1. Do not attempt to install, repair, or service this heater

or the gas supply line unless you have continuing

expert training and knowledge of gas heaters.  

Qualifications for service and installation of this

equipment are as follows:

a. To be a qualified gas heater service person, you

must have sufficient training and experience to

handle all aspects of gas-fired heater installation,

service and repair.  This includes the task of

installation, troubleshooting, replacement of

defective parts and testing of the heater.  You

must be able to place the heater into a continuing

safe and normal operating condition.  You must

completely familiarize yourself with each model

heater by reading and complying with the safety

instructions, labels, Owner’s Manual, etc., that is

provided with each heater.

b. To be a qualified gas installation person, you must

have sufficient training and experience to handle

all aspects of installing, repairing and altering gas

lines, including selecting and installing the proper

equipment, and selecting proper pipe and tank

size to be used.  This must be done in accordance

with all local, state and national codes as well as

the manufacturer’s requirements.

2. All installations and applications of L. B. White

heaters must meet all relevant local, state and

national codes.  Included are AS5601 Gas

Installation Code, electrical, and safety codes.  Your

local fuel gas supplier, a local licensed electrician,

the local fire department or similar government

agencies, or your insurance agent can help you

determine code requirements.

3. Do not move, handle, or service heater while in

operation or connected to a power or fuel supply.

4. This heater may be installed in areas subject to

washdown.  This heater may only be washed on the

external case assembly—see Cleaning Instructions.

Do not wash the interior of the heater.  Use only

compressed air, soft brush or dry cloth to clean the

interior of the heater and it’s components.  After

external washdown, do not operate this heater until it

is completely dry.  In any event, do not operate the

heater for at least one hour after external washdown.

5. For safety, this heater is equipped with a manual

reset high-limit switch and an air flow switch.  Never

operate this heater with any safety device that has

been bypassed.  Do not operate this heater unless all

of these features are fully functioning.

6. Do not operate the heater with its door open or panel

removed.  

7. Do not locate fuel gas containers or  fuel supply

hoses anywhere near the blower outlet of the heater.

8. Do not block air intakes or discharge outlets of the

appliance.  Doing so may cause improper combustion

or damage to heater components leading to property

damage or animal loss.

9. The hose assembly (if provided) shall be visually

inspected on an annual basis.  If it is evident there is

excessive abrasion or wear, or if the hose is cut, it

must be replaced prior to the heater being put into

operation.  The hose assembly shall be protected

from animals, building materials, and contact with

hot surfaces during use.  The hose assembly shall be

that specified by the manufacturer.  See parts list.

10. Check for gas leaks and proper function upon heater

installation, before building repopulation or when

relocating.

11. This heater should be inspected for proper operation

by a qualified service person before building

repopulation and at least annually.

12. Always turn off the gas supply to the heater if the

appliance is not going to be used in the heating of

livestock.

13. This heater is wired for a three-wire electrical system.

There is a hot lead, neutral lead and ground lead.

The heater may or may not incorporate a plug in the

power cord to the heater and the plug may or may not

incorporate a pin for the ground wire.  In any case,

the heater must be properly connected into a

grounded electrical supply using the ground lead in

the power cord.  Failure to use a properly grounded

electrical supply can result in electrical shock,

personal injury or death.

14. Hot surface ignition heaters will make up to  three

trials for ignition.  If ignition is not achieved after the

third trial, the control system will “lock out” the gas

control valve.  If gas is smelled after system lock out

has occurred, immediately close all fuel supply

valves.  Do not relight until you are sure that all gas

that may have accumulated has cleared away.  In any

event, do not relight for at least 5 minutes.  

15. In a hanging type installation, rigid pipe or copper

tubing coupled directly to the heater may cause gas

leaks during movement, and therefore must not be

used.  Use only a certified gas hose assembly 

(AS/NZS 1869 Class B or D) that is rated and

approved for LP-gas and natural gas in a hanging type

of installation.

16. Installations not using the gas hose supplied with this

heater must connect dimensionally using the

Australian AS5601 Gas Installations or local codes as

required.  (Aluminum piping or tubing shall not be

used.)  Copper tubing when used for conveying

natural gas, shall be internally tinned or equivalently

treated to resist sulphur.

6

Safety Precautions

Содержание AW230

Страница 1: ...ating heater for the heating of agricultural animal confinement buildings The heater is approved for either indoor or outdoor mounting If you are considering using this product for any application oth...

Страница 2: ...ury or loss of life GENERAL HAZARD WARNING Failure to comply with the precautions and instructions provided with this heater can result in Death Serious bodily injury or burns Property damage or loss...

Страница 3: ...cal L B White distributor or the L B White Co Inc for assistance or if you have any questions about the use of the equipment or its application The L B White Co Inc has a policy of continuous product...

Страница 4: ...as Gas Model Ventilation Air Required to Support Combustion 1 83 Meters Reference AS1596 and AS5601 Gas Installations Burner Manifold Pressure Electrical Supply Volts Hz Phase Amp Draw Starting Amps I...

Страница 5: ...ss and difficulty in breathing Symptoms of improper combustion affecting livestock can be disease lower feed conversion or death Asphyxiation Hazard Some people cannot smell well Some people cannot sm...

Страница 6: ...e fuel gas containers or fuel supply hoses anywhere near the blower outlet of the heater 8 Do not block air intakes or discharge outlets of the appliance Doing so may cause improper combustion or dama...

Страница 7: ...f pipe compound before further tightening Further tighten the gas connections as necessary to stop the leak After all connections are checked and any leaks are stopped turn on the main burner Stand cl...

Страница 8: ...ts found in performing any of the service or maintenance procedures must be eliminated and defective parts replaced immediately The heater must be retested by properly qualified service personnel befo...

Страница 9: ...mounted in a vertical position Make sure pipe thread compound that is resistant to both L P and natural gas is used in making all connections Check all connections for gas leaks using approved gas lea...

Страница 10: ...ring of a thermostat must be done by an electrician or someone properly qualified b The thermostat may use 18 gauge 2 wire cord to handle the low voltage being supplied to the thermostat from the tran...

Страница 11: ...tance in troubleshooting Only qualified and properly trained personnel shall service or repair the heater 7 On a call for heat the motor will start up and run for five 5 seconds and then stop This pre...

Страница 12: ...d the area between the heat chamber top and inside case is also free of dust Additionally the flame sensor should be removed and cleaned according to the service instructions within this Owner s Manua...

Страница 13: ...ITCH ARM FANWHEEL PIVOT POINT OF FLAPPER EDGE OF FLAPPER PIVOT POINT OF FLAPPER FLAPPER 31 7 MMTO 34 9 MM 1 Shut off the gas supply to the heater 2 Disconnect the heater from its electrical supply 3 M...

Страница 14: ...nlet pressures to gas control valve are shown in the heater specifications table See page 4 and on the heater s dataplate The inlet pressure may need adjustment as necessary to achieve proper manifold...

Страница 15: ...sensor IMPORTANT For proper flame sense operation the flame sensor tip must be properly positioned within the burner flame Normally 12 7 mm to 19 mm is sufficient See Fig 13 FIG 13 The high limit swi...

Страница 16: ...it will relate directly to problem solving provided by the flow charts The ignition control module is self diagnostic The red light on the module will flash a specific pattern depending upon the probl...

Страница 17: ...Switch Closes Gas Control Valve Opens Ignition Occurs Igniter stays Powered up for 6 seconds after Ignition Flame Proving occurs in 6 seconds Igniter Shuts Off Gas Valve Stays Open Room Warms to Desir...

Страница 18: ...ly Requirements Provide Proper Voltage From Electrical Supply Check Circuit Breakers in Building Electrical System Check Power Cord for Continuity Replace Thermostat Replace Selector Switch Are 24 Vol...

Страница 19: ...Rapid Flash Reverse Polarity Have Electrician Check Neutral and Hot Wire Connections that Outlet Heater is Connected to Long Flash Two Seconds On Two Seconds Off Repetitively for 15 Minutes Heater ha...

Страница 20: ...or Check for Housing Alignment Tighten Set Screw s on Fan Make sure Set Screw s are Tightened Against Flat s of Motor Shaft Yes Clean the Fan Wheel with Compressed Air or Soft Brush Defective Motor or...

Страница 21: ...is read adjust outlet pressure as necessary B If gas pressure is not read replace the control valve Defective Igniter Perform Continuity Check and Replace Igniter If Necessary Clean Flame Sensor with...

Страница 22: ...wire only to determine if part is defective Replace the part IMMEDIATELY or do not operate unit until properly serviced NEVER operate a heater with a jumper wire used to bypass a safety device as a te...

Страница 23: ...ons Verify Proper Voltage with a Voltage Tester Contact a Qualified electrician if Proper voltage is not Present No No Yes Is Proper Voltage Supplied to Selector Switch from Power Cord No Problem Moto...

Страница 24: ...SOLENOID S TRANSFORMER 240V 24V L E D INDICATOR GROUND POWER CORD IND L1 HSI HSIG L2 W PSI FSI GV PSO FSG C HSI CONTROL SELECTOR SWITCH HEAT OFF VENT TRANSFORMER FOR OPTIONALTHERMOSTAT CONTROL INSTAL...

Страница 25: ...oard which sends and receives voltages to various controls in an automatic hot surface ignition system An important safety feature of the control board is that it will shu down the entire heater there...

Страница 26: ...Parts Identification PARTS SCHEMATIC 26...

Страница 27: ...2 Chamber Heat 20024 23 Door Right 20757 24 Latch Assembly for case assembly and control box 20959 25 Case Assembly with Doors and Latches 21286 26 Hinge 05868 27 Door Left 20756 28 Harness 9 wire 9 m...

Страница 28: ...ERCORD EXIT HOLE 21008WARNING WASHDOWN INSTRUCTIONS 20575 WIRING DIAGRAM 21012WARNING FIRE AND EXPLOSION HAZARD INSIDE OF MOTOR END ACCESS DOOR 21280 BADGE AUSTRALIAN LISTED 20453WARNING HOT SURFACES...

Страница 29: ...and Transformer to Wire Nut Brown 19 cm 20662 Wire Toggle Switch to Wire Nut Blue 15 cm 20663 Wire Toggle Switch to Transformer Blue 14 cm 20664 Wire Burner to Ground Green Yellow 168 cm 21192 Wire Ga...

Страница 30: ...ate of purchase by the end user Warranty is automatic if a component is found defective within 12 months of the date code marked on the part If the defect occurs more than 12 months later than the dat...