In the event of a power loss your KwiKool® resumes operation when the power is
restored if in the ON position. All operational functions are preserved in the memory
of the control.
BioKool™ systems are factory equipped with an internal high lift condensate
pump. KwiKool condensate pumps are able to pump the condensation collec-
ted in the reservoir of the pump to a drain or other area approved for the
discharge water by attaching ¼” I.D. tubing to the ¼” O.D. barbed condensate
outlet. KwiKool condensate pumps are equipped with a pump safety cut-off
that prevents accidental water overflow by shutting your KwiKool down and
alerting operators with an audible alarm and displays CP on the control.
Call
1-800-KWIKOOL
if this alarm is present on start up. The most common
reason for this alarm to activate during operation is restricted water flow thru the
discharge tubing or excessive discharge line connected to the system. Automa-
tic reset upon correction of the condensate flow. If this alarm is engaged the
system will not operate in cool or fan mode.
Condensate Pump & High Level Alarm
BUILT IN SAFEGUARDS
Automatic Restart