Tradesman Construction Heaters
www.lbwhite.com
Owner’s Manual • Tradesman
16
7. For reassembly, reverse the respective service
procedure. Ensure gas connections are tightened
securely.
8. After servicing, start the heater to ensure proper
operation and check for gas leaks.
9. Clean the heater’s ori
fi
ce with compressed air or a
soft, dry rag. Do not use
fi
les, drills, broaches, etc.
to clean the ori
fi
ce. Doing so may enlarge the hole,
causing combustion or ignition problems. Replace
the ori
fi
ce if it cannot be cleaned properly.
Motor, Fan, and Air
Proving Switch
1. Remove fan guard and screws securing the motor
mount to the heater’s barrel. See Fig 10.
2. Lift motor/fan assembly from heater.
FIG. 10
Motor
-- Remove both screws and strap securing the motor.
-- Position the motor between motor mount stops
when reinstalling.
Air Proving Switch (See Fig. 11)
(Not provided on Tradesman 170 standard heater)
-- Remove screw securing switch bracket to motor
mount.
-- On reassembly, ensure tab on switch bracket is
located in hole.
NOTE:
The air proving switch contacts must be open
prior to motor start-up. If the switch contacts
do not close after the motor starts, or are
closed prior to motor starting, the igniter will
not spark nor will the gas control valve open.
REMOVE
REMOVE
(BOTH SIDES)
Fan
-- Loosen set screw at hub.
-- Pull fan from shaft.
-- Ensure fan is
fl
ush on shaft end, and set screw is
positioned over
fl
at of motor shaft before tighten-
ing.
FIG. 11
Auto Reset High Limit
Switches
The auto reset high limit switch is designed to cut off
power to the gas control valve if the heater should
overheat due to blockage at the air inlet or discharge
outlet.
Depending on heater model, there can be one or
two high limit heat switches.
All Tradesman 170
heaters have two limits. Tradesman 400
heaters have only one limit switch.
Regardless of model, ensure any mounting hardware
(screws, spacers, or washers) is installed when
replacing or testing the switch.
Locations of the limits are:
Tradesman 170:
■
One on the burner plate and one on the underside
of the combustion chamber. See Figs. 12 and 13.
■
The switch on the underside of the combustion
chamber is accessed by removing the base bottom
of the heater.
- The combustion chamber is stamped with the let-
ters P (Propane) or N (Natural Gas) adjacent to the
screw holes to identify location for the appropriate
gas being used.
FAN HUB FLUSH WITH SHAFT END
SET SCREW
REMOVE
SCREWS
AIR PROVING
SWITCH
TAB IN HOLE
STRAP
Содержание Tradesman CP400
Страница 21: ...Tradesman Construction Heaters Owner s Manual Tradesman 21 FIG 29 FIG 30 COPPER WASHER COPPER WASHER...
Страница 38: ...Tradesman Construction Heaters www lbwhite com Owner s Manual Tradesman 38 Notes...
Страница 39: ......
Страница 78: ...Calefactores Tradesman para construcciones www lbwhite com Manual del usuario Tradesman 38 Notas...
Страница 79: ......
Страница 118: ...Fournaises de construction Tradesman www lbwhite com Manuel du propri taire Tradesman 38 Remarques...
Страница 119: ......