LAARS Heating Systems
Page 16
Table 3. Required Exhaust Vent Material.
VENTING INSTALLATION STANDARDS
MATERIAL
UNITED STATES
CANADA
Stainless Steel
UL 1738
Venting must be ULC-S636 certified for use as
PVC, sch 40
ANSI/ASTM D1785
venting material. The venting material must be chosen
CPVC, sch 40
ANSI/ASTM F441
based upon the intended application of the boiler.
Polypropylene
UL1738 or ULC-S636
4.4 Venting (Exhaust)
The flue temperature of the Mascot FT changes
dramatically with changes in operating water
temperature. Therefore, it is necessary to assess the
application of the boiler to determine the required
certified vent class. If the Mascot FT is installed
in an application where the ambient temperature
is elevated, and/or installed in a closet/alcove,
CPVC, polypropylene, or stainless steel material is
required. If the system temperatures are unknown at
the time of installation, stainless, polypropylene or
CPVC material is recommended.
The Mascot FT is a Category IV appliance and may
be installed with PVC, CPVC or polypropylene that
complies with
ULC-S636, ANSI/ASTM D1785 F441
(see
Table 3)
or a stainless steel venting system that
complies with UL 1738 Standard and ULC S636.
WARNING
Use of cellular core PVC (ASTM F891), cellular core
CPVC, or Radel® (polyphenolsulfone) in venting
systems shall be prohibited.
WARNING
Failure to use the appropriate vent material, installation
techniques, glues/sealants could lead to vent failure
causing property damage, personal injury or death.
WARNING
All venting must be installed according to this manual
and any other applicable local codes, including but not
limited to, ANSI Z224.1/NFPA 54, CAN/CSA B149.1
and ULC-S636. Failure to follow this manual and
applicable codes may lead to property damage, severe
injury, or death.
INSTALLATIONS IN CANADA
require the use of
venting material certified to ULCS636. All Gas
vents connected to the Mascot FT, plastic, stainless
steel or otherwise must be certified to this ULC
standard. Appropriate selection of vent material is
very important for proper performance and safe
operation of the Mascot FT.
The flue temperature of the Mascot FT changes
dramatically with changes in operating water
temperature. Therefore, it is necessary to assess
the application of the boiler to determine the
required certified vent class. If the Mascot FT is
installed in an application where the outlet water
temperature exceeds 145°F, and/or installed in a
closet, class IIB or higher vent material is required.
If the system temperatures are unknown at the time
of installation, class IIB or higher venting material
is recommended.
IN CANADA
all venting used must meet the
following requirements:
1. ULC-S636 certified and marked
2. The first 3 feet of venting must be accessible
for visual inspection.
3. All components used in the vent system must
be from a certified manufacturer.
4 . Vent system components must not be mixed
with alternate manufacturers certified
components and/or unlisted components.
5 . The venting must be installed according to the
vent manufacturers installation instructions.
The unit’s vent can terminate through the roof, or
NOTICE
DO NOT COMMON VENT MASCOT FT UNITS.
Mascot FT units are never permitted to share a
vent with Category I appliances.
AVIS
NE PAS ÉVENT COMMUNE MASCOTTE FT UNITÉS
.
Mascotte FT unités ne sont jamais autorisés à
partager un évent Catégorie I avec les appareils.
Содержание MASCOT FT MFTCW
Страница 45: ...Mascot FT Combination Boiler Page 43 Notes...
Страница 47: ...Mascot FT Combination Boiler Page 45 4 21 Ladder Diagram SECTION 4 Installation F B level Air Pressure Sensor...
Страница 63: ...Mascot FT Combination Boiler Page 61 6 2 Fault Tree Analysis 1 Flame detection...
Страница 76: ...LAARS Heating Systems Page 74 Heat Exchanger Tank 70 71 72 74 65 60 62 63 75 76 77 69 68...