![Laars MASCOT FT MFTCW Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/laars/mascot-ft-mftcw/mascot-ft-mftcw_installation-and-operation-instructions-manual_3265583031.webp)
Mascot FT Combination Boiler
Page 29
SECTION 4. Installation
4.12 High Altitude Installations and Orifices
The Mascot FT is shipped with a Natural Gas Nozzle
(Orifice) that is suitable for altitudes up to 3,000 ft. The
Mascot FT may be installed at elevations up to 10,000
ft, and it can be converted to use Propane Gas to
operate at elevations up to 10,000 ft, but to achieve
this, the Gas Line Nozzle must be changed out to suit
the installation altitude and the desired gas.
To order the Gas Line Nozzle to suit your installation
altitude and gas, please visit laars.com/support to
get the contact info for your nearest Laars Sales
Representative.
Value
Nozzle (NAT)
Nozzle (LP)
0-3000 ft
(0-914 m)
6.5 mm
(0.256")
Factory Installed
4.85 mm
(0.191")
Included in Box.
3,000-6,500 ft
(914-1,981 m)
7.1 mm
(0.280")
#S182100096
5.0 mm
(0.197")
#S182100097
6,500-10,000 ft
(1,981-3,048 m)
5.1 mm
(0.201")
#S182100098
See Section 4.13
for instructions to change out
the Gas Line Nozzle in the Mascot FT.
Gas Line Nozzle (Orifice)
Содержание MASCOT FT MFTCW
Страница 45: ...Mascot FT Combination Boiler Page 43 Notes...
Страница 47: ...Mascot FT Combination Boiler Page 45 4 21 Ladder Diagram SECTION 4 Installation F B level Air Pressure Sensor...
Страница 63: ...Mascot FT Combination Boiler Page 61 6 2 Fault Tree Analysis 1 Flame detection...
Страница 76: ...LAARS Heating Systems Page 74 Heat Exchanger Tank 70 71 72 74 65 60 62 63 75 76 77 69 68...