background image

Mighty Max Volume Water Heater

Page 7

2G. Water System Piping

2G-1. Water Chemistry

Laars equipment is designed to be used in a

variety of water conditions. The water velocity in the
heat exchanger tubes is kept high enough to prevent
scaling from hard water, yet low enough to avoid
erosion by soft water. The water in 95 percent of the
urban centers in the United States is compatible with
this equipment, but in some areas a water supply will
contain a large quantity of scaling chemicals or the
water may be extremely soft or erosive. In rare
situations the water will contain both scaling
chemicals and erosive chemicals such as calcium or
sodium chloride. These conditions may be caused by
well water or a nearby pumping station, and the
particular condition may not be characteristic of the
entire city water system.

NOTE: It is possible to have hard and soft water

in the same city. Check with the local water company.

If an installer sees damage to any water handling

equipment at the installation site, it should be repaired
as soon as possible to help reduce maintenance costs.
If there is erosion, resize the pump to reduce water
velocity before the tube ruptures. If scaling is bad, set
up a heat exchanger tube-cleaning maintenance
schedule to prevent heat exchanger tube cracking and
wear. Not fixing the condition may cause serious
damage to the heater and the water system.

Scaling is a layer on the inner surface of the heat

exchanger tubes which restricts the flow of water.
Scale can be any color or texture, smooth or rough,
granular or amorphous. Erosion is usually identified
by pitting, cavitation, ridges and “islands” on the
inner surfaces of the heat exchanger tubes. If this is
caused by extremely soft water, or a water softener in
the system, the internal copper surfaces will be very
shiny. Other chemicals, such as chlorine or chlorides
in the water, will cause dark patches of erosion.

NOTE: Laars does not warrant heat exchangers

damaged by scaling, corrosion, or erosion.

2G-2. Water Piping

VW heaters are intended for heating large

volumes of water at constant flow rates, usually for
storage in a tank. Heaters in this type of application
are sometimes called circulating water heaters.

Figure 5 shows the VW heater with tank and two

pumps. One pump (recirculation) only circulates the
hot water through the building plumbing. The other
pump (heater) circulates water between the tank and
the heater. This heater circulating pump is essential
for proper operation of the heater (see Section 2G-5).

The heater circulating pump must be sized to

provide enough flow to prevent damage to the heat

exchanger, and must handle the hardness or softness
of the water being heated. Generally, hard water must
be pumped at higher velocity; however, soft water will
erode holes in the heat exchanger tubing if pumped
too fast.

The Mighty Max VW heater comes standard

with copper tubes, but in areas where the water supply
is soft or corrosive, the heat exchanger should be
factory ordered with cupronickel tubes. Consult the
local factory representative or Laars factory for
additional information.

2G-3. Pressure Buildup in Water System

The water utility supply meter may contain a

check valve, back flow preventer, or water pressure
reducing valve. This will create a closed water supply
system. Contact the water supplier or local plumbing
inspector on how to control this situation.

During the heating cycle of the heater, the water

expands creating a pressure buildup in the water
system. The pressure and temperature relief valve may
discharge hot water under these conditions, causing a
loss/waste of energy and a buildup of lime on the
relief valve seat.

NOTE: Do not plug the relief valve.

There are two methods to prevent the water

heater pressure relief valve from discharging hot
water in a closed water system:

1.

Install a pressure relief valve on the cold water
supply line. Make sure that the discharge of this
valve is directed to an open drain and protected
from freezing.

2.

Install a properly sized thermal expansion tank
on the cold water supply line.

2G-4. Temperature and Pressure Relief

Valve

For protection against excessive pressure, the

water heater is equipped with a pressure relief valve.

When the water heater is connected to a separate

storage vessel, a temperature and pressure relief valve
must be installed on the storage vessel. The
temperature and pressure relief valve must be design-
certified by a nationally recognized testing laboratory
that maintains periodic inspection of listed equipment
or materials, in accordance with the requirements for
Relief Valves and Automatic Gas Shutoff Devices for
Hot Water Supply Systems, ANSI Z21.22. (in Canada,
in accordance with the requirements for the Standard
for Temperature and Pressure Relief Valves and
Vacuum Relief Valves, CAN1-4.4).

The temperature and pressure relief valve must

have a BTU/h (kW) capacity rating that is greater than
the BTU/h (kW) input of the water heater. The
temperature and pressure relief valve must be marked
with a maximum working pressure not to exceed the

Содержание Mighty Max VW Series

Страница 1: ...a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance...

Страница 2: ...ersion for Ducted Combustion Air 14 2K 4 Combustion Air Piping 15 2L Electrical Wiring 15 SECTION 3 Operation 3A Start Up Requirements 17 3B Hi Limit Checkout 17 3C Venturi and Gas Pressure Regulator...

Страница 3: ...clude the heater serial number and model number this information can be found on the rating plate installation date and name of the installer Shipping costs are not included in the warranty coverage S...

Страница 4: ...utdoor From Combustibles Inches mm Inches mm Top 18 457 Unobstructed Water Conn Side 12 305 12 305 Opposite side 6 152 6 152 Front Alcove Unobstructed Rear 6 152 6 152 Vent 6 152 Flooring Combustible...

