 9 Hydronic Piping Single Boiler Zoning with Circulators...

Страница 25: ...Page 25 NEOTHERM Residential Boilers Figure 10 Hydronic Piping Single Boiler Low Temp Radiant Space Heating Using Low Loss Header and Zone Valves...

Страница 26: ...Page 26 LAARS Heating Systems Figure 11 Hydronic Piping Multiple Boilers Zoning with Circulators...

Страница 27: ...Page 27 NEOTHERM Residential Boilers Figure 12 Hydronic Piping Multiple Boilers with Indirect DHW Tank Piped from System Loop...

Страница 28: ...Page 28 LAARS Heating Systems Figure 13 Hydronic Piping Multiple Boilers Reverse Return Multi Temp Zones Zoning with Circulators...

Страница 29: ...Page 29 NEOTHERM Residential Boilers Figure 14 Hydronic Piping Heating Zones with Indirect DHW Tank Piped with Zone Pumps The indirect DHW tank is piped directly off of the boiler...

Страница 30: ...Page 30 LAARS Heating Systems Figure 15 Hydronic Piping Multiple Boilers with Indirect DHW Off of One Boiler The indirect DHW tank is piped directly off of the boiler...

Страница 31: ...isolation or unless otherwise instructed by procedures outlined in this manual To signal a call for heat use the 24V field interlock as shown in the wiring diagram DO NOT MAKE AND BREAK THE LINE VOLTA...

Страница 32: ...ommon settings used in a typical installation If your installation is more complex refer to Section 8C To reach the Quick Start menu press the I button Info Install then press the Quick Start menu ite...

Страница 33: ...Page 33 NEOTHERM Residential Boilers Figure 16 Control Panel Layout...

Страница 34: ...tions 7 F Lead Lag Connections These boilers can be connected in a lead lag series up to a total of 8 residential Units One as the Lead control and 7 more as the following controllers For general info...

Страница 35: ...olled and monitored using a BAS Building Automation Systems control but only if one of the EMEA User Interfaces is replaced with the available color touchscreen Call your Manufacturers Representative...

Страница 36: ...R GR VT GY R WH R GN TO J6 2 Y TO J4 10 OUTDOOR TEMP SENSOR TO GAS VALVE P1 1 2 2 1 6 1 6 1 6 1 Y WH GR TB6 FIELD CONNECTIONS ALARM TO J6 7 TO J6 8 BL BL Y OR BLK WH GY WH OR ALARM DHW TEMP SENSOR BLK...

Страница 37: ...WH R WH R LTGN FS 1 DKB Y PK R BLK WH GN GR R WH CL CL CL CL CL WH R GN TN BRN OR TN BL TN R Y GY BL VT WH WH BLK BLK BLK TO XFORMER WH TO XFORMER WH R BRN WH BRN R Y PUR PUR BLK TN Y TN WH TN BLK WH...

Страница 38: ...Page 38 LAARS Heating Systems Figure 19 Ladder Diagram 7 H Ladder Diagram...

Страница 39: ...his is not the same as the round OK button the two have different functions Note This user interface is also referred to as the EMEA Display Videos are available online Figure 20 The User Interface SE...

Страница 40: ...play Repeat this step for the other parameters if desired 8 E Entering Changing Control Settings Info Install Display including PASSWORDS The Info Install Display is where you will start every time Al...

Страница 41: ...option to adjust the contrast of the display or change the items which appear at the top of the Home display See the section on Display Setup Table 17 Functions on Info Install Menu Press the round OK...

Страница 42: ...me diagnostic and troubleshooting functions The installer level password is lnt lower case LNT OEM Level Some of the settings can only be changed at the Manufacturer factory Once you enter a password...

Страница 43: ...to enter the new value Changing the DHW Domestic Hot Water Setpoint See the procedure described above for the CH setpoint Changing a Value Using a Slider There is another type of control screen that...

Страница 44: ...then connected to terminal blocks 3 and 4 TB3 and TB4 See Figure 30 8 H Hydronic Heating Demand When using the unit for hydronic heating a call for heat must be supplied to the T T or Interlock termi...

Страница 45: ...s of the outdoor temperature The line in the graph would run straight across the display However with the Outdoor Reset feature turned on the system will adjust for changes in the outdoor temperature...

Страница 46: ...I to go to Info Install Choose Advanced Setup then go to Lead Lag Configuration Select Lead Lag Outdoor Reset Set the value on the line for Min Outdoor Temp 4 Set the low water temperature If the out...

Страница 47: ...ter DHW as a stand alone volume unit DHW models or as a secondary function while the unit also provides hydronic heating The piping used to supply domestic hot water DHW can be set up in several diffe...

Страница 48: ...an also be 0 10Vdc using a converter When setting up a sys tem using an external control take care to set Anti Short Cycle feature to prevent hunting and possible premature component failure Boiler Pu...

Страница 49: ...n rates of all of the operating boilers Lead Lag Modulation Cycle Note We will explain the modulation cycle here in case you need to understand how the Lead Lag system actually operates If you are ins...

Страница 50: ...of these addresses The unit operating as the Lead Lag Master should have address 1 and the other boilers should each have unique Modbus address numbers CAUTION You should set the Modbus addresses bef...

Страница 51: ...change the firing order of the boilers based on the run time of each burner identify each unit as a Follower by turning on Follower Enable How to get there From the Home screen press I to go to Info I...

Страница 52: ...Home screen press I to go to Info Install Choose Test then go to Forced Rate Select Set High Fire then select Start Test The CO2 readings should be between the values shown in Table 19 If the CO2 is n...

Страница 53: ...setting The Gas Valve in the 80 thru 210 is at the front of the unit and can be reached after the front panel is pulled forward and then off Always be patient with your combustion analyzer when making...

Страница 54: ...rt has been under water Manufacturer requires boilers to be replaced not repaired if they have been partially or completely submerged SECTION 9 FIRST START UP AND ADJUSTMENT INSTRUCTIONS 9 A Filling t...

Страница 55: ...the post purge cycle One or three additional attempts to light will follow Each cycle will include pre purge ignitor on valve flame on and post purge Ignition will not occur because the gas is off Th...

Страница 56: ...life and dependable operation but the safety of equipment depends on their proper functioning Only a qualified service technician should inspect the basic items listed below every year a Unit controls...

Страница 57: ...in gas supply line Remove the front door of the boiler to gain access to the flame sensor electrode Remove the flame sensor wire from the electrode Remove the two bolts fastening the electrode to the...

Страница 58: ...uired maintenance lack of water flow or improper operating practices WARNING Failure to rinse the debris from the heat exchanger and temporary drain line may lead to clogged condensate lines traps and...

Страница 59: ...l Boilers size mbtu Kit number 80 CA006201 105 CA006202 150 CA006203 210 CA006204 Table 20 Propane Gas Conversion Kits size mbtu Kit number 80 CA006206 105 CA006206 150 CA006206 210 CA006206 Table 21...

Страница 60: ...trol will lockout with a 109 error code 7 The call for heat signal is removed 8 The gas valve shuts off 9 The fan and pump continue to run for the over run times to purge the system This is the basic...

Страница 61: ...temperature rise delta T is calculated using the inputs from the outlet and inlet sensor temperatures Stack Limit The stack temperature is sensed by a dual thermistor sensor and is limit rated The co...

Страница 62: ...n 12 Front Bezel R50D7121 R50D7121 R50D7121 R50D7121 13 Display mounting frame R50D7122 R50D7122 R50D7122 R50D7122 12 13 Complete Assembly R50D7120 R50D7120 R50D7120 R50D7120 Internal Components See F...

Страница 63: ...Water Temp SensorRE2320600 RE2320600 RE2320600 RE2320600 64 Duplex Outlet Water RE2319900 RE2319900 RE2319900 RE2319900 Temperature Sensor 65 Duplex Stack RE2319700 RE2319700 RE2319700 RE2319700 Temp...

