background image

Page 24

LAARS HEATING SYSTEMS

developed. The factory recommends cleaning the filter
at least once every 30 days. In high contamination
areas, such as construction sites, factories, etc., the
filter may need to be cleaned daily. Failure to do so
could result in lower heat output and potential unsafe
operation.

SECTION 5
Troubleshooting

5A. Sequence of Operation

To troubleshoot the heater properly you must

first understand the sequence of operation of the
heater:

1.

Upon a call for heat a 24 Vac signal is sent
through fusible links and high limit(s) to the
ignition control “TH” terminal.

2.

The “IND” terminal of the ignition control is
energized for a 15 second pre-ignition purge
period during which the combustion blower
purges the combustion chamber.

3.

After the purge period there is a 20 to 35 second
igniter heat up period. The glow of the igniter
can be seen through the heater sight glass.

4.

Then there is a seven second trial for ignition.
During this time the gas valves are energized and
the main burner ignites. The gas valves will
remain energized throughout the call for heat as
long as the ignition control igniter senses a
stable flame.

5.

After the call for heat is satisfied the ignition
control closes the gas valves and operate the
blower for a thirty (30) second post purge cycle.
This clears the combustion chamber of
combustion products.

The ignition is attempted three times. If ignition

is not successful, the control shuts down and “locks
out”. It remains in the lockout condition until the
heater is turned off then back on or 120 Vac power to
the heater is interrupted.

5B. Venturi and Gas Pressure

Regulator System

Field Checkout
See Section 3B “Venturi and Gas Pressure

Regulator System” for proper setup procedure.

5C. Electrical Components

This section describes guidelines for checking

the operation of electrical components installed on the

heater. Refer to the wiring diagram for correct
connection locations.

5C-1. General Troubleshooting

This section describes guidelines for checking

the electrical components of the heater. Experience
has shown that most complaints about heaters failing
to fire have nothing to do with the heater itself.
Usually, one of the protective switches in the heater
system has shut down operation.

Any of the following can prevent proper

operation. Check these items first:

1.

Be sure the heater has been properly installed
(see Section 2).

2.

Make sure the pump is not airlocked, clogged or
otherwise inoperative.

3.

Make sure the gas valve is on and there is
sufficient gas pressure in the line. All external
gas valves must be open.

Caution

The ignition control and igniter operate on 120V
power. Keep this in mind while servicing the heater,
and take care to avoid electrical shock.

4.

Verify that the electrical circuit serving the
boiler is ON

5.

Make sure the toggle switch on the right side of
the boiler is ON.

6.

Check the fuse inside the black, twist-lock fuse
holder. If it is burned, replace it with a 2-amp
fuse (part number E0084400).

7.

With the power off inspect all electrical
connections and wiring. Finding a loose
connection or charred wire can save a lot of time
and money.

8.

Make sure the temperature controller is set high
enough to call for heat.

9.

Make sure none of the manual reset controls, i.e.,
low water cutoff, high limit, etc., have tripped.
Reset any tripped switches

If the pump is circulating water and the

foregoing items check out okay, the trouble may be in
the boiler control system.

IMPORTANT: Disconnect power to the heater

before removing or replacing any component or wire
connection. If the power is not disconnected,
“jumping” the gas valve or accidentally grounding the
wire harness or component terminals to the heater
frame or jacket could cause the ignition control fuse to
blow.

Содержание Mighty Max VW Series

Страница 1: ...a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance...

Страница 2: ...ersion for Ducted Combustion Air 14 2K 4 Combustion Air Piping 15 2L Electrical Wiring 15 SECTION 3 Operation 3A Start Up Requirements 17 3B Hi Limit Checkout 17 3C Venturi and Gas Pressure Regulator...

Страница 3: ...clude the heater serial number and model number this information can be found on the rating plate installation date and name of the installer Shipping costs are not included in the warranty coverage S...

Страница 4: ...utdoor From Combustibles Inches mm Inches mm Top 18 457 Unobstructed Water Conn Side 12 305 12 305 Opposite side 6 152 6 152 Front Alcove Unobstructed Rear 6 152 6 152 Vent 6 152 Flooring Combustible...

Страница 5: ...drop 2 Check supply pressure and local code requirements before proceeding with work 3 Pipe fittings must be considered when determining gas pipe sizing Table 3 Natural Gas and Propane Pipe Size Requ...

Страница 6: ...controls see Figure 4 Fit the trap with a threaded cap which can be removed for cleaning 5 When required by code install a second manual gas shutoff valve Do not remove manual shutoff valve supplied w...

Страница 7: ...circulating pump is essential for proper operation of the heater see Section 2G 5 The heater circulating pump must be sized to provide enough flow to prevent damage to the heat exchanger and must hand...

Страница 8: ...of withstanding 210 F 99 C without distortion 4 Must be installed to allow complete drainage of both the relief valve and discharge pipe 5 Must not have any valve between the relief valve and the end...

Страница 9: ...ls to the heating system piping since the piping contains water for potable use Do not use solder containing lead in the potable water lines If the space heating system requires water temperatures gre...

Страница 10: ...r of the boiler jacket over the stack opening on the top panel of the boiler 8 Apply high temperature sealant see Table 6 to vent collar stack and install on the rear of the flue collector 9 Slip the...

Страница 11: ...on Category I Exhaust Terminal Detail Side View Wall Figure 7 Venting and Combustion Air Options NOTE All views are shown from rear of heater Horizontal Intake Terminal Detail Combustion Air Side View...

Страница 12: ...ollector IMPORTANT Maximum pipe length allowed is 50 feet 15m regardless of the number of elbows Maximum number of elbows allowed is 5 Vent pipe minimum clearance from combustible surfaces is 6 inches...

Страница 13: ...t the installer may determine it should be higher depending on local conditions 5 Locate the terminal so the vent exhaust does not settle on building surfaces and other nearby objects Vent products ma...

Страница 14: ...ke sure the ventilation air is not directed at the heater water piping or other equipment which could be damaged by freezing 2K 3 Conversion for Ducted Combustion Air The conversion to ducted combusti...

Страница 15: ...to ground the metal parts of the heater Often plastic pipe or dielectric unions isolate the heater electrically Service and maintenance personnel who work on or around the heater may be standing on we...

Страница 16: ...Page 16 LAARS HEATING SYSTEMS Figure 11 Wiring Diagram IGNITION SYSTEM 20 ON OFF SIZES 320 1000 NATURAL OR PROPANE...

Страница 17: ...oiler for a long enough period to bring the water temperature within the range of the hi limit slowly back off the high limit setting until the boiler shuts off The main burners should re ignite when...

Страница 18: ...the venturi throat tap yellow After installing the shutoff valves be certain they are closed Low Side of Manometer High Side of Manometer Venturi Inlet Tap Blue Venturi Throat Tap Yellow Gas Orifice T...

Страница 19: ...concepts The following section describes this setup procedure 5 Leaving the positive side of the manometer connected to the venturi inlet tap blue connect the negative side of the manometer to the sh...

Страница 20: ...regulator to track air pressure even when abnormal conditions occur such as blockage of the combustion air Before firing confirm that this tube and the venturi pressure switch tubes are in place and f...

Страница 21: ...GAS ORIFICE UNFIRED ELEVATION OFFSET DIFFERENTIAL VENTURI FT PRESSURE PRESSURE DIFFERENTIAL inch W C inch W C inch W C SEA LEVEL 0 4 4 0 5 8 2000 0 4 3 7 5 3 4000 0 4 3 4 4 9 6000 0 4 3 2 4 6 8000 0 4...

Страница 22: ...4B 2 4B 1 Inspection of the Heat Exchanger WARNING Improper installation or maintenance can cause nausea or asphyxiation from carbon monoxide in flue gases which could result in severe injury property...

Страница 23: ...device 5 Low water cutoffs including flushing or float types Every six months Other maintenance requirements include 1 Periodic cleaning of filters when supplied 2 Lubrication of moving parts when app...

Страница 24: ...ribes guidelines for checking the operation of electrical components installed on the heater Refer to the wiring diagram for correct connection locations 5C 1 General Troubleshooting This section desc...

Страница 25: ...Mighty Max Volume Water Heater Page 25 Figure 19 Troubleshooting Chart...

Страница 26: ...t Laars Heating Systems 480 S Service Road West Oakville Ontario Canada L6K 2H4 Telephone 905 844 8233 Item Description Part Number 1 Base Assembly 320M 20157801 400M 20157802 520M 20157803 625M 20157...

Страница 27: ...Mighty Max Volume Water Heater Page 27 Front View Right Side View...

Страница 28: ...Page 28 LAARS HEATING SYSTEMS Front View Rear View Right Side View Left Side View...

Страница 29: ...erature E2101400 13 Display Temperature E2101600 14 Heat Exchanger Assy 2 pass Copper Tubes 520M 20256003 625M 20256004 775M 20256005 1000M 20256006 Item Description Part Number Heat Exchanger Assy 2...

Страница 30: ...nt Safety Switch E2103000 37 Cover Plate For Gas Conn 320M 400M 20262701 520M 625M 20262702 775M 1000M 20262703 Item Description Part Number 38 Tile Assembly 320M 20255101 400M 20255102 520M 20255103...

Страница 31: ...Mighty Max Volume Water Heater Page 31...

Страница 32: ...05 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laars com Lith...

Отзывы: