![Laars MASCOT FT MFTCW Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/laars/mascot-ft-mftcw/mascot-ft-mftcw_installation-and-operation-instructions-manual_3265583030.webp)
LAARS Heating Systems
Page 28
4.10 Gas Supply Pressure
Refer to the illustration
*
.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any
pressure testing of the system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve
during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
Loosen the pressure port bolts before you check the gas inlet pressure.
SECTION 4. Installation
Inlet Gas Pressure port
*
Offset Adjustment.
Do Not Adjust without using a combustion analyzer
to verify adjustment. Adjust ONLY when in MIN
Fire and when using a combustion analyzer.
See Section 4.13 for step by step details.
Gas Outlet Pressure Port
*
4.11 Gas Setup and Adjustment
For the Step by step process to measure CO
2
values on the Mascot FT, please refer to Step 11 thru
Step 19 in Section 4.13 of this Installation Manual.
Always turn OFF Control Display before changing the DIP switches.
Table 10.
CO2 Values
Table 11.
Manifold Pressures
WARNING
Installer is required to verify combustion settings as part of
the installation process. CO should not exceed 200 ppm.
Standard Factory Setting is for MAX Fire. 9.0%
CO2 @ 0-2,000 ft altitude (Natural Gas).
Customer Service and Product Support:
800.900.9276 • Fax 800.559.1583
Headquarters:
20
Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com
Litho in U.S.A. © Laars Heating Systems 1503 Document 4288
800.900.9276
•
Fax 800.559.1583
(Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867
•
603.335.6300
•
Fax 603.335.3355
(Applications Engineering)
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8
•
905.238.0100
•
Fax 905.366.0130
www.Laars.com
Document 4288
M
ascot FT Gas Conversion Kit
pg 4 of 4
Figure F (Conversion label)
19.
Once the CO2 and manifold pressure measurements for both MIN and MAX Fire are correct,
turn OFF the Control Display
and set DIP switches 6 and 7 to the OFF position for
Nominal Fire (normal operation).
Turn the Control Display
back on when done.
20.
Write in the correct Conversion Date and the Technicians Name to the included gas
conversion sticker. See Figure F. Then apply that sticker adjacent to the rating plate.
21.
Put the boiler cover back on and assemble/tighten the 4 screws that hold the cover in place.
WARNING
Always make sure that the Control Display is turned
OFF
before changing any DIP switch. Then turn Control
Display back ON to continue with CO2 measurements.
Table C
Table D
This unit was converted on ____/____/___to _____gas
with kit #____________by______________________
(name and company __________________________
accountable)_________________________________
___________________________________________
Cette unité a été converti ____/____/____ten ______gaz
en utilisant le kit numéro _____ par______________
(nom et société_________________________________
responsable)___________________________________
_____________________________________________
CO
2
value
Natural Gas (NG)
Propane Gas (LP)
2˝ VENT
3˝ VENT
2˝ VENT
3˝ VENT
MFTCW140
MAX FIRE
8.5 - 10.5%
9.5 - 11%
MIN FIRE
8 - 10%
9 - 10.5 %
Manifold pressure
Natural Gas (NG)
Propane Gas (LP)
2˝ VENT
3˝ VENT
2˝ VENT
3˝ VENT
MFTCW140
MAX FIRE
-0.15” W.C
-0.216” W.C
-0.15” W.C
-0.216” W.C
MIN FIRE
0” W.C
0.002” W.C
0.1” W.C
0.079” W.C
NOTE: Installer is required to verify combustion
settings as part of the installation process.
CO should not exceed 200 ppm.
H2373800-
Customer Service and Product Support:
800.900.9276 • Fax 800.559.1583
Headquarters:
20
Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com
Litho in U.S.A. © Laars Heating Systems 1503 Document 4288
800.900.9276
•
Fax 800.559.1583
(Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867
•
603.335.6300
•
Fax 603.335.3355
(Applications Engineering)
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8
•
905.238.0100
•
Fax 905.366.0130
www.Laars.com
Document 4288
M
ascot FT Gas Conversion Kit
pg 4 of 4
Figure F (Conversion label)
19.
Once the CO2 and manifold pressure measurements for both MIN and MAX Fire are correct,
turn OFF the Control Display
and set DIP switches 6 and 7 to the OFF position for
Nominal Fire (normal operation).
Turn the Control Display
back on when done.
20.
Write in the correct Conversion Date and the Technicians Name to the included gas
conversion sticker. See Figure F. Then apply that sticker adjacent to the rating plate.
21.
Put the boiler cover back on and assemble/tighten the 4 screws that hold the cover in place.
WARNING
Always make sure that the Control Display is turned
OFF
before changing any DIP switch. Then turn Control
Display back ON to continue with CO2 measurements.
Table C
Table D
This unit was converted on ____/____/___to _____gas
with kit #____________by______________________
(name and company __________________________
accountable)_________________________________
___________________________________________
Cette unité a été converti ____/____/____ten ______gaz
en utilisant le kit numéro _____ par______________
(nom et société_________________________________
responsable)___________________________________
_____________________________________________
CO
2
value
Natural Gas (NG)
Propane Gas (LP)
2˝ VENT
3˝ VENT
2˝ VENT
3˝ VENT
MFTCW140
MAX FIRE
8.5 - 10.5%
9.5 - 11%
MIN FIRE
8 - 10%
9 - 10.5 %
Manifold pressure
Natural Gas (NG)
Propane Gas (LP)
2˝ VENT
3˝ VENT
2˝ VENT
3˝ VENT
MFTCW140
MAX FIRE
-0.15” W.C
-0.216” W.C
-0.15” W.C
-0.216” W.C
MIN FIRE
0” W.C
0.002” W.C
0.1” W.C
0.079” W.C
NOTE: Installer is required to verify combustion
settings as part of the installation process.
CO should not exceed 200 ppm.
H2373800-
CAUTION
Содержание MASCOT FT MFTCW
Страница 45: ...Mascot FT Combination Boiler Page 43 Notes...
Страница 47: ...Mascot FT Combination Boiler Page 45 4 21 Ladder Diagram SECTION 4 Installation F B level Air Pressure Sensor...
Страница 63: ...Mascot FT Combination Boiler Page 61 6 2 Fault Tree Analysis 1 Flame detection...
Страница 76: ...LAARS Heating Systems Page 74 Heat Exchanger Tank 70 71 72 74 65 60 62 63 75 76 77 69 68...