4.14 Re-Circulation Setting
Select Water Heater Mode (LT199NRX1, LT199PRX1)
Mode
Description
Setting
Requirement
Performance
11:RC
Dedicated
Return Line
Accessory
Wait Time
Water Savings
Energy
Savings
Hot Water
Temperature
No Recirculation
Same as regular tankless water heaters.
OFF
No
-
-
-
-
Internal
Hot water without dedicated return line.
Itnl
No
-
Better
Better
Better
External
Quick hot water with dedicated return line.
Etnl
Yes
-
Best
Better
Best
On Demand
(Title-24)"
Only operates recirculation line with a push
of a button.
tt24
Yes
O
Better
Best
Best
Crossover
Quick warm water without dedicated return
line.
CrOS
No
O
Best
Good
Warm
* Recirculation is activated by Timer [Auto / Manual].
Recirculation Modes : Internal Mode / External Mode / On-Demand Mode / Crossover Mode.
To select a recirculation mode, you must set from the ‘Installer Mode’ on the front control panel.(Refer to the page 34 )
When you use a recirculation mode, there will be some minor efficiency loss, as a result of the water heater maintaining a steady
temperature within the recirculation loop.
With the recirculation operation, hot water will be automatically circulated in the hot water pipes. Even with this function activated,
it may take several minutes for hot water to be completely circulated through the plumbing system. Set the timer to activate the
recirculation system prior to the first use of hot water to ensure hot water is available.
This water heater has a built-in pump and temperature sensor.
No Recirculation Mode, Internal Recirculation Mode
Recirculation timer setting can be changed by customer's own desire time.
Auto (self learning mode) function can be selected by customer's need.
1. Only POTABLE water may be plumbed through the water heater.
2. The water heater cannot be used for space heating applications.
3. Expansion tank is required if a backflow preventer is installed.