Страница 64: ...108700 RE2108700 RE2108700 RE2108700 82 High Voltage Shield R50D7002 R50D7002 R50D7002 R50D7002 83 Top Panel Bracket R50D7003 R50D7003 R50D7003 R50D7003 84 Electronic Control Contact Customer Service...

Страница 65: ...Page 65 NEOTHERM Residential Boilers Figure 41 Jacket Components Optional Touchscreen User Interface Kit KM50D7130 Call your local Manufacturers Rep...

Страница 66: ...Page 66 LAARS Heating Systems Figure 42 Gas Train Components Sizes 80 210 Figure 43 Internal Components Sizes 80 210...

Страница 67: ...Page 67 NEOTHERM Residential Boilers Figure 44 Heat Exchanger Components 68A 65 67 60 66 63 64...

Страница 68: ...Page 68 LAARS Heating Systems Figure 45 Electrical Components...

Страница 69: ...nual Pump Operation Info Advanced Setup System Config Pump Config Boiler pump cycle count Y A new value can be written here if the pump or controller is replaced Info Advanced Setup System Config Stat...

Страница 70: ...nfiguration I gain LL Y When using the Lead Lag system to control multiple boilers This gain is applied to the Integral term of the PID equation for the hydronic heating loop Info Advanced Setup Lead...

Страница 71: ...system will use the normal CH setpoint Quick Start Info Advanced Setup CH Configuration Outdoor Reset Config Min outdoor temp LL When using the Lead Lag system to control multiple boilers with Outdoor...

Страница 72: ...steresis value normally about 10 F Info Advanced Setup Lead Lag Configuration LL Master Config Outdoor reset CH Enable Outdoor Reset feature turned on Quick Start Info Advanced Setup CH Configuration...

Страница 73: ...Lead Lag Master to supervise the Lead Lag system The controllers on all of the other boilers must be enabled as Followers See the section on About Lead Lag The choices are Disable Enable via Modbus Ma...

Страница 74: ...erification L 1 Device in Configuration mode and safety parameters need verification and a device needs reset to complete verification 2 Configuration ended without verification re enter configuration...

Страница 75: ...ing flame sensing time H 26 Internal fault Static flame ripple H 27 Internal fault Flame rod shorted to ground detected H 28 Internal fault A D linearity test fails H 29 Internal fault Flame bias cann...

Страница 76: ...wer at Terminal Block 8 TB8 for the Safety Chain components See Figure 16 on page 33 3 Check wiring and correct any faults 4 Check all safety interlocks connected to the safety circuit to assure prope...

Страница 77: ...Domestic Hot Water sensor fault H 1 Check wiring and correct any possible errors 2 Replace the DHW sensor 3 If previous steps are correct and fault persists replace the module 94 Header sensor fault...

Страница 78: ...iled L 1 Check wiring and correct any potential wiring errors 2 Check VFD s Variable speed Fan Drive ability to change speeds 3 Change the VFD 4 If the fault persists replace the module 123 Purge rate...

Страница 79: ...sists replace the module 160 Ignition On L 1 Check Ignition terminal wiring and correct any errors 2 Reset and sequence the module If fault persists replace the module 161 Ignition Off L 1 Check the i...

Страница 80: ...sensor type setting L 192 Invalid igniter on during setting L 193 Invalid ignite failure delay setting L 194 Invalid ignite failure response setting L 195 Invalid ignite failure retries setting L 196...

Страница 81: ...ing L 221 Unconfigured DHW Domestic Hot Water high limit setpoint setting L 222 Unconfigured Outlet high limit setpoint setting L 223 Unconfigured Stack limit setpoint setting L 224 Invalid DHW Domest...

Страница 82: ...LAARS Heating Systems Notes...

Страница 83: ...NEOTHERM Residential Boilers Notes...

Страница 84: ...00 Fax 905 636 0666 www Laars com Litho in U S A Laars Heating Systems 20 04 Document 1252G Notes Dimensions and specifications subject to change without notice in accordance with our policy of contin...

Отзывы: