Document 4288
M
ascot FT Gas Conversion Kit
pg 4 of 4
Figure F (Conversion label)
19.
Once the CO2 and manifold pressure measurements for both MIN and MAX Fire are correct,
turn OFF the Control Display
and set DIP switches 6 and 7 to the OFF position for
Nominal Fire (normal operation).
Turn the Control Display
back on when done.
20.
Write in the correct Conversion Date and the Technicians Name to the included gas
conversion sticker. See Figure F. Then apply that sticker adjacent to the rating plate.
21.
Put the boiler cover back on and assemble/tighten the 4 screws that hold the cover in place.
WARNING
Always make sure that the Control Display is turned
OFF
before changing any DIP switch. Then turn Control
Display back ON to continue with CO2 measurements.
Table C
Table D
This unit was converted on ____/____/___to _____gas
with kit #____________by______________________
(name and company __________________________
accountable)_________________________________
___________________________________________
Cette unité a été converti ____/____/____ten ______gaz
en utilisant le kit numéro _____ par______________
(nom et société_________________________________
responsable)___________________________________
_____________________________________________
CO
2
value
Natural Gas (NG)
Propane Gas (LP)
2˝ VENT
3˝ VENT
2˝ VENT
3˝ VENT
MFTCW140
MAX FIRE
8.5 - 10.5%
9.5 - 11%
MIN FIRE
8 - 10%
9 - 10.5 %
Manifold pressure
Natural Gas (NG)
Propane Gas (LP)
2˝ VENT
3˝ VENT
2˝ VENT
3˝ VENT
MFTCW140
MAX FIRE
-0.15” W.C
-0.216” W.C
-0.15” W.C
-0.216” W.C
MIN FIRE
0” W.C
0.002” W.C
0.1” W.C
0.079” W.C
NOTE: Installer is required to verify combustion
settings as part of the installation process.
CO should not exceed 200 ppm.
H2373800-
4.13 Natural Gas to Propane Conversion
SECTION 4. Installation
Содержание MASCOT FT MFTCW
Страница 45: ...Mascot FT Combination Boiler Page 43 Notes...
Страница 47: ...Mascot FT Combination Boiler Page 45 4 21 Ladder Diagram SECTION 4 Installation F B level Air Pressure Sensor...
Страница 63: ...Mascot FT Combination Boiler Page 61 6 2 Fault Tree Analysis 1 Flame detection...
Страница 76: ...LAARS Heating Systems Page 74 Heat Exchanger Tank 70 71 72 74 65 60 62 63 75 76 77 69 68...