background image

Page 22

LAARS HEATING SYSTEMS

3.

If a strainer is used in a pressure reducing valve
or in the piping, clean it every 6 months in
accordance with the manufacturer's instructions.

4.

At startup and every 6 months after, look at the
main burner flame for proper performance. The
burner should not require maintenance in normal
operation. If any malfunction indicates that the
burner needs service (e.g., a flame that is yellow,
or entire burner surface glowing red), call a
professional service technician. Flame
characteristics may be inspected during the first
30 seconds after ignition. Characteristics of a
good flame are:

a.

Blue flame color

b.

Dark-colored burner surface with
occasional glowing fibers on surface.
NOTE: After 30 seconds of operation the
combustion chamber will heat up and
prevent reliable flame observation.

5.

Inspect the venting system for blockage, leakage,
and corrosion at least once a year.

6.

Keep the heater area clear of combustible
material, gasoline, and other flammable liquids
and vapors.

7.

Be sure all combustion air and ventilation
openings are not blocked.

8.

After installation and first startup, check the heat
exchanger for black carbon soot buildup after the
following periods of operation: 24 hours, 7 days,
30 days, 90 days, and once every 6 months
thereafter.

4B. Heat Exchanger

Black carbon soot buildup on the external

surfaces of the heat exchanger is caused by one or
more of the following: incomplete combustion,
combustion air problems, venting problems and heater
short cycling. As soon as any buildup is seen, correct
the cause of the buildup. Scale can build up on the
inner surface of the heat exchanger tubes and
restrict the water flow
. Inspect the heat exchanger in
accordance with Section 4B-1.

If the heat exchanger needs cleaning see

Section 4B-2.

4B-1. Inspection of the Heat Exchanger

WARNING

Improper installation or maintenance can cause
nausea or asphyxiation from carbon monoxide in
flue gases which could result in severe injury,
property damage, or death.

4B-1a. External Heat Exchanger

Inspection

1.

Disconnect electrical supply to the heater.

2.

Turn off the gas supply by closing the manual
gas valve on the heater.

3.

On indoor models, remove the vent pipe, top
jacket section, flue collector.

4.

On outdoor models, remove outdoor vent
terminal, top jacket section, flue collector.

5.

After removing the flue collector, inspect the
finned copper tubing using a flashlight.

6.

If there is a buildup of black carbon soot or other
debris on the heat exchanger tubes which may
restrict flue gas passage, refer to section 4B-2a.

7.

If there is no buildup of black carbon soot or
other debris which may restrict flue gas passage
through the heat exchanger, reassemble the
heater.

4B-1b. Internal Heat Exchanger

Inspection

1.

Remove the inlet/outlet header of the heat
exchanger.

2.

Remove the return cover of the heat exchanger.

3.

Inspect the internal surface of the copper tubes
for signs of scale buildup and erosion.

4.

If buildup exists clean per 4B-2b.

4B-2a. Cleaning the Heat Exchanger -

External

NOTE: The heat exchangers are heavy and may

require two people to remove to avoid personal injury.

Caution

Black carbon soot buildup on a dirty heat exchanger
can be ignited by a random spark or flame. To
prevent this from happening, dampen the soot
deposits with a wet brush or fine water spray before
servicing the heat exchanger.

1.

Disconnect the 120 Vac electrical supply to the
heater.

2.

Turn off the gas supply by closing the manual
gas valve on the heater.

3.

Disconnect and remove the wires and conduit
from the low water cutoff.

4.

Remove the top jacket section, venting and the
flue collector as mentioned in Section 4B-1
“Inspection of the Heat Exchanger”.

5.

Isolate the heat exchanger from water supply.

6.

Drain the heat exchanger.

Содержание Mighty Max VW Series

Страница 1: ...a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance...

Страница 2: ...ersion for Ducted Combustion Air 14 2K 4 Combustion Air Piping 15 2L Electrical Wiring 15 SECTION 3 Operation 3A Start Up Requirements 17 3B Hi Limit Checkout 17 3C Venturi and Gas Pressure Regulator...

Страница 3: ...clude the heater serial number and model number this information can be found on the rating plate installation date and name of the installer Shipping costs are not included in the warranty coverage S...

Страница 4: ...utdoor From Combustibles Inches mm Inches mm Top 18 457 Unobstructed Water Conn Side 12 305 12 305 Opposite side 6 152 6 152 Front Alcove Unobstructed Rear 6 152 6 152 Vent 6 152 Flooring Combustible...

Страница 5: ...drop 2 Check supply pressure and local code requirements before proceeding with work 3 Pipe fittings must be considered when determining gas pipe sizing Table 3 Natural Gas and Propane Pipe Size Requ...

Страница 6: ...controls see Figure 4 Fit the trap with a threaded cap which can be removed for cleaning 5 When required by code install a second manual gas shutoff valve Do not remove manual shutoff valve supplied w...

Страница 7: ...circulating pump is essential for proper operation of the heater see Section 2G 5 The heater circulating pump must be sized to provide enough flow to prevent damage to the heat exchanger and must hand...

Страница 8: ...of withstanding 210 F 99 C without distortion 4 Must be installed to allow complete drainage of both the relief valve and discharge pipe 5 Must not have any valve between the relief valve and the end...

Страница 9: ...ls to the heating system piping since the piping contains water for potable use Do not use solder containing lead in the potable water lines If the space heating system requires water temperatures gre...

Страница 10: ...r of the boiler jacket over the stack opening on the top panel of the boiler 8 Apply high temperature sealant see Table 6 to vent collar stack and install on the rear of the flue collector 9 Slip the...

Страница 11: ...on Category I Exhaust Terminal Detail Side View Wall Figure 7 Venting and Combustion Air Options NOTE All views are shown from rear of heater Horizontal Intake Terminal Detail Combustion Air Side View...

Страница 12: ...ollector IMPORTANT Maximum pipe length allowed is 50 feet 15m regardless of the number of elbows Maximum number of elbows allowed is 5 Vent pipe minimum clearance from combustible surfaces is 6 inches...

Страница 13: ...t the installer may determine it should be higher depending on local conditions 5 Locate the terminal so the vent exhaust does not settle on building surfaces and other nearby objects Vent products ma...

Страница 14: ...ke sure the ventilation air is not directed at the heater water piping or other equipment which could be damaged by freezing 2K 3 Conversion for Ducted Combustion Air The conversion to ducted combusti...

Страница 15: ...to ground the metal parts of the heater Often plastic pipe or dielectric unions isolate the heater electrically Service and maintenance personnel who work on or around the heater may be standing on we...

Страница 16: ...Page 16 LAARS HEATING SYSTEMS Figure 11 Wiring Diagram IGNITION SYSTEM 20 ON OFF SIZES 320 1000 NATURAL OR PROPANE...

Страница 17: ...oiler for a long enough period to bring the water temperature within the range of the hi limit slowly back off the high limit setting until the boiler shuts off The main burners should re ignite when...

Страница 18: ...the venturi throat tap yellow After installing the shutoff valves be certain they are closed Low Side of Manometer High Side of Manometer Venturi Inlet Tap Blue Venturi Throat Tap Yellow Gas Orifice T...

Страница 19: ...concepts The following section describes this setup procedure 5 Leaving the positive side of the manometer connected to the venturi inlet tap blue connect the negative side of the manometer to the sh...

Страница 20: ...regulator to track air pressure even when abnormal conditions occur such as blockage of the combustion air Before firing confirm that this tube and the venturi pressure switch tubes are in place and f...

Страница 21: ...GAS ORIFICE UNFIRED ELEVATION OFFSET DIFFERENTIAL VENTURI FT PRESSURE PRESSURE DIFFERENTIAL inch W C inch W C inch W C SEA LEVEL 0 4 4 0 5 8 2000 0 4 3 7 5 3 4000 0 4 3 4 4 9 6000 0 4 3 2 4 6 8000 0 4...

Страница 22: ...4B 2 4B 1 Inspection of the Heat Exchanger WARNING Improper installation or maintenance can cause nausea or asphyxiation from carbon monoxide in flue gases which could result in severe injury property...

Страница 23: ...device 5 Low water cutoffs including flushing or float types Every six months Other maintenance requirements include 1 Periodic cleaning of filters when supplied 2 Lubrication of moving parts when app...

Страница 24: ...ribes guidelines for checking the operation of electrical components installed on the heater Refer to the wiring diagram for correct connection locations 5C 1 General Troubleshooting This section desc...

Страница 25: ...Mighty Max Volume Water Heater Page 25 Figure 19 Troubleshooting Chart...

Страница 26: ...t Laars Heating Systems 480 S Service Road West Oakville Ontario Canada L6K 2H4 Telephone 905 844 8233 Item Description Part Number 1 Base Assembly 320M 20157801 400M 20157802 520M 20157803 625M 20157...

Страница 27: ...Mighty Max Volume Water Heater Page 27 Front View Right Side View...

Страница 28: ...Page 28 LAARS HEATING SYSTEMS Front View Rear View Right Side View Left Side View...

Страница 29: ...erature E2101400 13 Display Temperature E2101600 14 Heat Exchanger Assy 2 pass Copper Tubes 520M 20256003 625M 20256004 775M 20256005 1000M 20256006 Item Description Part Number Heat Exchanger Assy 2...

Страница 30: ...nt Safety Switch E2103000 37 Cover Plate For Gas Conn 320M 400M 20262701 520M 625M 20262702 775M 1000M 20262703 Item Description Part Number 38 Tile Assembly 320M 20255101 400M 20255102 520M 20255103...

Страница 31: ...Mighty Max Volume Water Heater Page 31...

Страница 32: ...05 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laars com Lith...

Отзывы: