ADVR-054

 

SECTION 3 : DIP SWITCH SETTINGS, LED INDICATORS AND ADJUSTMENTS 

 

VOLT Voltage Adjustment 

The  adjustment  range  is  set  by 
SW2.

 

 

U/F Under Frequency Protection 

50 Hz system preset at 45 Hz, 

60 Hz system preset at 55 Hz, 

To change the setting, see the 
Adjustment Step 3. 
 

U/F LED 

Under Frequency Protection status. 

 

A

Sensing Input terminal 

 

A to C: 170 

– 520 Vac 

 

F+ , F-

Connect to generator 

excitation field. 

 

B

Power Input terminal 

 

B to C: always less than 300 Vac 

C

Sensing Input and Power Input terminals 

 

EXT.VR Ext Potentiometer, 

1K  ohm  1W.  Keep  shorted  when 
not in use. 

ADJUSTMENTS AFTER GENERATOR IS STARTED : 

1. First,  turn  VOLT  and  STAB  trimpots  fully  counterclockwise  before  starting  the  generator.  Set  the  engine 

governor to 50 or 60 Hz. Start the generator and wait till it reaches rated speed. Now slowly turn VOLT trimpot 
clockwise to increase the working voltage. (If you use an external potentiometer, set it to the center position). 
Keep EXT. VR shorted when not in use. 

2. Next,  slowly  adjusting  the  STAB  trimpot  etting  (clockwise),  this  change  the  response  time  of  the  AVR  to 

changing loads. If the setting is too high the voltage is unstable but if set too low the response is sluggish. We 
recommend  using  an  analog  DC  voltage  meter  on  F,  F+  and  adjust  STAB  for  the  lowest  amount of  voltage 
fluctuation (needle movement). 

3. Last,  Under  Frequency  (U/F)  adjustment.  (The  U/F  is  Factory  preset  and  needs  no  adjustments)  put  in  rare 

applications.  Use  the  U/F  LED  as  a  guide.  When  this  LED  is  ON  the  circuit  is  operational  turning  off  the 
regulators output. To recalibrate, adjust the generator speed to the new U/F kneel point, usually 5 Hz under 
rated speed (Hz) then set the U/F trim-pot to the point at which the U/F LED just changes from off to on rated 
speed (Hz) then set the U/F trimpot to the point at which the U/F LED just changes from off to on. Adjustment 
range for 50Hz system is 40 to 51 Hz. For 60 Hz system the range is 50 to 61 Hz. 

 

Over Excitation (O/E) LED 

When the excitation voltage is greater than 35% 
of  input  power  voltage,  the  LED  will  lit  after  5 
sec. If the DIP switch SW3 set at OFF then it will 
also shut off excitation output at the same time. 

DIP Switches 

System Freqency 

SW1

 

ON:

50 Hz, 

OFF:

60 Hz 

Sensing Input 

SW2

 

ON:

220V, 

OFF:

440V 

O/E Protection 

SW3 ON:

Disable

, OFF:

Enable

 

 

STAB Stability Setting 

With  No  Load,  slowly  turn  the 
STAB 

counterclockwise 

until 

voltage  becomes  unstable  then 
turn clockwise about 1/5 turn.

 

 

-

+

S

F

40

51

(50)

(61)

ADVR-054

Содержание ADVR-054

Страница 1: ...t Qianzhen Dist Kaohsiung City 80664 Taiwan ADVR 054 Universal Hybrid Analog Digital Voltage Regulator Operation Manual Self Excited 5 Amp Analog Digital Voltage Regulator For shunt and auxiliary windings generators With over excitation and lost of sensing protection Use with Kutai EP200 Paralleling Module for parallel operation ...

Страница 2: ...e 170 260 Vac 220 Vac 1 phase 2 wires Max 8 watts 340 520 Vac 440 Vac 1 phase 2 wires 220 440 Vac DIP switch setting Under Frequency Protection Factory Presets Frequency 50 60 Hz DIP switch setting 50 Hz system presets knee point at 45 Hz 60 Hz system presets knee point at 55 Hz Power Input B C Voltage 100 300 Vac 1 phase 2 wires Over Excitation Voltage Protection Frequency 40 60 Hz Set point 78 V...

Страница 3: ...ch ATTENTION 1 Only qualified technicians should install and operate the AVR 2 The voltage regulator may be installed at any suitable location on the generator set dimensions are shown in Figure 1 It is recommended that unit is mounted vertically with the green resistors on the regulator upwards to achieve the best cooling effect 3 All AC voltage sensing readings are average value only Figure 1 Ou...

Страница 4: ...anging loads If the setting is too high the voltage is unstable but if set too low the response is sluggish We recommend using an analog DC voltage meter on F F and adjust STAB for the lowest amount of voltage fluctuation needle movement 3 Last Under Frequency U F adjustment The U F is Factory preset and needs no adjustments put in rare applications Use the U F LED as a guide When this LED is ON t...

Страница 5: ...ADVR 054 Aux winding 1000 Ohm EXT VR G Field R S N T ADVR 054 Figure 5 340 520V sensing connection Figure 6 Auxiliary Winding connection Package include 4 pcs of M4 L25 Round head bolts and 2 pcs of terminal jumpers Use only replacement fuses specified in this user manual Appearance and specifications of products are subject to change for improvement without prior notice Refer to Section 3 for DIP...

Отзывы: