ADVR-054

 

WARNING 

1. Some  generators  even  when  working  at  high  voltage  are  factory  set  to  sense  at  lower  voltages. 

Remember to set the DIP SW 2 to the sensing voltage not the working voltage of the generator even do 
sometimes it can be the same. If you have a 480/277V generator but you have the sensing wires C and A 
connected to 240 Volts move DIP SW 2 to ON 

 

Another example are rental units with multi-voltage output with a switches for Y, YY, Delta & ZZ output, 

but  sensing  is  always  at  240V  from  T7  and  T9  even  though  the  generator  is  running  sometimes  at 
480/277V. 

2. All voltage readings are to be taken with an average-reading voltmeter Meggers and high-potential test 

equipment must not be used. Use of such equipment could damage the AVR. 

3. Improper  setting  of  under-frequency  protection  could  cause  the  output  voltage  of  the  unit  to  drop  or 

become  unstable  under  with  changes  in  load.  Avoid  making  any  changes  to  the  U/F  setting  unless 
necessary.

 

 

SECTION 1 : SPECIFICATION 

Sensing Input (A, C) Average Reading 

Static Power Dissipation

 

  Voltage 

170 

 260 Vac @ 220 Vac, 1 phase 2 wires

 

  Max.8 watts 

   

340 

 520 Vac @ 440 Vac, 1 phase 2 wires   

   

220/440 Vac, DIP switch setting 

Under Frequency Protection (Factory Presets) 

  Frequency 

50/60 Hz, DIP switch setting 

  50 Hz system presets knee point at 45 Hz 

 

  60 Hz system presets knee point at 55 Hz 

Power Input (B, C)

 

 

  Voltage 

100 

 300 Vac, 1 phase 2 wires 

Over Excitation Voltage Protection

 

  Frequency 

40 

 60 Hz

 

  Set point 78 Vdc +/- 6% @ power input 220 Vac 

 

  Time delay 5 secs. This function can be turned off. 

Excitation Output (F+, F-) 

 

  220V 1 phase Continuous 63 Vdc 5A 

Voltage Thermal Drift 

   

Max. 90 Vdc 7A for 10 secs. 

  Less than 3% at temperature range -40 to +70 

˚C 

  Resistance 

Min. 15 ohms,    Max. 100 ohms 

 

  Fuse Spec. 

Slow blow 5 x 20mm S505-5A 

Under-Frequency Knee Point Thermal Drift 

 

  Less than +/- 0.1 Hz at -

40 to +70 ˚C 

External Voltage Adjustment (EXT.VR)

 

 

  Max. +/- 3.5% @ 1K ohm 1 watt potentiometer 

Environment 

 

  Operating Temperature  -40 to +60 

˚C 

Voltage Regulation

 

  Storage Temperature 

-40 to +85 

˚C 

  Less than +/- 0.5% ( with 4% engine governing ) 

  Relative Humidity 

Max. 95% 

 

  Vibration 

5 Gs @ 60 Hz 

Build Up Voltage

 

 

  5 Vac 25 Hz residual volts at power input terminal 

Dimensions 

 

  121.0 (L) x 81.0 (W) x 44.5 (H) mm 

Soft Start Ramp Time 

  4.76 (L) x 3.19 (W) x 1.75 (H) inch 

  3 s/- 10% 

 

 

Weight 

Typical System Response 

  270 g +/- 2% 

  Less than 20 milliseconds 

  0.6 lb +/- 2% 

 

 

EMI Suppression

 

 

  Internal electromagnetic interference filtering 

 

Содержание ADVR-054

Страница 1: ...t Qianzhen Dist Kaohsiung City 80664 Taiwan ADVR 054 Universal Hybrid Analog Digital Voltage Regulator Operation Manual Self Excited 5 Amp Analog Digital Voltage Regulator For shunt and auxiliary windings generators With over excitation and lost of sensing protection Use with Kutai EP200 Paralleling Module for parallel operation ...

Страница 2: ...e 170 260 Vac 220 Vac 1 phase 2 wires Max 8 watts 340 520 Vac 440 Vac 1 phase 2 wires 220 440 Vac DIP switch setting Under Frequency Protection Factory Presets Frequency 50 60 Hz DIP switch setting 50 Hz system presets knee point at 45 Hz 60 Hz system presets knee point at 55 Hz Power Input B C Voltage 100 300 Vac 1 phase 2 wires Over Excitation Voltage Protection Frequency 40 60 Hz Set point 78 V...

Страница 3: ...ch ATTENTION 1 Only qualified technicians should install and operate the AVR 2 The voltage regulator may be installed at any suitable location on the generator set dimensions are shown in Figure 1 It is recommended that unit is mounted vertically with the green resistors on the regulator upwards to achieve the best cooling effect 3 All AC voltage sensing readings are average value only Figure 1 Ou...

Страница 4: ...anging loads If the setting is too high the voltage is unstable but if set too low the response is sluggish We recommend using an analog DC voltage meter on F F and adjust STAB for the lowest amount of voltage fluctuation needle movement 3 Last Under Frequency U F adjustment The U F is Factory preset and needs no adjustments put in rare applications Use the U F LED as a guide When this LED is ON t...

Страница 5: ...ADVR 054 Aux winding 1000 Ohm EXT VR G Field R S N T ADVR 054 Figure 5 340 520V sensing connection Figure 6 Auxiliary Winding connection Package include 4 pcs of M4 L25 Round head bolts and 2 pcs of terminal jumpers Use only replacement fuses specified in this user manual Appearance and specifications of products are subject to change for improvement without prior notice Refer to Section 3 for DIP...