2.3 E r r o r List
Error
Display Text
Description
E004
Module: Short-circuit power supply
Overload at power supply of external extension module
E005
Module: External voltage applied
Power supply of external extension module independent
E006
Pressure sensor: Cable break
Overload or cable break at pressure sensor input
E007
Pressure sensor: Measurement
negative
Negative value measured at pressure sensor input
E009
Pressure sensor: Overload of power supply
Outlet of pressure sensor power supply overloaded
E010
Pressure sensor: external voltage applied at
outlet
External voltage applied to outlet of “pressure sensor
power supply”
E011
Thermal element: Short-to-ground
Short-circuit to ground at thermal element line
E012
Thermal element: Short-circuit
supply
Short-circuit at thermal element supply line
E013
Thermal element: Cable break
Cable break at thermal element
E014
Chimney fan: Error (zero-cross) leading edge
Line frequency not identified
E015
Chimney fan: Error (4Hz) leading edge
Line frequency not plausible
E016
Chimney fan: Error (timing) leading edge
Leading edge outlet not correct
E100
24V supply: too low
24V supply too low
E101
24V supply: too high
24V supply too high
E102
CFC10: Internal error
Deviating internal 5V-supply
E103
CFC10: Internal error
Deviating reference voltage
E104
CFC10: Internal error
External watchdog was triggered
E105
CFC10: Internal error
Malfunction of internal relay actuator
E106
CFC10: Error memory full
Error memory is full
E200
CFC10: Differential pressure too low
Differential pressure too low
E201
CFC10: Differential pressure value not
plausible
Pressure sensor does not send plausible values
E202
Chimney fan: no feedback
No feedback signal from chimney fan
E203
Chimney fan: Unexpected feedback
Unexpected feedback signal from chimney fan
E204
CFC10: Set pressure not reached
Set pressure is not reached
E500
CFC10: Checksum for parameters invalid
CRC32 sum of parameters is not correct
E501
CFC10: Parameters outside value margin
At least one parameter is outside the permissible value
margin
E502
CFC10: Not enough memory
Overflow of dynamic memory
E503
CFC10: Hardware self-test failed
Periodic hardware self-test was not completed
successfully