Страница 5: ...drop 2 Check supply pressure and local code requirements before proceeding with work 3 Pipe fittings must be considered when determining gas pipe sizing Table 3 Natural Gas and Propane Pipe Size Requ...

Страница 6: ...controls see Figure 4 Fit the trap with a threaded cap which can be removed for cleaning 5 When required by code install a second manual gas shutoff valve Do not remove manual shutoff valve supplied w...

Страница 7: ...circulating pump is essential for proper operation of the heater see Section 2G 5 The heater circulating pump must be sized to provide enough flow to prevent damage to the heat exchanger and must hand...

Страница 8: ...of withstanding 210 F 99 C without distortion 4 Must be installed to allow complete drainage of both the relief valve and discharge pipe 5 Must not have any valve between the relief valve and the end...

Страница 9: ...ls to the heating system piping since the piping contains water for potable use Do not use solder containing lead in the potable water lines If the space heating system requires water temperatures gre...

Страница 10: ...r of the boiler jacket over the stack opening on the top panel of the boiler 8 Apply high temperature sealant see Table 6 to vent collar stack and install on the rear of the flue collector 9 Slip the...

Страница 11: ...on Category I Exhaust Terminal Detail Side View Wall Figure 7 Venting and Combustion Air Options NOTE All views are shown from rear of heater Horizontal Intake Terminal Detail Combustion Air Side View...

Страница 12: ...ollector IMPORTANT Maximum pipe length allowed is 50 feet 15m regardless of the number of elbows Maximum number of elbows allowed is 5 Vent pipe minimum clearance from combustible surfaces is 6 inches...

Страница 13: ...t the installer may determine it should be higher depending on local conditions 5 Locate the terminal so the vent exhaust does not settle on building surfaces and other nearby objects Vent products ma...

Страница 14: ...ke sure the ventilation air is not directed at the heater water piping or other equipment which could be damaged by freezing 2K 3 Conversion for Ducted Combustion Air The conversion to ducted combusti...

Страница 15: ...to ground the metal parts of the heater Often plastic pipe or dielectric unions isolate the heater electrically Service and maintenance personnel who work on or around the heater may be standing on we...

Страница 16: ...Page 16 LAARS HEATING SYSTEMS Figure 11 Wiring Diagram IGNITION SYSTEM 20 ON OFF SIZES 320 1000 NATURAL OR PROPANE...

Страница 17: ...oiler for a long enough period to bring the water temperature within the range of the hi limit slowly back off the high limit setting until the boiler shuts off The main burners should re ignite when...

Страница 18: ...the venturi throat tap yellow After installing the shutoff valves be certain they are closed Low Side of Manometer High Side of Manometer Venturi Inlet Tap Blue Venturi Throat Tap Yellow Gas Orifice T...

Страница 19: ...concepts The following section describes this setup procedure 5 Leaving the positive side of the manometer connected to the venturi inlet tap blue connect the negative side of the manometer to the sh...

Страница 20: ...regulator to track air pressure even when abnormal conditions occur such as blockage of the combustion air Before firing confirm that this tube and the venturi pressure switch tubes are in place and f...

Страница 21: ...GAS ORIFICE UNFIRED ELEVATION OFFSET DIFFERENTIAL VENTURI FT PRESSURE PRESSURE DIFFERENTIAL inch W C inch W C inch W C SEA LEVEL 0 4 4 0 5 8 2000 0 4 3 7 5 3 4000 0 4 3 4 4 9 6000 0 4 3 2 4 6 8000 0 4...

Страница 22: ...4B 2 4B 1 Inspection of the Heat Exchanger WARNING Improper installation or maintenance can cause nausea or asphyxiation from carbon monoxide in flue gases which could result in severe injury property...

Страница 23: ...device 5 Low water cutoffs including flushing or float types Every six months Other maintenance requirements include 1 Periodic cleaning of filters when supplied 2 Lubrication of moving parts when app...

Страница 24: ...ribes guidelines for checking the operation of electrical components installed on the heater Refer to the wiring diagram for correct connection locations 5C 1 General Troubleshooting This section desc...

Страница 25: ...Mighty Max Volume Water Heater Page 25 Figure 19 Troubleshooting Chart...

Страница 26: ...t Laars Heating Systems 480 S Service Road West Oakville Ontario Canada L6K 2H4 Telephone 905 844 8233 Item Description Part Number 1 Base Assembly 320M 20157801 400M 20157802 520M 20157803 625M 20157...

Страница 27: ...Mighty Max Volume Water Heater Page 27 Front View Right Side View...

Страница 28: ...Page 28 LAARS HEATING SYSTEMS Front View Rear View Right Side View Left Side View...

Страница 29: ...erature E2101400 13 Display Temperature E2101600 14 Heat Exchanger Assy 2 pass Copper Tubes 520M 20256003 625M 20256004 775M 20256005 1000M 20256006 Item Description Part Number Heat Exchanger Assy 2...

Страница 30: ...nt Safety Switch E2103000 37 Cover Plate For Gas Conn 320M 400M 20262701 520M 625M 20262702 775M 1000M 20262703 Item Description Part Number 38 Tile Assembly 320M 20255101 400M 20255102 520M 20255103...

Страница 31: ...Mighty Max Volume Water Heater Page 31...

Страница 32: ...05 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laars com Lith...

Отзывы: