3. Set the DHW priority time. If the DHW function has the
priority, the priority will continue during the priority time.
If your system has just one boiler –
How to get there: From the “Home” screen, press “I” to
go to “Info/ Install.” Choose “Advanced Setup,” then go
to “DHW Configuration.” Select “DHW Priority Time.”
If your system has more than one boiler, and is
controlled using the Lead/ Lag function –
How to get there: On the unit used as the Lead Lag
Master, from the “Home” screen, press “I” to go to “Info/
Install.” Choose “Advanced Setup,” then go to “DHW
Configuration.” Select “DHW Priority Time.”
Figure 32. Lead / Lag Operation, 2 boilers.
Low demand -
The first boiler in
sequence fires at
less than 65%
First
boiler
Second
boiler
Demand increases -
Once the first boiler
reaches 65%,
the second boiler
switches on, and
both modulate
together between 20%
and 65% (adjustable up to 20% and
85%
).
Nearing max. demand -
Once both reach 65%,
then they are both
allowed to go over
65%
8.N About Lead Lag Operation
If an installation includes two or more boilers (up to 8
residential units), they may be set up for “Lead Lag”
operation. One boiler will be set up as the “Master”, and
the others will operate as “Followers.” Figure 38 shows
an installation with four boilers. (A Lead Lag system can
include up to eight boilers.) The boiler controllers are
connected in a “daisy chain” using a Modbus connection.
For the full wiring diagram for lead lag, See Figure
17 on page 34.
A single System sensor is used to monitor the demand
for heat. The input from this sensor is used by the Master
controller to control the modulation rates of all of the
operating boilers.
Lead Lag Modulation Cycle -
Note - We will explain the modulation cycle here, in case
you need to understand how the Lead Lag system actually
operates. If you are installing the unit(s) and want to skip
this section, just remember that, as the heating demand
increases, the Lead Lag system puts more boilers on-line.
As the heating demand is reduced, the Lead Lag system
shuts off some of the boilers.
The signal from the System sensor is sent to the unit
operating as the Lead Lag Master. A Run sequence is
initiated when the system temperature falls to the Lead
Lag Central Heat setpoint. (Actually this is the LL CH
setpoint less the On Hysteresis value. The default setting
for On Hysteresis is 5°F, but this is adjustable.)
Notice that, when a boiler is operating as part of a Lead
Lag system, it does not use the normal CH setpoint – it
uses the special LL CH setpoint on the Lead Lag Master.
The unit acting as the Lead Lag Master decides
which boiler is assigned to start first.
This assignment
is rotated across all of the available boilers so that
any one boiler does not run significantly longer than
the others. The Lead Lag controller tracks the run
times for all of the boilers, and uses this to calculate
the starting order for the boilers. This means that
each time the system starts up, a different boiler
may start first.
• When the Run sequence is initiated, the boiler with
the least amount of runtime will fire.
• If the heating demand increases so that the
firing rate of that first boiler rises to your boiler
configurations Base Load Value
(see
Table 18
)
, the
next boiler in the sequence will start up and begin
firing at 20 to 35% fan speed (depending on your
configuration). After this, the entire configuration
of boilers will modulate up or down together, in
Содержание NEOTHERM NTH Series
Страница 4: ...LAARS Heating Systems...
Страница 24: ...Page 24 LAARS Heating Systems Figure 9 Hydronic Piping Single Boiler Zoning with Circulators...
Страница 26: ...Page 26 LAARS Heating Systems Figure 11 Hydronic Piping Multiple Boilers Zoning with Circulators...
Страница 33: ...Page 33 NEOTHERM Residential Boilers Figure 16 Control Panel Layout...
Страница 38: ...Page 38 LAARS Heating Systems Figure 19 Ladder Diagram 7 H Ladder Diagram...
Страница 67: ...Page 67 NEOTHERM Residential Boilers Figure 44 Heat Exchanger Components 68A 65 67 60 66 63 64...
Страница 68: ...Page 68 LAARS Heating Systems Figure 45 Electrical Components...
Страница 82: ...LAARS Heating Systems Notes...
Страница 83: ...NEOTHERM Residential Boilers Notes...