background image

Mighty Max Volume Water Heater

Page 13

3.

Routing vent pipe through spaces which, except
for the terminal, remain above 60°F (16°C)
during heater operation.

2J-3. Horizontal Venting - Non-Category I

When venting is horizontal, or cannot meet the

code requirements for Category I - Blower-Assisted
Vertical Vents, it can develop positive pressure and
must be installed in accordance with this section.

The following requirements must be used for

Horizontal Venting - Non-Category I:

1.

Laars specified vent piping materials
(Table 6) and sizes (Table 7).

2.

Laars side wall vent hood.

3.

Pipe insulation and sealing tape.

4.

Routing vent pipe through spaces which, except
for the terminal, remain above 60°F (16°C)
during heater operation.

2J-4. Side Wall Vent Terminal

The side wall vent hood must be used when the

heater is vented through a side wall. It provides a
means of installing vent piping through the building
wall, and must be located in accordance with ANSI
Z223.1/NFPA 54 and applicable local codes. In
Canada the installation must be in accordance with
CAN/CGA B149.1 or .2 and local applicable codes
(see Figure 9). Consider the following when installing
the terminal:

1.

Locate the vent terminal so that it will not be
damaged by pedestrians and other traffic, and so
the discharge is not objectionable. The National
Fuel Gas Code requires a through-wall vent
terminal be at least 7 feet (2.1m) above grade if
located at a public walkway.

2.

Locate the vent terminal so that vent gases
cannot be drawn into air conditioning system
inlets. The National Fuel Gas Code requires that
it be at least 6 feet (1.8m) above any such inlet
that is within 10 feet (3m).

3.

Locate the vent terminal so that vent gases
cannot enter the building through doors,
windows, gravity inlets or other openings. The
National Fuel Gas Code requires that it be
located at least 4 feet (1.2m) below, 4 feet
(1.2m) horizontally from, or 3 feet (0.9m) above
such openings.

4.

Locate the vent terminal so that it cannot be
blocked by snow. The National Fuel Gas code
requires that it be at least 12 inches (305mm)

above grade, but the installer may determine it
should be higher depending on local conditions.

5.

Locate the terminal so the vent exhaust does not
settle on building surfaces and other nearby
objects. Vent products may damage such
surfaces or objects. But the actual construction
of the vent terminal and the flow of vent
products must not be altered.

6.

Locate the terminal at least 6 feet (1.8m)
horizontally from any gas or electric metering,
regulating, or relief equipment, or building
opening.

2K. Air for Combustion and Ventilation

The heater requires air for combustion and the

space around the heater requires ventilation.
Combustion air can be provided by standard practices
as specified in the installation codes (ANSI Z223.1/
NFPA 54, in Canada, CAN/CGA B149.1 or .2 and
local applicable codes), or ducted directly to the
heater. Ventilation air must be provided in either case.

2K-1. Air From Room

Standard requirements for providing air for

combustion and ventilation are provided by ANSI
Z223.1/NFPA 54 and in Canada by CAN/CGA
B149.1 or .2. These codes require passages be
provided for air flow into the space where the heater
is installed. The size of these passages is based on the
firing rate of the heater and the path of air flow into
the space. In general, installations which take air from
inside the building require larger passages than those
which take air directly through an outside wall.

Failure to provide adequate combustion and

ventilation air can cause the heater, and other
appliances occupying the same space, to operate with
dangerous and inefficient combustion, and can cause
overheating of the space. Be sure to provide air
passages in accordance with ANSI Z223.1/NFPA 54,
in Canada, CAN/CGA B149.1 or .2 and local
applicable codes, and do not permit any other
condition, such as an exhaust blower, to affect the air
supply for combustion and ventilation.

2K-2. Ducted Combustion Air

Combustion air can be brought directly to the

heater through a duct of suitable size and length (see
Table 7). Consult Laars about installations not
covered by Table 7.

Combustion air must be taken from out-of-doors

by means of the Laars side wall terminal.
Locate the terminal within 10 feet (3m) of the
heater vent exhaust terminal, but no closer than 3 feet
(0.9m) (centerline distance).

Содержание Mighty Max VW Series

Страница 1: ...a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance...

Страница 2: ...ersion for Ducted Combustion Air 14 2K 4 Combustion Air Piping 15 2L Electrical Wiring 15 SECTION 3 Operation 3A Start Up Requirements 17 3B Hi Limit Checkout 17 3C Venturi and Gas Pressure Regulator...

Страница 3: ...clude the heater serial number and model number this information can be found on the rating plate installation date and name of the installer Shipping costs are not included in the warranty coverage S...

Страница 4: ...utdoor From Combustibles Inches mm Inches mm Top 18 457 Unobstructed Water Conn Side 12 305 12 305 Opposite side 6 152 6 152 Front Alcove Unobstructed Rear 6 152 6 152 Vent 6 152 Flooring Combustible...

Страница 5: ...drop 2 Check supply pressure and local code requirements before proceeding with work 3 Pipe fittings must be considered when determining gas pipe sizing Table 3 Natural Gas and Propane Pipe Size Requ...

Страница 6: ...controls see Figure 4 Fit the trap with a threaded cap which can be removed for cleaning 5 When required by code install a second manual gas shutoff valve Do not remove manual shutoff valve supplied w...

Страница 7: ...circulating pump is essential for proper operation of the heater see Section 2G 5 The heater circulating pump must be sized to provide enough flow to prevent damage to the heat exchanger and must hand...

Страница 8: ...of withstanding 210 F 99 C without distortion 4 Must be installed to allow complete drainage of both the relief valve and discharge pipe 5 Must not have any valve between the relief valve and the end...

Страница 9: ...ls to the heating system piping since the piping contains water for potable use Do not use solder containing lead in the potable water lines If the space heating system requires water temperatures gre...

Страница 10: ...r of the boiler jacket over the stack opening on the top panel of the boiler 8 Apply high temperature sealant see Table 6 to vent collar stack and install on the rear of the flue collector 9 Slip the...

Страница 11: ...on Category I Exhaust Terminal Detail Side View Wall Figure 7 Venting and Combustion Air Options NOTE All views are shown from rear of heater Horizontal Intake Terminal Detail Combustion Air Side View...

Страница 12: ...ollector IMPORTANT Maximum pipe length allowed is 50 feet 15m regardless of the number of elbows Maximum number of elbows allowed is 5 Vent pipe minimum clearance from combustible surfaces is 6 inches...

Страница 13: ...t the installer may determine it should be higher depending on local conditions 5 Locate the terminal so the vent exhaust does not settle on building surfaces and other nearby objects Vent products ma...

Страница 14: ...ke sure the ventilation air is not directed at the heater water piping or other equipment which could be damaged by freezing 2K 3 Conversion for Ducted Combustion Air The conversion to ducted combusti...

Страница 15: ...to ground the metal parts of the heater Often plastic pipe or dielectric unions isolate the heater electrically Service and maintenance personnel who work on or around the heater may be standing on we...

Страница 16: ...Page 16 LAARS HEATING SYSTEMS Figure 11 Wiring Diagram IGNITION SYSTEM 20 ON OFF SIZES 320 1000 NATURAL OR PROPANE...

Страница 17: ...oiler for a long enough period to bring the water temperature within the range of the hi limit slowly back off the high limit setting until the boiler shuts off The main burners should re ignite when...

Страница 18: ...the venturi throat tap yellow After installing the shutoff valves be certain they are closed Low Side of Manometer High Side of Manometer Venturi Inlet Tap Blue Venturi Throat Tap Yellow Gas Orifice T...

Страница 19: ...concepts The following section describes this setup procedure 5 Leaving the positive side of the manometer connected to the venturi inlet tap blue connect the negative side of the manometer to the sh...

Страница 20: ...regulator to track air pressure even when abnormal conditions occur such as blockage of the combustion air Before firing confirm that this tube and the venturi pressure switch tubes are in place and f...

Страница 21: ...GAS ORIFICE UNFIRED ELEVATION OFFSET DIFFERENTIAL VENTURI FT PRESSURE PRESSURE DIFFERENTIAL inch W C inch W C inch W C SEA LEVEL 0 4 4 0 5 8 2000 0 4 3 7 5 3 4000 0 4 3 4 4 9 6000 0 4 3 2 4 6 8000 0 4...

Страница 22: ...4B 2 4B 1 Inspection of the Heat Exchanger WARNING Improper installation or maintenance can cause nausea or asphyxiation from carbon monoxide in flue gases which could result in severe injury property...

Страница 23: ...device 5 Low water cutoffs including flushing or float types Every six months Other maintenance requirements include 1 Periodic cleaning of filters when supplied 2 Lubrication of moving parts when app...

Страница 24: ...ribes guidelines for checking the operation of electrical components installed on the heater Refer to the wiring diagram for correct connection locations 5C 1 General Troubleshooting This section desc...

Страница 25: ...Mighty Max Volume Water Heater Page 25 Figure 19 Troubleshooting Chart...

Страница 26: ...t Laars Heating Systems 480 S Service Road West Oakville Ontario Canada L6K 2H4 Telephone 905 844 8233 Item Description Part Number 1 Base Assembly 320M 20157801 400M 20157802 520M 20157803 625M 20157...

Страница 27: ...Mighty Max Volume Water Heater Page 27 Front View Right Side View...

Страница 28: ...Page 28 LAARS HEATING SYSTEMS Front View Rear View Right Side View Left Side View...

Страница 29: ...erature E2101400 13 Display Temperature E2101600 14 Heat Exchanger Assy 2 pass Copper Tubes 520M 20256003 625M 20256004 775M 20256005 1000M 20256006 Item Description Part Number Heat Exchanger Assy 2...

Страница 30: ...nt Safety Switch E2103000 37 Cover Plate For Gas Conn 320M 400M 20262701 520M 625M 20262702 775M 1000M 20262703 Item Description Part Number 38 Tile Assembly 320M 20255101 400M 20255102 520M 20255103...

Страница 31: ...Mighty Max Volume Water Heater Page 31...

Страница 32: ...05 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laars com Lith...

Отзывы: