Ceiling Kit Discharge Outlet
(condenser exhaust) & Discharge
Make Up (fresh air inlet)
Align the holes of the flange to the holes located on the top of the unit. Attach to the top
of the KwiKool BioKool™ system using the specially factory supplied fasteners.
Attach each duct to the flanges on the replacement ceiling panel(s); secure the duct to
each flange using the supplied clamps.
Install the replacement ceiling panel(s) in the ceiling grid with the duct attached,
connect the open end of the duct to the flanges on your KwiKool and secure with
supplied clamps. Your KwiKool must have fresh make up air going to the condenser to
operate at peak performance. Ensure the ducted space can absorb the heat load. It must
be open enough to keep hot air from returning.
KwiKool
®
two duct ceiling kit (CK-12) is designed especially for KBIO models. BioKool™ is
regularly used for primary, supplemental or standby cooling. In order to ensure you are
able to utilize 100% of the units rated capacity and without creating a negative pressure
in your conditioned space, use KwiKool’s custom ceiling kit. KwiKool’s exclusive IO
integral condenser system isolates both the condenser discharge air and the condenser
make up air from the conditioned space.
The ceiling kit is comprised of flanges with foam tape, fasteners, two (2) eight foot lengths of
flexible duct, duct clamps, and one 24 x 24 in. replacement ceiling tile.
Normally, the make up air and discharge air is directed
above a drop ceiling. However, the ceiling kit is not limited
to ceiling use and may be placed or fastened to any vertical
surface or wall. The important thing is space must be well
ventilated and large enough for the heat load to be
absorbed. Condenser discharge air is prevented from
entering the make up air inlet by way of a factory installed
deflector on your Ceiling Kit. The deflector should
discharge from the rear duct. If the condenser discharge
and return space is unventilated, or unable to handle the
exiting heat load, KBIO’s high pressure safety switch will
t
r
i
p
.
If this occurs, you will get an “HP” on the control panel.
Resolve this by finding appropriate ventilation then reset
the high pressure switch per the instructions in the
troubleshooting guide. For areas with a closed ceiling or
no ceiling use the double flange ceiling kit method, or
extended duct method.
OPTIONAL CEILING KIT
A Well Ventilated Space
13